12
Typical Wiring (Field Supplied)
for 1-Stage Cool, 1-Stage Heat
Typical Wiring (Field Supplied)
for 2-Stage Cool, 1-Stage Heat
Figure 10. Typical Thermostat Connection
E
O
G
R
Y1
1
2
3
4
5
6
7
8
9
Blue
ECONOMIZER
PLUG
INDOOR
THERMOSTAT
SUB-BASE
Green
FROM
BLOWER
RELAY
(Optional,Check
Thermostat
Instructions)
Y2
W2
W3
X
E
R
W2
O
Y
C
DEFROST
BOARD
E
O
G
R
Y1
1
2
3
4
5
6
7
8
9
Blue
ECONOMIZER
PLUG
INDOOR
THERMOSTAT
SUB-BASE
Green
FROM
BLOWER
RELAY
(Optional,Check
Thermostat
Instructions)
Y2
W2
W3
X
E
R
W2
O
Y
C
DEFROST
BOARD
External Static Pressure Drop - inches water column
Model
Speed
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Q4SA-036
High
1600
1510
1410
1310
1200
1070
930
760
Medium
1410
1330
1250
1150
1050
940
820
670
Low
1130
1070
1000
930
850
760
650
530
Q4SA-048
High
2200
2140
2070
2000
1930
1850
1770
1690
Medium
1940
1890
1830
1760
1700
1630
1560
1490
Low
1560
1510
1460
1410
1360
1310
1250
1200
Q4SA-060
High
2200
2140
2070
2000
1930
1850
1770
1690
Medium
1940
1890
1830
1760
1700
1630
1560
1490
Low
1560
1510
1460
1410
1360
1310
1250
1200
-
Speed set at factory
Table 1. Q4 Blower Curves