4

Figure 1. minimum unit clearances

12"

12"

24"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

0"

gEnERal inFoRmation

Single packaged heat pumps are ready for easy and 

immediate installation and can be readily connected into 

the high static duct system of a home. This unit is completely 

assembled, wired, and run tested at the factory. The only 

connections needed for installation are the supply and 

return ducts, the line voltage, and thermostat wiring. Use 

of components other than those specified may invalidate 

AHRI Certification, Code Agency Listing, and limited 

warranty on the air conditioner.

before You install this unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. 

It is recommended that the area to be conditioned be 

completely insulated and vapor sealed.

  Check the electrical supply and verify the power supply 

is adequate for unit operation. If there is any question 

concerning the power supply, contact the local power 

company.

  All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage 

prior to installing the equipment at the job site. Verify 

coil fins are straight. If necessary, comb fins to remove 

flattened or bent fins. Claims for damage (apparent or 

concealed) should be filed immediately with the carrier.

  Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read 
all instructions before installing the unit.

locating the Heat Pump

•  Survey the job site to determine the best location for 

mounting the outdoor unit.

•  Choose  an  appropriate  location  that  minimizes  the 

length of the supply and return air ducts.

•  Overhead  obstructions,  poorly  ventilated  areas,  and 

areas subject to accumulation of debris should be 

avoided.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must be maintained in order to achieve rated 
performance. See 

Figure 1

 for minimum clearances to 

obstructions.

•  Consideration  should  also  be  given  to  availability  of 

electric power, service access, noise, and shade.

air Duct System

Air ducts must be installed in accordance with the standards 

of the National Fire Protection Association “Standard for 

Installation of Air Conditioning and Ventilation Systems” 

(NFPA 90A), “Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems” (NFPA 

90B), these instructions, and all applicable codes. NFPA 

publications are available by writing to: National Fire 

Protection Association, Batterymarch Park, Quincy, ME 

02269 or visit www.NFPA.org on the web.

•  Design the duct work according to methods described 

by the Air Conditioning Contractors of America (ACCA). 

•  The  supply  duct  system,  including  the  number  and 

type of registers, will have much more effect on the 

performance of the system than any other factor. The 

REQuiREmEntS & coDES

•  All electrical wiring must be completed in accordance 

with local, state & national codes and regulations and 

with the National Electric Code (ANSI/NFPA 70) or in 

Canada the Canadian Electric Code Part 1 CSA C.22.1.

•  The  installer  must  comply  with  all  local  codes  and 

regulations which govern the installation of this type 

of equipment. Local codes and regulations take 

precedence over any recommendations contained in 

these instructions. Consult local building codes and the 

National Electrical Code (ANSI CI) for special installation 

requirements.

•  This equipment contains liquid and gaseous refrigerant 

under high pressure. Installation or servicing should only 

be performed by qualified trained personnel thoroughly 

familiar with this type equipment.

•  Air  Ducts  must  be  installed  in  accordance  with  the 

standards of the National Fire Protection Association 

“Standards for Installation of Air Conditioning and 

Ventilation Systems” (NFPA 90A), “Standard for 

Installation of Residence Type Warm Air Heating and Air 

Conditioning Systems” (NFPA 90B), these instructions, 

and all applicable local codes.

•  Consult 

Table 1, (page 8)

, and the rating plate for 

the proper circulating air flow and temperature rise. It is 

important that the duct system be designed to provide 

the correct flow rates and external pressure rise. An 

improperly designed duct system can result in nuisance 

shutdowns, and comfort or noise issues.

•  This unit is designed for outdoor installations only and 

should be positioned as described in Locating the Heat 

Pump.

•  Follow  all  precautions  in  the  literature,  on  tags,  and 

on labels provided with the equipment. Read and 

thoroughly understand the instructions provided with 

the equipment prior to performing the installation and 

operational checkout of the equipment.

•  The installer should become familiar with the units wiring 

diagram before making any electrical connections to the 
unit. See the unit wiring label or 

Figure 13 (page 16) 

Figure 14 (page 17)

.

Содержание Q5RF-X24KA

Страница 1: ... plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require li...

Страница 2: ...Electric Heat Package optional 10 Startup adjustments 11 Pre Start Checklist 11 Start Up Procedure 11 Air Circulation 11 System Heating 11 System Cooling 11 Short Cycle Protection 11 Emergency Heat 11 Adjustment of Refrigerant Charge 11 Charging the Unit in AC Mode 11 Charging the Unit in Heating Mode 12 Forced Defrost Mode Field Test 12 Anti Short Cycle Timer Test 12 Heating Mode 12 Cooling Mode ...

Страница 3: ...ing gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product known to the state of California to cause cancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations Fiberglass ...

Страница 4: ...ence Type Warm Air Heating and Air Conditioning Systems NFPA 90B these instructions and all applicable codes NFPA publications are available by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the ...

Страница 5: ... if air is lost to the outside through leaks in the duct system Ducts that are collapsed or restricted by foreign objects will also prevent adequate air flow Supply Air Figure 2 Return Supply Air Collars 14 Duct Dimples Return Air Transition Duct Screws Installing Return Supply Air Collars If the supply and return collars are supplied with the unit they will be located in the supply duct They can ...

Страница 6: ...on the furnace Figure 4 Drain Trap P Trap Elbow SINGLE DUCT APPLICATION MULTIPLE DUCT APPLICATION Figure 3 Typical Duct Applications Condensate Drainage A 3 4 condensate fitting extends out of the side of the unit as shown in Figure 4 The drain trap shipped in the electricalcompartment mustbeinstalledtopreventwater from collecting inside the unit 1 Thread the elbow provided with the unit into the ...

Страница 7: ...to the contactor Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Use of rain tight conduit is recommended See the unit wiring label for proper high and low voltage wiring Make all electrical connections in accordance with all applicable codes and ordinances CAUTION Label al...

Страница 8: ...lizes a 2 speed condenser fan motor this motor will operate on low speed when in low cooling heating and on high speed when in high cooling heating Ambient Sensor Mounting For optimum performance of the heat pump system the ambient sensor Figure 6 page 9 must be mounted on the outside of the unit 1 Removethemountingbracketandallhardwareincluded in the packet 2 Remove star bushing from 7 8 hole in ...

Страница 9: ...frost curves settings The factory default setting does not include a 30 second compressor delay function and has a 40 F defrost terminate temperature If additional defrost time is needed a higher terminate temperature is available by selecting a different demand curve NOTE The 30 second compressor delay occurs when the unit enters defrost and exits defrost The delay function is optional and based ...

Страница 10: ...ost Board Outdoor Thermostat optional Blower Relay Compressor Solenoid ECM Motor if applicable Y1 1st Stage Heat Pump Y2 2nd Stage Heat Pump W1 1st Stage Auxillary Heat Green from blower relay 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Boa...

Страница 11: ...l minutes and check for the discharge of cool air at the supply registers Short Cycle Protection The control circuit is equipped with a time delay feature for protection against short cycling With the system operating in the cooling mode gradually raise the thermostat temperature setting until the system de energizes Immediatelylowerthethermostattemperature to the original setting and verify that ...

Страница 12: ...essureincreasesabove20psig Thelow pressureswitchinterruptsthethermostatinputstotheunit NOTE When the switch opens and then closes there will be a 5 minute short cycling delay before the unit can energize High Pressure Switch The high pressure switch is factory installed and located in the compressor discharge line internal to the unit The Unit MAINTENANCE WARNING To prevent electrical shock person...

Страница 13: ...48 Table 3 Physical Data A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View L W 18 01 Electric Heater Power Supply Power Supply Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Figure 8 Unit Dimensions Top View Side View ...

Страница 14: ...ESSURE PSIG LIQUID TEMPERATURE F X36KA CHARGING CHART Rem ove refrigerant when above curve Add refrigerant when below curve Figure 9 Charging Chart for 2 Ton Units 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID PRESSURE PSIG LIQUID TEMPERATURE F Rem ove refrigerant when above curve Add refrigerant when below curve X2...

Страница 15: ...ove refrigerant when above curve Add refrigerant when below curve Figure 12 Charging Chart for 5 Ton Units Figure 11 Charging Chart for 4 Ton Units 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID PRESSURE PSIG LIQUID TEMPERATURE F X48KA CHARGING CHART Rem ove refrigerant when above curve Add refrigerant when below cur...

Страница 16: ... CAPACITOR OUTDOOR MOTOR COMPRESSOR TRASFORMER 240V 24V COM RED YELLOW BLACK BLACK ORANGE BLUE COMPRESSOR CONTACTOR TO POWER SUPPLY GND TO T STAT BLUE FAN REVERSING VALVE COIL YELLOW YELLOW BLACK BLACK BLACK 4 3 2 1 8 7 6 5 9 HIGH SPEED BLOWER RELAY 24V BLOWER RELAY YELLOW BLACK YELLOW BLUE 5 4 3 2 1 N G L C BLOWER MOTOR C S R BROWN YELLOW ORANGE BROWN BLUE ORANGE RED GREY GREY GREEN YELLOW BLACK ...

Страница 17: ...UL CAPACITOR COMPRESSOR TRASFORMER 240V 24V HIGH SPEED BLOWER RELAY 24V BLOWER RELAY COM RED BLACK BLACK BROWN COMPRESSOR CONTACTOR TO T STAT BLUE DF2 YELLOW WHITE YELLOW GREEN REVERSING VALVE COIL BLACK BLACK YELLOW BLACK YELLOW YELLOW BLACK BLUE BLUE YELLOW YELLOW 5 4 3 2 1 N G L C BLOWER MOTOR 1 2 3 L N G OUTDOOR MOTOR TO POWER SUPPLY GND C S R BROWN YELLOW ORANGE BROWN BLUE ORANGE GREY GREY GR...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ...per Figure 1 page 4 YES NO INSTALLER NAME CITY_________________ STATE____________ ELECTRICAL SYSTEM Electrical connections tight YES NO Linevoltagepolaritycorrect YES NO Rated Voltage _________________________ VOLTS L1 L2 Volts ___________________________ VOLTS Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO PROP...

Отзывы: