If the outdoor temperature is below 35 degrees F:
After completing the refrigerant line connections, leak
checking the system, and evacuating the indoor section
and all line connections (using proper methods), perform
the following steps:
1. Determine the recommended charge addition (if applicable)
for the system being installed. This information is in the
unit’s QRD (Quick Reference Data sheet).
2. Calculate the amount of additional refrigerant needed for
the line set length of the actual installation. This information
is on the first page of the unit’s QRD (Quick Reference
Data sheet).
3. Weigh in the additional charge amounts determined by
steps 1 and 2 above.
4. Return to the system when the outdoor temperature is 35
degrees F or higher and follow the steps defined in step 4
of the “If the outdoor temperature is between 35 degrees
and 65 degrees F" or "If the outdoor temperature is 65
degree F or higher” sections above as applicable.