background image

5

REFRIGERANT CHARGING

 WARNING:

*SA3BD4M Split System Air Conditioners are 

shipped charged with R410A refrigerant and 

ready for installation. If repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. Under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

After refrigerant line connections and expansion device 

installation are completed, it is required that you leak check 

and evacuate the indoor section and all line connections 

(using proper methods) before finalizing the full system 

refrigerant charge.

Note: additional charging instructions located near the end 

of this document.  (See 

page 9

)

•  Refer to the Quick Reference Data sheet for additional 

charging information for this unit with the approved Nortek 

indoor units.  For reference, these units are listed in the 

AHRI Directory with all approved combinations of indoor 

coils and units.  Installing these outdoor units on systems 

that combine it with an indoor coil or unit not listed there, is 

not recommended.   When approved combinations of indoor 

and outdoor units are installed, they should be set up to 

operate within the airflow and other operational parameters 

prescribed in all of the units provided instructions and 

technical specifications.

• Installation of this outdoor unit with other, non-listed 

indoor unit combinations may require different airflows, 

expansion devices, charge values and system setup from 

the instructions provided here and with this unit.  Nortek 

does not recommend the use of this product in unlisted 

combinations, and the system performance and efficiency 

values of unlisted unit combinations may be different than 

the listed product combinations.

•  *SA3BD4M outdoor units with non-AHRI listed indoor coils 

are not recommended. Deviations from rated airflows or 

non-listed combinations may require modification to the 

expansion device and refrigerant charging procedures for 

proper and efficient system operation.

•  The refrigerant charge can be checked and adjusted through 

the service ports provided external to the outdoor unit. Use 

only gage line sets which have a “Schrader” depression 

device present to actuate the valve.

• An automatic high-pressure switch is factory-installed 

installed in these units and is located on the discharge 

line after the unit's compressor. This switch is designed to 

protect the system when very high pressures occur during 

abnormal conditions. Under normal conditions, the switch 

is closed. If the system pressure rises to 650 psig, then 

the switch will open and de-energize the contactor coil 

in the outdoor unit. The switch will close again once the 

liquid pressure decreases to 460 psig and allow the unit 
to restart.

ELECTRICAL WIRING

 WARNING:

To avoid risk of electrical shock, personal 

injury, or death, disconnect all electrical power 

to the unit before performing any maintenance 

or service. The unit may have more than one 

electrical supply.
Label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause 

improper and dangerous operation.

• All electrical connections must be in compliance with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For Canadian installations the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

 Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper voltage wiring.

  If replacing an existing unit, verify that the: current wiring, 

unit disconnect and circuit breaker is properly sized and 

rated for the new units requirements.  Verify that information 

with the MCA and MOP values on the unit nameplate.

 Verify factory wiring is in accordance with the unit wiring 

diagrams 

Figure 5 (page) 11

). Inspect for loose 

connections.

Содержание 1SN18K

Страница 1: ...stallation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE IMPORTANT SAFETY INFORMATION 2 AIR CO...

Страница 2: ...checkout of the equipment When refrigerant tubing and electrical wiring penetrates a structures envelope the openings should be made to be suitably water tight after their installation This unit is de...

Страница 3: ...for unobstructed airflow through the outdoor coil must be maintained in order to achieve rated performance See Figure 1 for minimum clearances to obstructions Overhead obstructions Figure 1 poorly ve...

Страница 4: ...nds and contact of the refrigerant lines with metal surfaces Refrigeranttubingshouldbesupportedinamannerthatthe tubing will not vibrate or abrade during system operation Tubing should be kept clean of...

Страница 5: ...quire modification to the expansion device and refrigerant charging procedures for proper and efficient system operation Therefrigerantchargecanbecheckedandadjustedthrough the service ports provided e...

Страница 6: ...ccordance with the unit wiring diagram and the unit rating plate Connect the line voltage leads to the terminals on the contactor inside the control compartment Use only copper wire for the line volta...

Страница 7: ...al and Figure 3 for panel installation Inspect the electrical connections for tightness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or...

Страница 8: ...erify that the thermostat is set to the stand by or off setting And the fan switch is set to automatic or off Start Up Procedures The thermostat s function mode should be set to OFF and the fan mode s...

Страница 9: ...troubleshooting a system The system should be charged to match the superheat or subcooling targets as previously noted and not to match the system pressures Follow the same procedure described in 4b a...

Страница 10: ...Quick Reference Data sheet 2 Calculate the amount of additional refrigerant needed for thelinesetlengthoftheactualinstallation Thisinformation is on the first page of the unit s QRD Quick Reference Da...

Страница 11: ...itable for 105 deg C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and...

Страница 12: ...llon MO Nortek Global HVAC LLC 2022 All Rights Reserved REPLACEMENT PARTS Replacement parts are available through your distributor Please have the complete model and serial number of the unit when ord...

Отзывы: