background image

6

Figure 4. Minimum Clearances

 CAUTION:

All panels must be securely in place 

when rigging and hoisting.

The rigging must be located outside the unit’s 
center of gravity. Refer to 

Figure 3

 for center of 

gravity locations.

Rooftop — 

For rooftop installations use the 

appropriate accessory roof curb and follow all 
instructions included with it. Make sure the two 
supports beneath the unit have been removed. 
Locate the unit according to local building codes 
and ordinances. The curb must be level to insure 
proper condensate drainage. 

See Figure 7

The roof must be capable of handling the weight of 
the unit. 

See Figure 3 

for unit weights. Reinforce 

the roof if required.

AIR DUCTS

This unit is designed only for use with a supply 
and return duct. Air ducts should be installed in 
accordance with the standards of the National 
Fire Protection Association “Standard for 
Installation of Air Conditioning Systems” (NFPA 
90A), “Standard for Installation of Residence Type 
Warm Air Heating and Air Conditioning Systems” 
(NFPA 90B), and all applicable local codes.

Design the duct work according to methods 
described by the National Warm Air Heating 

Rigging and Hoisting — 

The unit should be lifted 

using slings and spreader bars. The spreader 
bars are necessary to prevent damaging the 
top of the unit’s cabinet. Make sure that the 
lifting equipment is adequate for the load. Refer 
to 

Figure 3

 for unit weights. Keep the unit in 

an upright position at all times. 

For rooftop 

installations, remove and discard the two 
supports attached beneath the unit.

 WARNING:

To avoid the risk of property damage 
or personal injury; it is the rigger’s 
responsibility to insure that whatever 
means are used to hoist the unit are 
safe and adequate.

Condensate Drain

Figure 5. Condensate Drain

36"

36"

0"

36"

72"

Содержание Q4SD-X24K

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...gas to a liquid 5 The blower circulates the heat throughout the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 In...

Страница 3: ...eat Some thermostats will include a system switch position termed EM HT or AUX HT etc This is a back up heating mode to be used only if there is a suspected problem With the system switch set to EM HT...

Страница 4: ...containedintheseinstructions All electrical wiring must be made in accordance with local codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code...

Страница 5: ...35 3 X30 455 28 0 25 5 39 0 35 3 X36 460 28 0 25 5 39 0 35 3 X42 565 29 5 26 0 43 0 39 3 X48 570 29 5 26 0 43 0 39 3 X60 580 29 5 26 0 43 0 39 3 Model Number Q4SD PPH1SD Unit Weight Center of Gravity...

Страница 6: ...rdance with the standards of the National Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A StandardforInstallationofResidenceType WarmAirHeatingandAirConditio...

Страница 7: ...er nominal ton of cooling capacity Duct work should be attached directly to the unit flanges for horizontal applications On roof curb installations the ducts must be attached to the curb hangers not t...

Страница 8: ...themotorwill gradually change speeds during start up shut down whenthermostatinputschange andwhen theductstaticpressurechanges ventsclosedor opened filter clogging etc The packaged heat pump unit is c...

Страница 9: ...A also provides a 60 second off delay at 50 airflow DelayB hasasinglestep30second on delayat 50 airflow Delay B also provides a 90 second off delay at 50 airflow Select the delay profile which is most...

Страница 10: ...e wire entrance in the packaged heat pump unit and remove jumper connector between B1 and B2 wire switch to close on temperature rise Set the thermostat as desired near 105 F CAUTION To avoid personal...

Страница 11: ...is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set to Off and the thermostat fan switch should be set to Auto Start Up Procedure Close all electrica...

Страница 12: ...Note The delay no delay pin concerns compressoroperationduringdefrosts Thedefault setting is delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit...

Страница 13: ...ake it necessary for evacuation and charging it should only be done by qualified trained personnel thoroughly familiarwiththisequipment Somelocal codes require licensed installation service personnel...

Страница 14: ...stat E O G R Y1 INDOOR THERMOSTAT SUB BASE Green Y2 W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional Outdoor Thermostat Field Supplied O E O G R Y1 INDOOR THERMOSTAT SUB...

Страница 15: ...2 67 25 7 21 2 2 95 24 5 20 6 3 26 1100 80 62 28 6 29 1 2 42 27 4 27 7 2 68 26 3 26 6 2 96 25 3 25 3 3 26 80 67 30 9 24 9 2 43 29 5 24 2 2 69 28 2 23 6 2 97 26 9 23 0 3 27 80 72 33 4 20 1 2 43 31 9 19...

Страница 16: ...0 5 4 12 40 2 29 6 4 58 38 2 28 7 5 13 1400 80 62 44 4 40 6 3 72 42 6 40 1 4 13 40 7 39 3 4 60 38 8 38 3 5 14 80 67 48 0 34 0 3 78 46 0 33 1 4 19 43 9 32 3 4 66 41 7 31 2 5 21 80 72 51 6 27 0 3 84 49...

Страница 17: ...0 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM Deg F...

Страница 18: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 19: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 20: ...s 7084390 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 08 08 708439I INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: