Nortek R8GE Series Скачать руководство пользователя страница 4

4

 WARNING:

The information listed below and on the next page 

must be followed during the installation, service, 

and operation of this unit. Unqualified individuals 

should not attempt to interpret these instructions 

or install this equipment. Failure to follow safety 

recommendations could result in possible damage 

to the equipment, serious personal injury or death.

•  The installation must conform with the National Fuel Gas 

Code (ANSI 2223.1, NFPA-54). Canadian installations must 

conform with CAN/CGA-B149 installation codes.

•  The installer must comply with all local codes and regulations 

which govern the installation of this type of equipment. 

Local codes and regulations take precedence over any 

recommendations contained in these instructions. Consult 

local building codes and the National Electrical Code (ANSI 

CI) for special installation requirements.

• This equipment contains liquid and gaseous refrigerant 

under high pressure. Installation or servicing should only be 

performed by qualified trained personnel thoroughly familiar 

with this type equipment.

•  All electrical wiring must be completed in accordance with 

local, state and national codes and regulations and with the 

National Electric Code (ANSI/NFPA 70) or in Canada the 

Canadian Electric Code Part 1 CSA C.22.1.

•  Air Ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standards for 

Installation of Air Conditioning and Ventilation Systems” 

(NFPA 90A), “Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems” (NFPA 

90B), these instructions, and all applicable local codes.

•  Install this unit only in a location and position as specified on 

page 5

. This unit is designed only for outdoor installations 

and should be located with consideration of minimizing the 

length of the supply and return ducts. Consideration should 

also be given to the accessibility of fuel, electric power, 

service access, noise, and shade.

•  Before beginning the installation, verify that the unit model 

is correct for the job. The unit model number is printed on 

the data label. Follow all precautions in the literature, on 

tags, and on labels provided with the equipment. Read and 

thoroughly understand the instructions provided with the 

equipment prior to performing the installation and operational 

checkout of the equipment.

•  Use only with the type of gas approved for this unit. Refer 

to the unit rating plate.

•  Provide adequate combustion and ventilation air to the unit. 

See 

Figure 1 (page 5)

.

•  Provide adequate clearances around the air vent intake 

terminal. See page 8.

•  Combustion products must be discharged outdoors. Connect 

this unit to an approved vent system only, as specified on 

page 8

.

• Never test for gas leaks with an open flame. Use a 

commercially available soap solution to check all connections. 

See 

page 14

.

• Consult 

Table 10 (page 22)

, and the rating plate for the 

proper circulating air flow and temperature rise. It is important 

that the duct system be designed to provide the correct flow 

rates and external pressure rise. An improperly designed 

duct system can result in nuisance shutdowns, and comfort 

or noise issues.

•  Installation of equipment may require brazing operations. 

Installer must comply with safety codes and wear appropriate 

safety equipment (safety glasses, work gloves, fire 

extinguisher, etc.) when performing brazing operations.

•  This equipment is 

NOT

 to be used for temporary heating of 

buildings or structures under construction.

REQUIREMENTS & CODES

This unit must be installed in accordance with instructions 

outlined in this manual, all applicable local building codes, 

and the current revision of the National Fuel Gas Code 

(NFPA54/ANSI Z223.1) or the Natural Gas and Propane 

Installation Code, CAN/CGA B149.1.

Additional codes listed below are for reference purposes only 

and do not necessarily have jurisdiction over local or state 

codes. Local codes and regulations take precedence over 

any recommendations contained in these instructions. Always 

consult with local authorities before installing any gas appliance.

Combustion & Ventilation Air

•  US: National Fuel Gas Code (NFGC), Air for Combustion and 

Ventilation

• CANADA: Natural Gas and Propane Installation Codes 

(NSCNGPIC), Venting Systems and Air Supply for Appliances

Duct Systems

• US and CANADA: Air Conditioning Contractors Association 

(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors 

National Association (SMACNA), or American Society of Heating, 

Refrigeration, and Air Conditioning Engineers (ASHRAE) 

Fundamentals Handbook

Electrical Connections

•  US: National Electrical Code (NEC) ANSI/NFPA 70

•  CANADA: Canadian Electrical Code CSA C22.1

Gas Piping & Gas Pipe Pressure Testing

•  US: NFGC and National Plumbing Codes

•  CANADA: NSCNGPIC

General Installation

•  US: Current edition of the NFGC and the NFPA 90B. For copies, 

contact the National Fire Protection Association Inc., Batterymarch 

Park, Quincy, MA 02269; or American Gas Association, 400 N. 

Capitol, N.W., Washington DC 20001 or www.NFPA.org

•  CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA 

International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, 

M9W 1R3 Canada

Safety

•  US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation 

Standards, Warm Air Heating and Air Conditioning Systems ANSI/

NFPA 90B.

•  CANADA: CAN/CGA-B149.1 and .2–M00 National Standard of 

Canada. (NSCNGPIC)

Содержание R8GE Series

Страница 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Страница 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Страница 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Страница 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Страница 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Страница 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Страница 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Страница 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Страница 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Страница 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Страница 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Страница 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Страница 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Страница 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Страница 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Страница 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Страница 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Страница 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Страница 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Страница 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Страница 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Страница 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Страница 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Страница 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Страница 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Страница 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Страница 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Страница 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Отзывы: