background image

7

3)  Lift the cap out of the unit. (The cap can 

be pushed up from the bottom by reaching 
through the fork slot).

4)  Cover the horizontal duct opening with the 

horizontal duct cap. The insulation will be 
on the indoor side.

5)  Fasten the cover with screws to seal. 

Clearance —

 These units are approved for 0 

inch clearance.

ELECTRICAL WIRING

General — 

Electrical power wiring must be made 

in accordance with all applicable local codes and 
ordinances, and with the current revision of the 
National Electric Code NFPA 70 or in Canada CSA 
C.22.1 - Canadian Electrical Code Part 1. If any 
of the original wire as supplied with the unit must 
be replaced, it must be replaced with material of 
the same gage and temperature rating.

 WARNING:

To avoid the risk of electrical shock, 
personal injury, or death, disconnect 
all electrical power to the unit before 
performing any maintenance or service. 
The unit may have more than one 
electrical power supply.

Line Voltage — 

Before proceeding with the 

electrical connections, make certain that the 
voltage, frequency, and phase of the supply 
source are the same as those specifi ed on the unit 
rating plate. Also verify that the service provided 
by the utility is suffi cient to handle the additional 
load imposed by this equipment.

and Air Conditioning Association (ACCA). The 
ducts must be properly sized not to exceed .2” 
w.c. pressure drop at 400 scfm per nominal ton 
of cooling capacity.

Duct work should be attached directly to the unit 
fl anges for horizontal applications. On roof curb 
installations the ducts must be attached to the 
curb hangers, not the unit.

Unconditioned Spaces —

 All duct work passing 

through unconditioned space must be properly 
insulated to minimize duct losses and prevent 
condensation. Use insulation with an outer vapor 
barrier. Refer to local codes for insulation material 
requirements.

Acoustical Duct Work — 

Certain installations 

may require the use of acoustical lining inside the 
supply duct work. Acoustical insulation must be in 
accordance with the current revision of the Sheet 
Metal and Air Conditioning Contractors National 
Association (SMACNA) application standard for 
duct liners. Duct lining must be UL classifi ed batts 
or blankets with a fi re hazard classifi cation of 
FHC-25/50 or less. Fiber duct work may be used 
in place of internal duct liners if the fi ber duct work 
is in accordance with the current revision of the 
SMACNA construction standard on fi brous glass 
ducts. Fibrous duct work and internal acoustical 
lining must be NFPA Class 1 air ducts when tested 
per UL Standard 181 for Class 1 ducts.

Horizontal to Down fl ow Conversion — 

The unit 

is shipped ready for horizontal duct connections. 
If down fl ow ducts are required, the unit must be 
converted following the steps below for both the 
supply and return ducts.

1)  Remove the horizontal duct cap.
2)  Locate the duct cap inside the duct openings 

and remove the screw holding it in place.

2"

Figure 6. Ground Level Installation

2”

Figure 7. Roof Top Installation

Содержание Q4SD-X24K

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...gas to a liquid 5 The blower circulates the heat throughout the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 In...

Страница 3: ...eat Some thermostats will include a system switch position termed EM HT or AUX HT etc This is a back up heating mode to be used only if there is a suspected problem With the system switch set to EM HT...

Страница 4: ...containedintheseinstructions All electrical wiring must be made in accordance with local codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code...

Страница 5: ...35 3 X30 455 28 0 25 5 39 0 35 3 X36 460 28 0 25 5 39 0 35 3 X42 565 29 5 26 0 43 0 39 3 X48 570 29 5 26 0 43 0 39 3 X60 580 29 5 26 0 43 0 39 3 Model Number Q4SD PPH1SD Unit Weight Center of Gravity...

Страница 6: ...rdance with the standards of the National Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A StandardforInstallationofResidenceType WarmAirHeatingandAirConditio...

Страница 7: ...er nominal ton of cooling capacity Duct work should be attached directly to the unit flanges for horizontal applications On roof curb installations the ducts must be attached to the curb hangers not t...

Страница 8: ...themotorwill gradually change speeds during start up shut down whenthermostatinputschange andwhen theductstaticpressurechanges ventsclosedor opened filter clogging etc The packaged heat pump unit is c...

Страница 9: ...A also provides a 60 second off delay at 50 airflow DelayB hasasinglestep30second on delayat 50 airflow Delay B also provides a 90 second off delay at 50 airflow Select the delay profile which is most...

Страница 10: ...e wire entrance in the packaged heat pump unit and remove jumper connector between B1 and B2 wire switch to close on temperature rise Set the thermostat as desired near 105 F CAUTION To avoid personal...

Страница 11: ...is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set to Off and the thermostat fan switch should be set to Auto Start Up Procedure Close all electrica...

Страница 12: ...Note The delay no delay pin concerns compressoroperationduringdefrosts Thedefault setting is delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit...

Страница 13: ...ake it necessary for evacuation and charging it should only be done by qualified trained personnel thoroughly familiarwiththisequipment Somelocal codes require licensed installation service personnel...

Страница 14: ...stat E O G R Y1 INDOOR THERMOSTAT SUB BASE Green Y2 W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional Outdoor Thermostat Field Supplied O E O G R Y1 INDOOR THERMOSTAT SUB...

Страница 15: ...2 67 25 7 21 2 2 95 24 5 20 6 3 26 1100 80 62 28 6 29 1 2 42 27 4 27 7 2 68 26 3 26 6 2 96 25 3 25 3 3 26 80 67 30 9 24 9 2 43 29 5 24 2 2 69 28 2 23 6 2 97 26 9 23 0 3 27 80 72 33 4 20 1 2 43 31 9 19...

Страница 16: ...0 5 4 12 40 2 29 6 4 58 38 2 28 7 5 13 1400 80 62 44 4 40 6 3 72 42 6 40 1 4 13 40 7 39 3 4 60 38 8 38 3 5 14 80 67 48 0 34 0 3 78 46 0 33 1 4 19 43 9 32 3 4 66 41 7 31 2 5 21 80 72 51 6 27 0 3 84 49...

Страница 17: ...0 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM Deg F...

Страница 18: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 19: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 20: ...s 7084390 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 08 08 708439I INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: