Nortek B64EM Series Скачать руководство пользователя страница 16

16

B64EM

A-CABINET

SWITCH SETTINGS

0 = OFF, 1 = ON

COOLING OR HEATING AIRFLOW (CFM)

DRY COIL ESP

1/5 2/6 3/7 4/8

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

0

0

0

585

550

520

460

420

405

1

0

0

0

710

670

650

610

560

530

475

440

0

1

0

0

845

790

765

715

680

655

625

580

1

1

0

0

890

865

840

785

760

710

680

655

0

0

1

0

955

925

900

850

825

790

770

720

1

0

1

0

1030

995

975

940

910

870

840

815

0

1

1

0

1115

1085

1060

1020

995

965

925

905

1

1

1

0

1155

1130

1095

1070

1040

1010

985

950

0

0

0

1

1200

1175

1145

1110

1085

1060

1025

1000

1

0

0

1

1240

1215

1195

1170

1140

1110

1080

1060

0

1

0

1

1320

1290

1265

1240

1215

1185

1160

1130

1

1

0

1

1355

1330

1305

1280

1255

1220

1200

1175

0

0

1

1

1405

1375

1345

1325

1295

1275

1250

1210

1

0

1

1

1440

1415

1385

1355

1325

1290

1255

1215

0

1

1

1

1465

1425

1390

1355

1320

1290

1260

1215

1

1

1

1

1465

1425

1390

1355

1320

1290

1260

1215

B64EM

B-CABINET

SWITCH SETTINGS

0 = OFF, 1 = ON

COOLING OR HEATING AIRFLOW (CFM)

DRY COIL ESP

1/5 2/6 3/7 4/8

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

0

0

0

600

550

430

390

1

0

0

0

660

610

540

460

425

0

1

0

0

830

750

695

640

580

520

1

1

0

0

860

825

765

690

630

600

525

485

0

0

1

0

935

895

835

790

710

655

620

585

1

0

1

0

1045

975

920

875

830

795

720

685

0

1

1

0

1095

1040

995

950

900

850

805

750

1

1

1

0

1155

1105

1060

1010

965

920

870

825

0

0

0

1

1230

1185

1140

1090

1045

1010

965

920

1

0

0

1

1285

1260

1210

1165

1125

1080

1040

1010

0

1

0

1

1330

1290

1245

1205

1170

1125

1085

1045

1

1

0

1

1395

1365

1315

1275

1235

1205

1160

1130

0

0

1

1

1450

1405

1375

1335

1295

1260

1220

1180

1

0

1

1

1490

1450

1410

1385

1340

1300

1270

1230

0

1

1

1

1530

1485

1460

1425

1380

1350

1310

1280

1

1

1

1

1530

1490

1465

1425

1390

1350

1310

1285

B64EM

C-CABINET

SWITCH SETTINGS

0 = OFF, 1 = ON

COOLING OR HEATING AIRFLOW (CFM)

DRY COIL ESP

1/5 2/6 3/7 4/8

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0

0

0

0

720

610

510

420

335

--

--

--

1

0

0

0

880

780

685

595

505

425

--

--

0

1

0

0

1035

940

850

765

690

620

560

--

1

1

0

0

1130

1050

975

900

830

760

695

630

0

0

1

0

1275

1195

1120

1050

985

920

865

815

1

0

1

0

1365

1295

1230

1165

1100

1035

975

915

0

1

1

0

1490

1425

1360

1300

1240

1185

1130

1075

1

1

1

0

1580

1525

1465

1410

1355

1300

1245

1190

0

0

0

1

1685

1630

1575

1520

1465

1410

1355

1300

1

0

0

1

1750

1695

1640

1585

1535

1480

1430

1375

0

1

0

1

1840

1785

1730

1680

1625

1575

1530

1480

1

1

0

1

1895

1850

1800

1750

1700

1650

1595

1540

0

0

1

1

1980

1930

1880

1830

1780

1735

1685

1640

1

0

1

1

2045

1995

1945

1895

1845

1795

1750

1700

0

1

1

1

2095

2045

1995

1945

1895

1845

1800

1755

1

1

1

1

2170

2120

2070

2020

1970

1925

1875

1830

Table 6. B64EM (FSHE) Airflow Data

Airflow Data

Содержание B64EM Series

Страница 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury...

Страница 2: ...wer Continuously 11 Selecting Continuous Low Speed Fan Operation 11 Turning the Blower Off 11 System Cooling 11 System Heating 11 Selecting Minimum Electric Heat Airflow 11 Blower Configurations 11 De...

Страница 3: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Страница 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Страница 5: ...needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready for vertical upflow installation a...

Страница 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Страница 7: ...ntact with valve when gas is escaping Always ensure adequate ventilation is present during the depressurization process Address any uncertainties before proceeding Failure to comply with this warning...

Страница 8: ...ondensables to prevent low efficiency operation or damage to the unit The suggested range of evacuation is 350 500 microns 9 Charge the system with refrigerant Refer to the outdoor unitinstallationman...

Страница 9: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Страница 10: ...5 Connect blue blower limit wires according to Heater Kit Installation Instructions and the corresponding Wiring Diagram If a heater kit is not installed 1 Remove the 2 wire plug of the air handler b...

Страница 11: ...n B64EM models B64VM models automatically set the heating speed based on the amount of installed heat The A B switch must be set appropriately for the unit cabinet size For C sized cabinets the A B sw...

Страница 12: ...cted airflow while the system is in the lo cool mode and 100 of the selected airflow while in hi cool mode Units with an FSHE control scheme B64EM have a control board that includes a 7 segment displa...

Страница 13: ...or on the blower and motor as part of the annual inspection Blower Fan Wheel Inspect the blower wheel blades for accumulations of dirt and clean if necessary Inspect mounting nut for tightness when do...

Страница 14: ...typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12 3 4 No B 43 5 16 19 11 16 18 1 4 No Tall...

Страница 15: ...l Drain Pan Coil Assembly Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Uppe...

Страница 16: ...0 795 720 685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0...

Страница 17: ...TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TON 1300 4 TON 700 2 TON 700 1350 750 750 1400 800 2 5 TON 800 2 5 TON 1450 850 850 1500 875 875 1550 890 950 1600 5 TON 930 1050 3 TON 1650 950 1150 3...

Страница 18: ...ING 0 OFF 1 ON AIRFLOW CFM 5 6 7 8 0 0 0 0 1100 0 0 0 1 1200 0 0 1 0 1250 0 0 1 1 1300 0 1 0 0 1350 0 1 0 1 1400 0 1 1 0 1450 0 1 1 1 1500 1 0 0 0 1550 1 0 0 1 1600 1 0 1 0 1650 1 0 1 1 1700 1 1 0 0 1...

Страница 19: ...W1 W2 EHEAT ON 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 8 KW 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Страница 20: ...fter 5 seconds delay 15 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 30 seconds delay 20 KW Stage 1 Heat on instantly Co...

Страница 21: ...cal Heat Pump with 2 Stage Air Handler G R W2 C O Y1 Thermostat O Y1 R C G R W E Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with 2 Stage Air Handler Typical 2 Stage Heat Pump with 2 Stage A...

Страница 22: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 12 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 13 Two Stage Contro...

Страница 23: ...R ECM BLOWER Figure 14 Fixed Speed Motor Control Board GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTP...

Страница 24: ...entation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac ut...

Страница 25: ...e tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cuivre 105 C du m me gabarit WIRING DIAGRAM CONNECT TO W1...

Страница 26: ...tterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the...

Страница 27: ...27...

Страница 28: ...10436960 NEW Specifications illustrations subject to change without notice or incurring obligations 08 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved...