background image

13

circulated by the indoor blower and verify that 
it is warmer than ambient temperature. Listen 
for any unusual noises. If present, locate and 
determine the source of the noise and correct 
as necessary.

NOTE:

 Other sources for heating (i.e.: electric 

furnace, fossil fuel furnace, air handler with 
electric heat options, etc.) that interface with 
the heat pump should be functionally checked 
to verify system operation and compatibility with 
the heat pump. Refer to the installation instruc-
tions for this equipment and perform a functional 
checkout in accordance with the manufacturer’s 
instructions.

UNIT MAINTENANCE

 WARNING:

To avoid risk of electrical shock, personal 
injury, or death, disconnect all electrical 
power to the unit before performing any 
maintenance or service. The unit may 
have more than one electrical supply.

Refrigerant Charging — 

Packaged heat pumps 

are fully charged at the factory. The system 
refrigerant charge can be checked and adjusted 
through the service ports provided behind the 
front panel. Use only gauge lines which have a 
“Schrader” depression device present to actuate 
the valve. Draw a vacuum on gauge lines to 
remove air before attaching them to the service 
ports on the unit. Refrigerant charging must be 
done by qualifi ed personnel familiar with safe 
and environmentally responsible refrigerant 
handling procedures.

 WARNING:

Single Packaged Heat Pumps are 
shipped fully charged and ready for 
installation. When a system is installed 
according to these instructions, no 
refrigerant charging is required. If repairs 
make it necessary for evacuation and 
charging, it should only be done by 
qualifi ed, trained personnel thoroughly 
familiar with this equipment. Some local 
codes require licensed installation/
service personnel to service this type 
of equipment. Under no circumstances 
should the owner attempt to install and/

or service this equipment. Failure to 
comply with this warning could result 
in property damage, personal injury, 
or death.

 CAUTION:

Use care when removing parts from this 
unit. Personal injury can result from sharp 
metal edges present in all equipment of 
sheet metal construction.

Routine Maintenance — 

Proper maintenance is 

important to achieve optimum performance from 
the heat pump. The ability to properly perform 
maintenance on this equipment requires certain 
mechanical skills and tools. If you do not possess 
these skills, contact your dealer for maintenance. 
Consult your local dealer about the availability of 
maintenance contracts. At a minimum, routine 
maintenance should include the following:

1.  Inspect and clean or replace air fi lters at 

the beginning of each heating and cooling 
season, or more frequently if required.

2.  Inspect the condensate drain and outdoor 

coil at the beginning of each cooling season. 
Remove any debris. Clean the outdoor coil 
and louvers as necessary using a mild 
detergent and water. Rinse thoroughly with 
water.

3.  Inspect the electrical connections for 

tightness at the beginning of each 
heating and cooling season. Service as 
necessary.

 CAUTION:

The unit should never be operated 
without a fi lter in the return air system. 
Replace disposable fi lters with the same 
type and size.

4.  The motors for the circulating air blower 

and the outdoor fan are pre-lubricated at 
the factory. No further oiling is required for 
the life of this product.

Содержание Q4SD-X24K

Страница 1: ...oning appliances Some local codes require licensed installation service personnel for this type equipment All installations must be in accordance with these instructions and with all applicable nation...

Страница 2: ...gas to a liquid 5 The blower circulates the heat throughout the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 In...

Страница 3: ...eat Some thermostats will include a system switch position termed EM HT or AUX HT etc This is a back up heating mode to be used only if there is a suspected problem With the system switch set to EM HT...

Страница 4: ...containedintheseinstructions All electrical wiring must be made in accordance with local codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Canadian Electric Code...

Страница 5: ...35 3 X30 455 28 0 25 5 39 0 35 3 X36 460 28 0 25 5 39 0 35 3 X42 565 29 5 26 0 43 0 39 3 X48 570 29 5 26 0 43 0 39 3 X60 580 29 5 26 0 43 0 39 3 Model Number Q4SD PPH1SD Unit Weight Center of Gravity...

Страница 6: ...rdance with the standards of the National Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A StandardforInstallationofResidenceType WarmAirHeatingandAirConditio...

Страница 7: ...er nominal ton of cooling capacity Duct work should be attached directly to the unit flanges for horizontal applications On roof curb installations the ducts must be attached to the curb hangers not t...

Страница 8: ...themotorwill gradually change speeds during start up shut down whenthermostatinputschange andwhen theductstaticpressurechanges ventsclosedor opened filter clogging etc The packaged heat pump unit is c...

Страница 9: ...A also provides a 60 second off delay at 50 airflow DelayB hasasinglestep30second on delayat 50 airflow Delay B also provides a 90 second off delay at 50 airflow Select the delay profile which is most...

Страница 10: ...e wire entrance in the packaged heat pump unit and remove jumper connector between B1 and B2 wire switch to close on temperature rise Set the thermostat as desired near 105 F CAUTION To avoid personal...

Страница 11: ...is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set to Off and the thermostat fan switch should be set to Auto Start Up Procedure Close all electrica...

Страница 12: ...Note The delay no delay pin concerns compressoroperationduringdefrosts Thedefault setting is delay Reciprocating compressors should only use this setting in conjunction with an approved hard start kit...

Страница 13: ...ake it necessary for evacuation and charging it should only be done by qualified trained personnel thoroughly familiarwiththisequipment Somelocal codes require licensed installation service personnel...

Страница 14: ...stat E O G R Y1 INDOOR THERMOSTAT SUB BASE Green Y2 W2 C DEFROST BOARD 1 2 3 4 5 6 7 8 9 Brown Orange Accessory Heat Plug Optional Outdoor Thermostat Field Supplied O E O G R Y1 INDOOR THERMOSTAT SUB...

Страница 15: ...2 67 25 7 21 2 2 95 24 5 20 6 3 26 1100 80 62 28 6 29 1 2 42 27 4 27 7 2 68 26 3 26 6 2 96 25 3 25 3 3 26 80 67 30 9 24 9 2 43 29 5 24 2 2 69 28 2 23 6 2 97 26 9 23 0 3 27 80 72 33 4 20 1 2 43 31 9 19...

Страница 16: ...0 5 4 12 40 2 29 6 4 58 38 2 28 7 5 13 1400 80 62 44 4 40 6 3 72 42 6 40 1 4 13 40 7 39 3 4 60 38 8 38 3 5 14 80 67 48 0 34 0 3 78 46 0 33 1 4 19 43 9 32 3 4 66 41 7 31 2 5 21 80 72 51 6 27 0 3 84 49...

Страница 17: ...0 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM Deg F...

Страница 18: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 19: ...1 80 24 3 1 58 4 52 29 6 1 90 4 57 31 9 2 03 4 59 39 4 2 48 4 67 46 9 2 90 4 74 52 2 3 20 4 79 54 5 3 32 4 81 62 0 3 72 4 89 Q4SD X60K OUTDOOR TEMPERATURE Deg F Indoor T 10 17 20 30 40 47 50 60 CFM De...

Страница 20: ...s 7084390 Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 08 08 708439I INSTALLER PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH...

Отзывы: