background image

12

•  If the pressure measured in step 1 is less than the 

required liquid refrigerant pressure determined in 

step 3, then there is too little charge in the system. 

Add refrigerant and repeat steps 1 through 3 until 

the system is correctly charged.

charging the unit in Heating mode

1.  Evacuate the refrigerant system.
2. Weigh in the proper charge as indicated on the unit 

label. Unit charge MUST be verified in cooling season.

3. Verify the unit is operating properly according to the 

System Heating section on 

page 11

.

Forced Defrost mode (Field test)

• 

When the 

tESt

 terminals are shorted with the 

Y

 input 

active and pressure switches closed, the ACST will 

be eliminated and the compressor contactor output 

energizes within 2 seconds. When the 

tESt

 terminals 

are shorted for more than 9 seconds with the Y input 

active, the control will be placed into a forced defrost 

mode.

 

notE:

 The coil temperature sensor does not need to 

be cold when the unit is forced into defrost.

•  After  the 

tESt

 input is shorted, the defrost mode 

will terminate in 13.7 minutes or less or when the coil 

temperature is above the terminate set point or when 

the thermostat 

Y

 input is removed, whichever occurs 

first.

anti Short cycle timer test

The 5 minute time delay feature can be bypassed by 

shorting the 

tESt

 pins together.

Heating Mode

When the 

tESt

 pins are shorted together for more than 

1 second, the control will switch between defrost mode 

and heating mode as described in the Forced Defrost 

Mode procedure section.
Cooling Mode

When the 

tESt

 pins are shorted together for more than 

1 second, the Anti Short Cycle Timer will be bypassed.

comPonEnt FunctionS

low Pressure Switch

The low pressure switch is factory installed and located in 

the suction line internal to the unit. The switch is designed 

to protect the compressor if a loss of charge occurs. Under 

normal conditions, the switch is closed.
If the suction pressure falls below 5 psig, then the switch will 

open and de-energize the unit. The switch will close again 

once the suction pressure increases above 20 psig. The low 

pressure switch interrupts the thermostat inputs to the unit.  

notE:

 When the switch opens and then closes, there 

will be a 5 minute short cycling delay before the unit can 

energize.

High Pressure Switch

The high pressure switch is factory installed and located 

in the compressor discharge line internal to the unit. The 

unit maintEnancE

 WaRning:

to prevent electrical shock, personal injury, or 

death, disconnect all electrical power to the unit 

before performing any maintenance or service. 

the unit may have more than one electrical supply.

Proper maintenance is important to achieve optimum 

performance from the heat pump. The ability to properly 

perform maintenance on this equipment requires certain 

mechanical skills and tools. If you do not possess these 

skills, contact your dealer for maintenance. Consult your 

local dealer about the availability of maintenance contracts. 

Routine maintenance should include the following:

•  Inspect and clean or replace air filters at the beginning 

of each heating and cooling season, or more frequently 

if required.

•  Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

•  Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season. Service 

as necessary.

 caution:

the unit should never be operated without a 

filter in the return air system. Replace disposable 

filters with the same type and size.

•  Do not attempt to add additional oil to motors unequipped 

with oil tubes. The compressor is hermetically sealed 

at the factory and does not require lubrication.

switch is designed to de-energize the system when very 

high pressures occur during abnormal conditions. Under 

normal conditions, the switch is closed.
If the discharge pressure rises above 650 psig, the switch 

will open and de-energize the unit. The switch will close 

again once the discharge pressure decreases to 460 

psig. The high pressure switch interrupts the thermostat 

inputs to the unit. 

notE:

 When the switch opens and 

then closes, there will be a 5 minute short cycling delay 

before the unit can energize.

Содержание Q5RF-X24KA

Страница 1: ... plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or property damage Theseinstructionsareprimarilyintendedtoassistqualifiedindividualsexperiencedintheproper installation of this appliance Some local codes require li...

Страница 2: ...Electric Heat Package optional 10 Startup adjustments 11 Pre Start Checklist 11 Start Up Procedure 11 Air Circulation 11 System Heating 11 System Cooling 11 Short Cycle Protection 11 Emergency Heat 11 Adjustment of Refrigerant Charge 11 Charging the Unit in AC Mode 11 Charging the Unit in Heating Mode 12 Forced Defrost Mode Field Test 12 Anti Short Cycle Timer Test 12 Heating Mode 12 Cooling Mode ...

Страница 3: ...ing gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product known to the state of California to cause cancer Disturbing the insulation of this product during installation maintenance or repair will expose you to fiberglass wool Breathing this material may cause respiratory irritations Fiberglass ...

Страница 4: ...ence Type Warm Air Heating and Air Conditioning Systems NFPA 90B these instructions and all applicable codes NFPA publications are available by writing to National Fire Protection Association Batterymarch Park Quincy ME 02269 or visit www NFPA org on the web Design the duct work according to methods described by the Air Conditioning Contractors of America ACCA The supply duct system including the ...

Страница 5: ... if air is lost to the outside through leaks in the duct system Ducts that are collapsed or restricted by foreign objects will also prevent adequate air flow Supply Air Figure 2 Return Supply Air Collars 14 Duct Dimples Return Air Transition Duct Screws Installing Return Supply Air Collars If the supply and return collars are supplied with the unit they will be located in the supply duct They can ...

Страница 6: ...on the furnace Figure 4 Drain Trap P Trap Elbow SINGLE DUCT APPLICATION MULTIPLE DUCT APPLICATION Figure 3 Typical Duct Applications Condensate Drainage A 3 4 condensate fitting extends out of the side of the unit as shown in Figure 4 The drain trap shipped in the electricalcompartment mustbeinstalledtopreventwater from collecting inside the unit 1 Thread the elbow provided with the unit into the ...

Страница 7: ...to the contactor Use only copper wire for the line voltage power supply to this unit Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit Use of rain tight conduit is recommended See the unit wiring label for proper high and low voltage wiring Make all electrical connections in accordance with all applicable codes and ordinances CAUTION Label al...

Страница 8: ...lizes a 2 speed condenser fan motor this motor will operate on low speed when in low cooling heating and on high speed when in high cooling heating Ambient Sensor Mounting For optimum performance of the heat pump system the ambient sensor Figure 6 page 9 must be mounted on the outside of the unit 1 Removethemountingbracketandallhardwareincluded in the packet 2 Remove star bushing from 7 8 hole in ...

Страница 9: ...frost curves settings The factory default setting does not include a 30 second compressor delay function and has a 40 F defrost terminate temperature If additional defrost time is needed a higher terminate temperature is available by selecting a different demand curve NOTE The 30 second compressor delay occurs when the unit enters defrost and exits defrost The delay function is optional and based ...

Страница 10: ...ost Board Outdoor Thermostat optional Blower Relay Compressor Solenoid ECM Motor if applicable Y1 1st Stage Heat Pump Y2 2nd Stage Heat Pump W1 1st Stage Auxillary Heat Green from blower relay 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug AMBIENT SENSOR COIL SENSOR TEST L R C Y O W2 IN W2 OUT COND FAN AMBIENT AMBG COILG COIL DEMAND DEFROST CONTROL BOARD M PRESS SW REV VALVE Demand Defrost Boa...

Страница 11: ...l minutes and check for the discharge of cool air at the supply registers Short Cycle Protection The control circuit is equipped with a time delay feature for protection against short cycling With the system operating in the cooling mode gradually raise the thermostat temperature setting until the system de energizes Immediatelylowerthethermostattemperature to the original setting and verify that ...

Страница 12: ...essureincreasesabove20psig Thelow pressureswitchinterruptsthethermostatinputstotheunit NOTE When the switch opens and then closes there will be a 5 minute short cycling delay before the unit can energize High Pressure Switch The high pressure switch is factory installed and located in the compressor discharge line internal to the unit The Unit MAINTENANCE WARNING To prevent electrical shock person...

Страница 13: ...48 Table 3 Physical Data A 3 Opening for 12 Diameter Supply Duct 9 15 17 50 9 0 Opening for 14 Diameter Return Duct 10 15 5 5 B 1 3 15 Rear View L W 18 01 Electric Heater Power Supply Power Supply Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Figure 8 Unit Dimensions Top View Side View ...

Страница 14: ...ESSURE PSIG LIQUID TEMPERATURE F X36KA CHARGING CHART Rem ove refrigerant when above curve Add refrigerant when below curve Figure 9 Charging Chart for 2 Ton Units 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID PRESSURE PSIG LIQUID TEMPERATURE F Rem ove refrigerant when above curve Add refrigerant when below curve X2...

Страница 15: ...ove refrigerant when above curve Add refrigerant when below curve Figure 12 Charging Chart for 5 Ton Units Figure 11 Charging Chart for 4 Ton Units 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 LIQUID PRESSURE PSIG LIQUID TEMPERATURE F X48KA CHARGING CHART Rem ove refrigerant when above curve Add refrigerant when below cur...

Страница 16: ... CAPACITOR OUTDOOR MOTOR COMPRESSOR TRASFORMER 240V 24V COM RED YELLOW BLACK BLACK ORANGE BLUE COMPRESSOR CONTACTOR TO POWER SUPPLY GND TO T STAT BLUE FAN REVERSING VALVE COIL YELLOW YELLOW BLACK BLACK BLACK 4 3 2 1 8 7 6 5 9 HIGH SPEED BLOWER RELAY 24V BLOWER RELAY YELLOW BLACK YELLOW BLUE 5 4 3 2 1 N G L C BLOWER MOTOR C S R BROWN YELLOW ORANGE BROWN BLUE ORANGE RED GREY GREY GREEN YELLOW BLACK ...

Страница 17: ...UL CAPACITOR COMPRESSOR TRASFORMER 240V 24V HIGH SPEED BLOWER RELAY 24V BLOWER RELAY COM RED BLACK BLACK BROWN COMPRESSOR CONTACTOR TO T STAT BLUE DF2 YELLOW WHITE YELLOW GREEN REVERSING VALVE COIL BLACK BLACK YELLOW BLACK YELLOW YELLOW BLACK BLUE BLUE YELLOW YELLOW 5 4 3 2 1 N G L C BLOWER MOTOR 1 2 3 L N G OUTDOOR MOTOR TO POWER SUPPLY GND C S R BROWN YELLOW ORANGE BROWN BLUE ORANGE GREY GREY GR...

Страница 18: ...18 ...

Страница 19: ...19 ...

Страница 20: ...per Figure 1 page 4 YES NO INSTALLER NAME CITY_________________ STATE____________ ELECTRICAL SYSTEM Electrical connections tight YES NO Linevoltagepolaritycorrect YES NO Rated Voltage _________________________ VOLTS L1 L2 Volts ___________________________ VOLTS Has the thermostat been calibrated YES NO Is the thermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO PROP...

Отзывы: