background image

8

Acoustical Duct Work — Certain installations
may require the use of acoustical lining inside
the supply duct work.  Acoustical insulation must
be in accordance with the current revision of the
Sheet Metal and Air Conditioning Contractors
National Association (SMACNA) application
standard for duct liners.  Duct lining must be UL
classified batts or blankets with a fire hazard
classification of FHC-25/50 or less.  Fiber duct
work may be used in place of internal duct liners
if the fiber duct work is in accordance with the
current revision of the SMACNA construction
standard on fibrous glass ducts.  Fibrous duct
work and internal acoustical lining must be NFPA
Class 1 air ducts when tested per UL Standard
181 for Class 1 ducts.

Horizontal to Down flow Conversion — The
unit is shipped ready for horizontal duct
connections.  If down flow ducts are required,
the unit must be converted following the steps
below for both the supply and return ducts.

1) Locate the duct cap inside the duct openings

and remove the screw holding it in place.

2) Lift the cap out of the unit.  (The cap can be

pushed up from the bottom by reaching
through the fork slot).

3) Cover the horizontal duct opening with the

cap.  The insulation will be on the indoor side.

4) Fasten the cover with screws and seal to

prevent air leakage.

Clearance — The Q4 Series is approved for 0
inch clearance.

Figure 6. Ground Level Installation

2"

Figure 7. Roof Top Installation

ELECTRICAL WIRING

General  —  Electrical power wiring must be
made in accordance with all applicable local
codes and ordinances, and with the current
revision of the National Electric Code NFPA  70
or in Canada CSA   C.22.1 - Canadian Electrical
Code Part  1.  If any of the original wire as
supplied with the unit must be replaced, it must
be replaced with material of the same gage and
temperature rating.

Line Voltage —  Before proceeding with the
electrical connections, make certain that the
voltage, frequency, and phase of the supply
source are the same as those specified on the
unit rating plate.  Also verify that the service
provided by the utility is sufficient to handle the
additional load imposed by this equipment.

!

 WARNING:

To avoid the risk of electrical shock,
personal injury, or death, disconnect
all electrical power to the unit before
performing any maintenance or service.
The unit may have more than one
electrical power supply.

See Figure 8 or the unit wiring label for proper
high and low voltage wiring.  Make all electrical
connections in accordance with all applicable
codes and ordinances.

Содержание Q4 Series

Страница 1: ...ntended to assist qualified individuals experienced in the proper installation of heating and or air conditioning appliances Some local codes require licensed installation service per sonnel for this...

Страница 2: ...ging and Hoisting 7 Rooftop 7 AIR DUCTS 7 Unconditioned Spaces 7 Acoustical Duct Work 8 Horizontal to Down flow Conversion 8 Clearance 8 ELECTRICAL WIRING 8 Line Voltage 8 Blower Speed 9 Low Voltage C...

Страница 3: ...out the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat tran...

Страница 4: ...and the outdoor fan off for approx imately six minutes following a previous operation or the interruption of the main electrical power Emergency Heat Some thermostats will include a system switch posi...

Страница 5: ...inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consignee RequirementsandCodes Theinstallermust comply with all local codes and regulations which...

Страница 6: ...View Center of Gravity Height in inches Model No C with base rails without base rails Q4SA 036 340 28 0 26 0 33 7 31 3 Q4SA 048 345 28 0 26 0 33 7 31 3 Q4SA 060 400 29 5 26 5 37 7 35 3 A B Unit Weight...

Страница 7: ...ppropriate accessory roof curb and follow all instructions included with it Locate the unit accordingtolocalbuildingcodesandordinances The curb must be level to insure proper condensate drainage See F...

Страница 8: ...ntal duct opening with the cap The insulation will be on the indoor side 4 Fasten the cover with screws and seal to prevent air leakage Clearance The Q4 Series is approved for 0 inch clearance Figure...

Страница 9: ...desired cooling blower speed lead on terminal 4 of the blower relay Use another wire tie field supplied to bundle the remaining motor leads CAUTION To avoid personal injury or property damage make cer...

Страница 10: ...the outdoor fan turns freely Verify that the power supply branch circuit overcurrent protection is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set t...

Страница 11: ...owner attempt to install and or service this equipment Failure to comply with this warning could result in property damage personal injury or death CAUTION Use care when removing parts from this unit...

Страница 12: ...Optional Check Thermostat Instructions Y2 W2 W3 X E R W2 O Y C DEFROST BOARD External Static Pressure Drop inches water column Model Speed 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Q4SA 036 High 1600 1510 1410...

Страница 13: ...1 20 144 132 25 152 132 30 161 132 35 169 131 44 185 140 57 211 158 70 236 175 21 151 130 26 158 130 31 165 130 36 172 129 45 192 137 58 218 153 71 243 169 22 158 128 27 164 128 32 170 128 37 176 127...

Страница 14: ...Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp 12 122 126 19 139...

Страница 15: ...Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp 68 188 122 70 191 123 204 135 72 192 140 207 139 222 137 234 14...

Страница 16: ...287 175 78 214 215 231 204 247 195 262 188 278 183 291 181 304 179 80 232 216 249 207 265 199 280 193 295 188 309 185 82 267 210 282 203 298 197 313 192 84 300 206 315 201 86 303 216 318 210 88 320 2...

Страница 17: ...HP 2 stage htg 1 stage cool auto M brand 912931 T stat HP 2 stage htg 1 stage cool auto I brand 912929 T stat HP 2 stage htg 1 stage cool manual M brand 912932 T stat HP 2 stage htg 1 stage cool manu...

Страница 18: ...ny of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rating of at least 105 C 4 For supply wire ampacities and overcurren...

Страница 19: ...H N I S U I H A S B I D D A R I STAN A R 210 T A I D N FIED T R E C E EN R C O I I O N ING T AI D N R CO I I O N I N G D ITI O N I N G N O C R I A R 707885W 707885A St Louis MO 707885A Replaces 70788...

Отзывы: