Nortek DS4BF Скачать руководство пользователя страница 15

15

table 3. coreSense

tm

 diagnostics & troubleshooting

StatUS led

StatUS led deScription

StatUS led troUBleShooting inFormation

Solid Green 

“RUN”

Module has power and

operating normally

Supply voltage is present at module terminals

Solid Red 

“TRIP”

Thermostat demand signal Y is 

present, but the compressor is not 

running

1.  Compressor protector is open

•  Check for high head pressure

•  Check compressor supply voltage

2.  Outdoor unit power disconnect is open

3.  Compressor circuit breaker or fuse(s) is open

4.  Broken wire or connector is not making contact

5.  High pressure switch open if present in system

6.  Compressor contactor has failed open

alert Flash codes

Yellow “ALERT”

Flash Code 1

long run time

Low Refrigerant Charge

Compressor is running extremely 

long run cycles

1.  Low refrigerant charge

2.  Evaporator blower is not running

•  Check blower relay coil and contacts

•  Check blower motor capacitor

•  Check blower motor for failure or blockage

•  Check evaporator blower wiring and connectors

•  Check indoor blower control board
•  Check thermostat wiring for open circuit

3.  Evaporator coil is frozen

•  Check for low suction pressure

•  Check for excessively low thermostat setting

•  Check evaporator airfl ow (coil blockages or return air fi lter)
•  Check ductwork or registers for blockage

4.  Faulty metering device

•  Check TXV bulb installation (size, location and contact)

•  Check if TXV/fi xed orifi ce is stuck closed or defective

5.  Liquid line restriction (fi lter drier blocked if present in system)
6.  Thermostat is malfunctioning

•  Check thermostat sub-base or wiring for short circuit

•  Check thermostat installation (location, level)

Yellow “ALERT”

Flash Code 2

compressor (pressure) trip

High Refrigerant Charge Discharge 

pressure out of limits or compressor 

overloaded

1.  Condenser fan is not running

•  Check fan capacitor

•  Check fan wiring and connectors

•  Check fan motor for failure or blockage

2.  High head pressure

•  Check high pressure switch if present in system

•  Check if system is overcharged with refrigerant

•  Check for non-condensable in system

3.  Condenser coil poor air circulation (dirty, blocked, damaged)

4.  Return air duct has substantial leakage

Yellow “ALERT”

Flash Code 3

pressure Switch cycling

Compressor is running only briefly 

due to pressure switch cycling

1.  Time delay relay or control board defective

2.  If high pressure switch present go to Flash Code 2 information

Yellow “ALERT”

Flash Code 4

locked rotor

1.  Run capacitor has failed

2.  Low line voltage (contact utility if voltage at disconnect is low)

•  Check wiring connections

3.  Excessive liquid refrigerant in compressor

4.  Compressor bearings are seized

•  Measure compressor oil level

Yellow “ALERT”

Flash Code 5

compressor (moderate run)

trip

1.  Evaporator blower is not running

•  Check blower relay coil and contacts

•  Check blower motor capacitor

•  Check blower motor for failure or blockage

•  Check evaporator blower wiring and connectors

•  Check indoor blower control board

•  Check thermostat wiring for open circuit

2.  Faulty metering device

•  Check TXV bulb installation (size, location and contact)

•  Check if TXV/fi xed orifi ce is stuck closed or defective

3.  Condenser coil poor air circulation (dirty, blocked, damaged)

4.  Low refrigerant charge

coreSenSe troUBleShooting

Содержание DS4BF

Страница 1: ...ckage for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE Installation Instructions important SAFETY INFORMATION 2 Air conditioner INSTallATION 3 Genera...

Страница 2: ...tions in the literature on tags and on labels provided with the equipment Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operation...

Страница 3: ...g the unit Locating the Air Conditioner Survey the job site to determine the best location for mounting the outdoor unit The outdoor unit should be installed no closer than 18 inches from the outside...

Страница 4: ...of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code CSA C22 1 and or local codes Pre E...

Страница 5: ...is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem Alert identification codes are also listed in Table 3 page 15 Compressor Protection TheCoreS...

Страница 6: ...e fan and compressor cycle off with the thermostat NOTE The blower should also stop unless fan mode is set to the ON position System Heating optional 1 Set the thermostat s system mode to HEAT and the...

Страница 7: ...ded Deviationsfromratedairflowsor non listedcombinationsmayrequiremodificationtothe expansion device and refrigerant charging procedures for proper and efficient system operation The refrigerant charg...

Страница 8: ...abel Charging charts are valid for a variety of indoor return air conditions and are most influenced by the outdoor ambienttemperature outdoorfanoperationandtheunit operatingvoltage Beforeusingthesech...

Страница 9: ...onductors suitable for 105 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circu...

Страница 10: ...R C S S C R L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR OUTDOOR FAN MOTOR Y2 Y L R C P DC SOL CSC C R Y2 Y LPS HPS CORESENSE COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC Contactor Coil CCH Cr...

Страница 11: ...le Phase 60 Hz WIRING DIAGRAM 7110150 1209 FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE BLACK BLUE YELLOW BLUE BLACK 208 230V H C F CCH R C S S C H L2 T2 COMPRESSOR CONTACTS L1 T1 COMPRESSOR FAN MOTOR...

Страница 12: ...tection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avan...

Страница 13: ...ACTS L1 T1 COMPRESSOR CSC C Y2 Y LPS HPS COMPRESSOR SOLENOID COIL 24 VOLT FIELD CONNECTIONS CC 208 230V Two Stage Split System Air Conditioner Outdoor Section With ECM Outdoor Motor Single Phase 60 Hz...

Страница 14: ...class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Couper le courant avant de faire letretien 8 Employez uniquement des conducte...

Страница 15: ...functioning Check thermostat sub base or wiring for short circuit Check thermostat installation location level Yellow ALERT Flash Code 2 Compressor Pressure Trip High Refrigerant Charge Discharge pres...

Страница 16: ...seized Measure compressor oil level Red LOCKOUT Flash Code 5 Yellow Off Compressor Moderate Run Trip 1 Evaporator blower is not running Check blower relay coil and contacts Check blower motor capacito...

Страница 17: ...17...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...______________________ Unit Installed Minimum clearances per Figure 1 page 3 YES NO INSTALLER NAME CITY________________________ STATE_________________ REFRIGERATION SYSTEM Was unit given 24 hr warm up...

Отзывы: