background image

4

Locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit. Select a solid, level position, 

preferably on a concrete slab, slightly above the grade 

level, and parallel to the home. If possible, select a site 

for the unit that is as close as possible to the proposed 

return grille location. 

DO NOT PLACE UNIT UNDER 

THE HOME.

• The unit should be located with consideration of 

minimizing the length of the supply and return ducts 

with no sharp radius bends. If practical, place the heat 

pump and its ducts in an area where they will be shaded 

from the afternoon sun, when the heat load is greatest.

•  Consideration should also be given to availability of 

electric power, service access, noise, and shade.

• Overhead obstructions, poorly ventilated areas, and 

areas subject to accumulation of debris should be 

avoided. The hot condenser air must be discharged up 

and away from the home, and if possible, in a direction 

with the prevailing wind. Do not place the unit in a 

confined space. See 

Figure 14 (page 15)

 and 

Table 

4 (page 15)

 for unit dimensions.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 

performance. For minimum clearances to obstructions, 

see 

Figure 1

.

Minimum Clearances

Minimum clearances MUST be maintained from adjacent 

structures to provide room for proper servicing and air 

circulation. DO NOT install unit in a confined or recessed 

area that will allow discharge air from the unit to re-circulate 

into the condenser air inlet, through the coil. See 

Figure 1

.

Service Access Clearance:

Blower access panel side .......................................... 24”

Electrical compartment access panel side ............... 12”

Clearance between overhang and top

of unit  .................................................................. 72”

Clearance around condenser coil area to

wall or shrubs (excludes duct panel side) .................. 12”

Clearances to Combustibles:

Combustible Base (wood or Class A, B, or C)

Roof Covering Material .............................................. 0”

Supply & return Air Ducts .......................................... 0”

Duct Connection SSide ............................................. 0”

REQUIREMENTS & CODES

•  All electrical wiring must be completed in accordance 

with local, state & national codes and regulations and 

with the National Electric Code (ANSI/NFPA 70) or in 

Canada the Canadian Electric Code Part 1 CSA C.22.1.

• The installer must comply with all local codes and 

regulations which govern the installation of this type 

of equipment. Local codes and regulations take 

precedence over any recommendations contained in 

these instructions. Consult local building codes and the 

National Electrical Code (ANSI CI) for special installation 

requirements.

• Air Ducts must be installed in accordance with the 

standards of the National Fire Protection Association 

“Standards for Installation of Air Conditioning and 

Ventilation Systems” (NFPA 90A), “Standard for 

Installation of Residence Type Warm Air Heating and Air 

Conditioning Systems” (NFPA 90B), these instructions, 

and all applicable local codes.

• Consult 

Table 2 (page 8)

, and the rating plate for 

the proper circulating air flow and temperature rise. It is 

important that the duct system be designed to provide 

the correct flow rates and external pressure rise. An 

improperly designed duct system can result in nuisance 

shutdowns, and comfort or noise issues.

•  This unit is designed for outdoor installations only 

and should be installed as described in Locating 

the Heat Pump.

GENERAL INFORMATION

Single packaged heat pumps are ready for easy and 

immediate installation and can be readily connected into the 

high static duct system of a home. This unit is completely 

assembled, wired, and run tested at the factory. The only 

connections needed for installation are the supply and 

return ducts, the line voltage, and thermostat wiring. Use 

of components other than those specified may invalidate 

AHRI Certification, Code Agency Listing, and limited 

warranty on the air conditioner.

Before You Install this Unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage should be filed 

immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

12"

12"

24"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

0"

Figure 1. Minimum Unit Clearances

Содержание PPH3RF Series

Страница 1: ...n important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage These instructions are primarily intended to assist qualified individuals experienced in the proper installation of this appliance Some local codes requir...

Страница 2: ... Test Pins 10 Clearing Defrost Board Fault Codes 10 Electric Heat Package optional 10 Outdoor Thermostat Options 10 HUD Outdoor Thermostat Option 10 2nd Stage Thermostat Option 10 STARTUP ADJUSTMENTS 11 Pre Start Checklist 11 Start Up Procedure 11 Air Circulation 11 System Heating 11 System Cooling 11 Short Cycle Protection 11 Emergency Heat 11 Forced Defrost Mode Field Test 11 Anti Short Cycle Ti...

Страница 3: ...ancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations or may cause lung cancer Fiberglass wool may also cause eye irritation skin sensitization or other allergic responses in susceptible individuals Always wear goggles disposable gloves long sleeved shirt and appropriate...

