NORMAGRUP NormaLux C24 Скачать руководство пользователя страница 1

P2843 SEP20

Central

Battery

System

C

24

User guide

Содержание NormaLux C24

Страница 1: ...P2843 SEP20 Central Battery System C 24 User guide...

Страница 2: ...of the unit 8 Screens directory 9 MENU screen 10 INFO screen 11 CONTROLS screen 12 OPTIONS screen 13 SETTINGS screen 14 Distances andwire sections calculation 15 Index of failures 16 Index of warnings...

Страница 3: ...t is possible to control the centrals from a PC 24Vdc permanent outputs available 3 24 Vdc 50w max relay outputs controlled by BUS In this gued you will find detailed information about the C24 central...

Страница 4: ...mmunication YES Batteries Duration Total output voltage I max A Input phase monitor Output control Potential free contact relay Functioning indicator Battery functioning indicator Fail Power supply in...

Страница 5: ...nting 3 Remove the 4 screws and open the front cover 1 Step Use the ring under the PCB to move the circuit Break open the pre cutted holes for the wiring 2 Step 2 1 3 4 ring Central Battery System C 2...

Страница 6: ...he fitting to the wall using the three holes in the housing 3 Step Connect the fitting with 230 Vac y 50 Hz between L y N and the earth connection 4 Step 1 2 3 L N 4 Central Battery System C 24 User g...

Страница 7: ...rt of the housing and connect them Close the central 5 Step 1 2 4 C24 300 mounting Take out the screw and remove the frontal panel by pulling the cover up and then pulling the cover towards you 1 Step...

Страница 8: ...back plate to the wall 2 Step Screw the housing of the central to the back plate that has been fixed to the wall and secure the screws firmly 3 Step 1 2 3 4 5 6 1 2 3 4 Central Battery System C 24 Us...

Страница 9: ...l 4 Step Central Battery System C 24 User guide The maximum number of luminaires to be connected in a central can be calculated following the table on page 2 with a maximum power limint of 3 5A on eac...

Страница 10: ...means of the SL Sense Loop output OUT 1 Output 1 OUT 2 Output 2 OUT 3 Output 3 OUT 4 Output 4 24v y 3 5A max outputs protected against short circuit by fuse and electronic cut These outputs include an...

Страница 11: ...ntial free contact relay that indicates that there is a failure in the central normally open BAT1 Battery connection The capacity depends on the model BAT2 Battery connection The capacity depends on t...

Страница 12: ...ng scheme Triphasic phase monitor L1 L2 L3 N PE General lighting L1 L2 L3 N PE General lighting L1 L3 N PE General lighting Triphasic phase monitor Monophasic phase monitor SL 10 Central Battery Syste...

Страница 13: ...riphasic phase monitor L1 L2 L3 N PE General lighting L1 L2 L3 N PE General lighting L1 L3 N PE General lighting Triphasic phase monitor Monophasic phase monitor OUT AUX SL SL CBS 1 CBS 2 Central Batt...

Страница 14: ...e LED on means the battery has been discharged totally The indication should be re armed Output 1 The LED on means that output 1 is activated Output 2 The LED on means that output 2 is activated Outpu...

Страница 15: ...il SL output has been restored Also the OUT AUX contact will be open allowing other centrals interconnected between them by means of this output to ge tinto EMERG_EXT mode as well EMERGENCY MODE The d...

Страница 16: ...equalize the capacity of both batteries This way when the batteries are charging both of them will start charging from the same point This process may take a few minutes Functioning logic EQUAL MODE...

Страница 17: ...ut there is no failure the current voltage output value will be displayed in ampers 8 Screens directory Using the up down left and right buttons located in the right part it is possible to browse thro...

Страница 18: ...TEST CARRIED OUT 2 1 1 5 10 POWER SUPPLY CONSUMED BY THE CENTRAL 2 1 1 5 11 RESET 2 1 2 CONTROLS 2 1 2 1 OUT 1 2 1 2 2 OUT 2 2 1 2 3 OUT 3 2 1 2 4 OUT 4 2 1 2 5 ALL 2 1 3 OPTIONS 2 1 3 1 OFF BAT DISCH...

Страница 19: ...AL INFO SCREEN 2 4 Information about the minimum programmed voltage to detect failures 5 ADDITIONAL INFO SCREEN 3 4 Time left for the next functioning test to be carried out 6 ADDITIONAL INFO SCREEN 4...

Страница 20: ...s out a functional test on the 4 outputs EXIT It exits the MENU screen to get back to the main screen 10 INFO screen Press INFO in the MENU screen to access this option The navigation method is the sa...

Страница 21: ...utput voltage and actual voltage consumed will be displayed as well It will also inform about the minimum failure current programmed This is the minimum current that the output should consume If that...

Страница 22: ...If it is 0 means there is no voltage SL SL Input with internal Pull Up This input is used to supervise the emergency mode functioning If the input is 1 it means that it has been jumpered and if it is...

Страница 23: ...event log will show several different parameters related to the functioning of the central It has eleven screens Screen 1 Time that the central has been working Screen 2 How long the power supply has...

Страница 24: ...of the batteries and capacity Press ACCEPT to exit 11 CONTROLS screen It controls each output and enables the user to check each output s functioning mode Once one output is selected we can check if i...

Страница 25: ...his paramenter the failure current value can be manually chosen If this value is 0 means that the failure current will not be checked 12 OPTIONS screen There are three options in this menu OFF BAT DIS...

Страница 26: ...ounds in the central There are three sounds that can be abled disabled EMER Makes it possible to able disable a sound alarm when the fitting starts to be powered by a battery FAIL Ables disables a sou...

Страница 27: ...en this event is programmed the first test will carried out in the same week After this this will be carried out in the selected interval The maximum interval that can be set is four weeks Due to the...

Страница 28: ...link in case there is any failure in any of the luminaires connected LED OUT 2 Makes it possible to set the status of the charge led of the luminaires connected to output 2 LED OUT 3 Makes it possible...

Страница 29: ...the central will show up an autonomy failure CAPACITY Selector of the capacity of the connected batteries SELFPROTECTION Sets a protection over the central s power supply INFO Shows the information a...

Страница 30: ...2 A 3 A 1 A 2 A 3 A 147 74 49 245 123 82 1 5 mm2 2 5 mm2 Distances for two wires cable and charge at the end of line Example of the distributed charges Maximum wiring lengths depending on the section...

Страница 31: ...OUT3_BROKEN Fuse in output 3 broken F12 F_FUSIBLE_OUT4_BROKEN Fuse in output 4 broken F13 F_CAR_FAIL Charger failure F14 F_OUT1_SHORTCIRCUIT Output 1 in shortcut F15 F_OUT2_SHORTCIRCUIT Output 2 in sh...

Страница 32: ...F_RANGE W38 W_OUT1_OFF_OVERCURRENT Output 1 has been switched off as it exceeds the total power of the output and has its self protection activated W39 W_OUT2_OFF_OVERCURRENT W40 W_OUT3_OFF_OVERCURREN...

Страница 33: ...NOTES...

Страница 34: ...l Battery System C 24 User guide NormaGrup Technology S A Parque Tecnol gico de Asturias Parcela 10 33428 Llanera Asturias Espa a T 34 985 267 100 F 34 985 266 992 normagrup normagrup com www normagru...