Nordyne JS5BD SERIES Скачать руководство пользователя страница 1

Please read this information thoroughly and become familiar with the capabilities and 
use of your appliance before attempting to operate or maintain this unit. Keep this 
literature where you have easy access to it in the future. If a problem occurs, check the 
instructions and follow recommendations given. If these suggestions don’t eliminate 
the problem, call your servicing contractor.

The Installation Instructions are primarily intended to assist qualified individuals 
experienced in the proper installation of this appliance. Some local codes require licensed 
installation/service personnel for this type of equipment. Please read all instructions 
carefully before starting the installation.

DO NOT DESTROY. PLEASE READ CAREFULLY AND 

KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.

IMPORTANT

SPLIT SYSTEM AIR CONDITIONER - R-22

USER’S MANUAL / INSTALLATION INSTRUCTIONS

JS5BD SERIES

13 SEER

Содержание JS5BD SERIES

Страница 1: ...minate the problem call your servicing contractor The Installation Instructions are primarily intended to assist qualified individuals experiencedintheproperinstallationofthisappliance Somelocalcodesr...

Страница 2: ...e 5 JS5BD 024KB 2 Ton Units 14 Table 6 JS5BD 030KB 2 5 Ton Units 15 Table 7 JS5BD 036KB 3 Ton Units 15 Table 8 JS5BD 042KA 3 5 Ton Units 16 Table 9 JS5BD 048KA 4 Ton Units 16 Table 10 JS5BD 060KA 5 To...

Страница 3: ...t operate regardless of the temperature selector setting Figure 1 Digital Thermostat Fan Mode Temperature Selector System Mode AIR CONDITIONER Maintenance Propermaintenanceismostimportanttoachievetheb...

Страница 4: ...s unit uses refrigerant R 22 DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the unit WARNING The information listed below must be followed during the installation...

Страница 5: ...be carefully inspected for damage prior to installing the equipment at the job site Verify coil fins are straight If necessary comb fins to remove flattened or bent fins Claims for damage apparent or...

Страница 6: ...nd ordinances and with the current revision of the National Electric Code ANSI NFPA 70 For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electr...

Страница 7: ...shouldbemadeinaccordance with the instructions supplied with the thermostat and the indoor equipment The outdoor unit is designed to operate from a 24 VAC Class II control circuit The control circuit...

Страница 8: ...tion Instructions first 2 Complete any brazing operations e g Split system line sets 3 Leak check and evacuate the whole system using proper methods 4 Purge the nitrogen holding charge 5 Evacuate the...

Страница 9: ...personal injury or death disconnect all electrical power to the unit before performing any maintenance or service The unit may have more than one electrical supply Proper maintenance is important to...

Страница 10: ...frigerant when above curve JS5BD 018KA SERIES CHARGING CHART Figure 5 Charging Chart for 1 5 Ton Units Figure 4 Unit Dimensions Model Number JS5BD Height H Width W Depth D 018KA 23 22 3 4 22 3 4 024KB...

Страница 11: ...d refrigerant when below curve JS5BD 024KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 7 Charging Chart for 2 5 Ton Units with Microchannel Coil 140 160 180 200 220 240 260 280 30...

Страница 12: ...ure psig Add refrigerant when below curve JS5BD 036KB SERIES CHARGING CHART Remove refrigerant when above curve Figure 9 Charging Chart for 3 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 36...

Страница 13: ...dd refrigerant when below curve JS5BD 048KA SERIES CHARGING CHART Remove refrigerant when above curve Figure 11 Charging Chart for 5 Ton Units 140 160 180 200 220 240 260 280 300 320 340 360 380 400 7...

Страница 14: ...142 208 144 223 145 84 182 146 195 148 211 148 225 150 239 151 86 199 151 213 153 227 154 241 156 256 157 88 216 157 230 158 243 160 258 161 272 163 90 220 160 233 162 247 164 260 165 274 166 92 237 1...

Страница 15: ...180 130 196 137 212 144 78 165 130 180 137 198 142 214 149 230 156 80 184 140 199 147 216 153 232 160 248 167 82 203 151 218 158 234 164 250 171 266 178 84 206 154 222 161 237 168 252 175 268 182 86 2...

Страница 16: ...202 156 212 155 222 154 83 197 159 205 160 214 159 224 158 234 158 85 209 163 217 163 226 163 236 162 246 162 87 221 167 229 167 238 166 248 166 258 165 89 224 170 233 171 242 170 250 170 260 169 91 2...

Страница 17: ...4 1 16 8 16 2 21 3 26 7 Delay Fuse Max 2 15 20 30 35 30 45 50 Min Circuit Ampacity 10 8 14 1 17 5 20 6 19 9 26 3 33 1 Component Data Coil Area 8 2 9 9 9 9 9 9 17 7 17 7 25 4 Rows FPI 1 22 1 18 1 18 1...

Страница 18: ...it If desired ASCT is factory installed on select models only or may be field installed as shown using manufacturer s approved kit If not present connect Yellow and Black wires per Note 6 8 DO NOT use...

Страница 19: ...19...

Страница 20: ...709244A Replaces 7092440 Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U S A 04 11...