Страница 4: ...e installation of this type of equipment Local codes and regulations take precedence over any recommendations contained in these instructions Consult local building codes and the NationalElectricalCode ANSICI forspecialinstallation requirements Air Ducts must be installed in accordance with the standards of the National Fire Protection Association Standards for Installation of Air Conditioning and...

Страница 5: ...ioningandVentilation Systems NFPA 90A Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems NFPA90B theseinstructions andallapplicable codes NFPA publications are available by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioni...

Страница 6: ... is in a corner or under a table if a minimum two inch clearance is available 1 Start the installation from under the home by cutting a small hole in the sub floor Determine how the floor joist location will affect cutting the opening needed for the return air box NOTE Floor joists are generally located on 16 centers leaving 14 3 8 between joists 2 After measuring the return air box approximately ...

Страница 7: ...ctrical Code ANSI NFPA 70 or the CSA C22 1 Electrical Code Use the grounding lug provided in the control box for grounding the unit Line Voltage It is recommended that the line voltage to the unit be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit Anelectricaldisconnectmustbelocatedwithinsight of and readily accessible to the unit This switch sh...

Страница 8: ... 6 8 10 25 4 4 6 10 30 3 4 6 8 35 3 4 6 8 40 2 3 4 6 45 2 3 4 6 50 2 3 4 6 55 1 2 3 4 60 Wire Size based on N E C for 60 type copper conductors Table 1 Copper Wire Size AWG 1 voltage drop Table 2 Airflow Data MODEL NUMBER MOTOR TAP EXTERNAL STATIC PRESSURE DROP IN WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CFM HEAT RISE CF...

Страница 9: ...ric heating operation CAUTION To avoid personal injury or property damage make certain that the motor leads cannot come into contact with any metal components of the unit 3 Verify the required speed from the airflow data found in Table 2 page 8 Place appropriate wire on the appropriate motor speed tap for the required airflow 4 Check all factory wiring per the unit wiring diagram and inspect the f...

Страница 10: ... soon as the jumper is removed the defrost cycle will end as determined by the typical criteria To determine operating status or fault conditions refer to Table 3 for diagnostic description Clearing Defrost Board Fault Codes Fault codes can be removed from memory through the use of the test pins This is accomplished by shorting the two test pins momentarily more than 1 second while there is no Y1 ...

Страница 11: ... supply registers System Cooling Set the thermostat s system mode to COOL and the fan mode to AUTO Change the thermostat temperature selector below the existing room temperature Allow the cooling system to operate for several minutes and check for the discharge of cool air at the supply registers Short Cycle Protection The control circuit is equipped with a time delay feature for protection agains...

Страница 12: ...ing of each heating and cooling season or more frequently if required Inspect the condensate drain and outdoor coil at the beginning of each cooling season Remove any debris Clean the outdoor coil and louvers as necessary using a mild detergent and water Rinse thoroughly with water Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as neces...

Страница 13: ...rigerant when below curve Remove refrigerant when above curve Figure 11 Charging Chart for 3 Ton Units Figure 10 Charging Chart for 2 Ton Units Liquid Temperature Deg F 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Q7RF X24K Charging Chart Cooling Remove refrigerant when above curve Add refrig...

Страница 14: ...refrigerant when above curve Add refrigerant when below curve Figure 13 Charging Chart for 5 Ton Units Figure 12 Charging Chart for 4 Ton Units Liquid Temperature Deg F 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95 100 105 110 115 120 125 130 135 Liquid Pressure psig Remove refrigerant when above curve Add refrigerant when below curve Q7RF X48K ...

Страница 15: ...01 1 75 Ø Electric Heater Power Supply 1 125 Ø Power Supply 0 875 Ø Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NUMBER LENGTH L WIDTH W HEIGHT H A B X24K 49 35 30 2 29 00 2 48 X36KA 49 35 38 2 35 02 2 48 X48K 63 35 38 2 35 02 2 48 X60K 63 35 38 2 35 02 2 48 Table 4 Physical Data ...

Страница 16: ...G DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour utili...

Страница 17: ...ower before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour utiliser les fils conducteurs adapté à ...

Страница 18: ...NG DIAGRAM NOTES 1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Employez uniquement des conducteurs en cuiver 3 Ne convient pas aux installations de plus de 150V a la terre 4 Remplacement pour util...

Страница 19: ...19 ...

Страница 20: ...lowthemanufacturer srefrigerant chargingandairflowinstructions Failuretoconfirm proper charge and airflow may reduce energy efficiency and shorten equipment life INSTALLATION ADDRESS CITY STATE UNIT MODEL UNIT SERIAL INSTALLER NAME CITY STATE Unit installed minimum clearances shown on page 4 YES NO Has the owner s information been reviewed with the customer YES NO Has the literature package been l...

Отзывы: