background image

7

Figure 4. Minimum Clearances

36"

36"

6"

72"

36"

Condensate Drain

Figure 5. Condensate Drain

UNIT INSTALLATION

Ground Level —  When installing the unit at
ground level, provide a concrete mounting pad
separate from the building foundation.  The pad
must be level to insure proper condensate
disposal and strong enough to support the unit’s
weight.  Refer to Figure 3.   Make sure the slab
is a minimum of 2" above the grade and in an
area that drains well (See Figure 6).

Rigging and Hoisting —  The unit should be
lifted using slings and spreader bars.  The
spreader bars are necessary to prevent damaging
the top of the unit’s cabinet.  Make sure that the
lifting equipment is adequate for the load.  Refer
to Figure 3 for unit weights.  Keep the unit in an
upright position at all times.

!

 WARNING:

To avoid the risk of property damage or
personal injury; it is the rigger’s
responsibility to insure that whatever
means are used to hoist the unit are
safe and adequate.

!

 CAUTION:

All panels must be securely in place
when rigging and hoisting.

The rigging must be located outside the unit’s
center of gravity.  Refer to Figure 3 for center of
gravity locations.

Rooftop  —  For rooftop installations use the
appropriate accessory roof curb and follow all
instructions included with it.  Locate the unit
according to local building codes and ordinances.
The curb must be level to insure proper
condensate drainage (See Figure 7).

The roof must be capable of handling the weight
of the unit.  (See Figure 3)  for unit weights.
Reinforce the roof if required.

AIR DUCTS

This unit is designed only for use with a
supply  and return duct.  Air ducts should be
installed in accordance with the standards of
the National Fire Protection Association
“Standard for Installation of Air Conditioning
S y s t e m s ”   ( N F P A   9 0 A ) ,   “ S t a n d a r d   f o r
Installation of Residence Type Warm Air
Heating and Air Conditioning Systems” (NFPA
90B), and all applicable local codes.

Design the duct work according to methods
described by the National Warm Air Heating and
Air Conditioning Association (ACCA). The ducts
must be properly sized not to exceed .2" w.c.
pressure drop at 400 scfm per nominal ton of
cooling capacity.

Duct work should be attached directly to the unit
flanges for horizontal applications.  On roof curb
installations the ducts must be attached to the
curb hangers, not the unit.

Unconditioned Spaces — All duct work passing
through unconditioned space must be properly
insulated to minimize duct losses and prevent
condensation.  Use insulation with an outer
vapor barrier.  Refer to local codes for insulation
material requirements.

Содержание Q4 Series

Страница 1: ...ntended to assist qualified individuals experienced in the proper installation of heating and or air conditioning appliances Some local codes require licensed installation service per sonnel for this...

Страница 2: ...ging and Hoisting 7 Rooftop 7 AIR DUCTS 7 Unconditioned Spaces 7 Acoustical Duct Work 8 Horizontal to Down flow Conversion 8 Clearance 8 ELECTRICAL WIRING 8 Line Voltage 8 Blower Speed 9 Low Voltage C...

Страница 3: ...out the home via the supply duct 6 The refrigerant returns to the outdoor coil and evaporates once again to absorb more heat SUMMER COOLING 1 Indoor air enters the return air duct 2 The cold heat tran...

Страница 4: ...and the outdoor fan off for approx imately six minutes following a previous operation or the interruption of the main electrical power Emergency Heat Some thermostats will include a system switch posi...

Страница 5: ...inspect it for apparent and concealed damage Claims for damage should be filed with the carrier by the consignee RequirementsandCodes Theinstallermust comply with all local codes and regulations which...

Страница 6: ...View Center of Gravity Height in inches Model No C with base rails without base rails Q4SA 036 340 28 0 26 0 33 7 31 3 Q4SA 048 345 28 0 26 0 33 7 31 3 Q4SA 060 400 29 5 26 5 37 7 35 3 A B Unit Weight...

Страница 7: ...ppropriate accessory roof curb and follow all instructions included with it Locate the unit accordingtolocalbuildingcodesandordinances The curb must be level to insure proper condensate drainage See F...

Страница 8: ...ntal duct opening with the cap The insulation will be on the indoor side 4 Fasten the cover with screws and seal to prevent air leakage Clearance The Q4 Series is approved for 0 inch clearance Figure...

Страница 9: ...desired cooling blower speed lead on terminal 4 of the blower relay Use another wire tie field supplied to bundle the remaining motor leads CAUTION To avoid personal injury or property damage make cer...

Страница 10: ...the outdoor fan turns freely Verify that the power supply branch circuit overcurrent protection is sized properly Verifythatthethermostatiswiredcorrectly The thermostat function switch should be set t...

Страница 11: ...owner attempt to install and or service this equipment Failure to comply with this warning could result in property damage personal injury or death CAUTION Use care when removing parts from this unit...

Страница 12: ...Optional Check Thermostat Instructions Y2 W2 W3 X E R W2 O Y C DEFROST BOARD External Static Pressure Drop inches water column Model Speed 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Q4SA 036 High 1600 1510 1410...

Страница 13: ...1 20 144 132 25 152 132 30 161 132 35 169 131 44 185 140 57 211 158 70 236 175 21 151 130 26 158 130 31 165 130 36 172 129 45 192 137 58 218 153 71 243 169 22 158 128 27 164 128 32 170 128 37 176 127...

Страница 14: ...Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp Suc Press Disch Press Disch Temp 12 122 126 19 139...

Страница 15: ...Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp Disch Pres Disch Temp 68 188 122 70 191 123 204 135 72 192 140 207 139 222 137 234 14...

Страница 16: ...287 175 78 214 215 231 204 247 195 262 188 278 183 291 181 304 179 80 232 216 249 207 265 199 280 193 295 188 309 185 82 267 210 282 203 298 197 313 192 84 300 206 315 201 86 303 216 318 210 88 320 2...

Страница 17: ...HP 2 stage htg 1 stage cool auto M brand 912931 T stat HP 2 stage htg 1 stage cool auto I brand 912929 T stat HP 2 stage htg 1 stage cool manual M brand 912932 T stat HP 2 stage htg 1 stage cool manu...

Страница 18: ...ny of the original wire as supplied with the furnace must be replaced it must be replaced with wiring material having a temperature rating of at least 105 C 4 For supply wire ampacities and overcurren...

Страница 19: ...H N I S U I H A S B I D D A R I STAN A R 210 T A I D N FIED T R E C E EN R C O I I O N ING T AI D N R CO I I O N I N G D ITI O N I N G N O C R I A R 707885W 707885A St Louis MO 707885A Replaces 70788...

Отзывы: