background image

6

Figure 2. Combustion Air Drawn from a Crawl 

Space or Vented Attic

Water

Heater

Vent or

Chimney

- - - - - - - - -

- - - - - - - - -

Furnace

Ventilation Louvers For 
Unheated Crawl Space

- - - - - - - - -

Inlet Air

Ventilation Louvers
(each end of attic)

NOTE:

 Air openings shall

each have a free area of
not less than one square
inch per 4,000 Btuh of the
total input rating of all 
equipment in the enclosure.

---

---

---

Alternate

Air Inlet

Outlet

Air

Example

:

If the combined input rate of all appliances is less 
than or equal to 100,000 Btuh, each opening must 
have a free area of at least 100 square inches. If the 
combined input rate of all appliances is 120,000 Btuh, 
each opening must have a free area of at least 120 
square inches.

Figure 1. Combustion Air Drawn from Inside

Total Input Rating 

(Btuh)

Minimum Free Area

 (Each Opening)

Round Duct 

Diameter

40,000

100 sq. In

12 inches

60,000

100 sq. In

12 inches

80,000

100 sq. In

12 inches

100,000

100 sq. In

12 inches

120,000

120 sq. In

13 inches

140,000

140 sq. In

14 inches

160,000

160 sq. In

15 inches

Vent or

Chimney

Furnace

Water
Heater

12” Max.

12” Max.

See

Notes

See

Notes

NOTES:

 

Each opening must be
at least 100 sq. in. or 
1 sq. in. per 1,000 Btuh
of total input rating, 
whichever is greater. 

Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.

•  Air openings on top of the furnace and in closet doors or 

walls must never be restricted. If the furnace is operated 
without adequate air for combustion, the fl ame roll-out 
switch will open, turning off the gas supply to the burners. 

This safety device is a manually reset switch. DO NOT 
install jumper wires across these switches to defeat 
their function or reset a switch without identifying 
and correcting the fault condition.

 If the switch must 

be replaced, use only the correct sized part specifi ed 
in the Replacement Parts List provided online.

 CAUTION:

Exhaust fans, clothes dryers, fi replaces  and 
other appliances that force air from the house 
to the outdoors can create a negative pressure 
inside the house, resulting in improper furnace 
operation or unsafe conditions such as fl ame roll 
out. It is imperative that suffi cient air exchange 
with the outdoors is provided to prevent 
depressurization. Additional information about 
how to test for negative pressure problems can 
be found in the IFGC.

Conventional Furnaces - Confi ned Spaces

A confi ned space is an area with volume less than 50 
cubic feet per 1,000 Btuh of the combined input rates of 
all appliances drawing combustion air from that space. 
Furnace closets, small equipment rooms and garages are 
confi ned spaces. Furnaces installed in a confi ned space 
which supply heated air to areas outside the space must 
draw return air from outside the space and must have the 
return air ducts tightly sealed to the furnace. Ducts must 
have cross - sectional area at least as large as the free 
area of their respective openings to the furnace space.

The required sizing of these openings is determined by 
whether inside or outside air is used to support combustion, 
the method by which the air is brought to the space, and 
by the total input rate of all appliances in the space. In 
all cases, the minimum dimension of any combustion air 
opening is 3 inches.

Air From Inside
If combustion air is taken from the heated space, the two 
openings must each have a free area of at least one square 
inch per 1,000 Btuh of total input of all appliances in the 
confi ned space, but 

not less than 100 square inches 

of free area 

(Figure 1)

.

Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the 
outdoors, each opening shall have a minimum free area 
of 1 square inch per 4,000 Btuh of total appliance input. 
The openings shall exchange directly, or by ducts, with 
the outdoor spaces (crawl or attic) that freely exchange 
with the outdoors (Figure 2).

Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical 
ducts, the openings and ducts must have a minimum free 
area of one square inch per 4,000 Btuh of total appliance 
input (Figure 3, page 7). Attics or crawl spaces must 
connect freely with the outdoors if they are the source of 
air for combustion and ventilation.

Содержание G7XC Series

Страница 1: ...e for future reference GAS FURNACES Installation Instructions Upflow Horizontal Model 92 1 AFUE DO NOT DESTROY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE FIRE OR EXPLOSION HAZARD Failure to follow safe...

Страница 2: ...CE INSTALLATION 12 General Requirements 12 Direct Vent 2 Pipe Applications 12 Upflow Installation 12 Side Return Air Inlet 12 Bottom Return Air Inlet 12 Horizontal Installation 12 Bottom Panel Removal...

Страница 3: ...nd position as specified in Table 1 page 5 Provide adequate combustion and ventilation air to the furnace space as specified on pages 4 8 Provide adequate clearances around the vent air intake termina...

Страница 4: ...stallation in a Garage WARNING Do not place combustible material on or against the furnace cabinet or within 6 inches of the vent pipe Do not place combustible materials including gasoline and any oth...

Страница 5: ...e operating at maximum speed Do not operate a summer exhaust fan 6 Follow the lighting instructions Place the appliance being inspected into operation Adjust the thermostat so appliance is operating c...

Страница 6: ...inside the house resulting in improper furnace operationorunsafeconditionssuchasflameroll out It is imperative that sufficient air exchange with the outdoors is provided to prevent depressurization Ad...

Страница 7: ...d at 45 000 Btuh input and a furnace rated at 75 000 Btuh requires a volume of 6 000 cubic feet 50 x 45 75 6 000 to be considered unconfined If the space has an 8 foot ceiling the floor area of the sp...

Страница 8: ...ible surfaces However itisgoodpracticetoallowspaceforconvenience in installation and service VENTING REQUIREMENTS This furnace is classified as a Category IV appliance which requires special venting m...

Страница 9: ...ed areas and do not terminate above any public walkways If venting horizontally a side wall vent kit is available according to the pipe diameter size of the installation kit 904349 Please follow the i...

Страница 10: ...ted in the Table For extremely cold climates or for conditions of short furnace cycles i e set back thermostat conditions the last 18 inches of vent pipe can be reduced It is acceptable to reduce from...

Страница 11: ...is installed which uses the furnace blower to provide airflow over the indoor coil the coil must be installed downstream on the outlet side of the furnace or in parallel with the furnace If a cooling...

Страница 12: ...oranycombustiblematerialother than wood flooring The G7XC gas furnace may be installed directly on combustible wood flooring or supports For venting guidelines and specifications see Venting Requirem...

Страница 13: ...m panel 2 out through the front of the furnace 7 Reassemble the furnace in reverse order Inducer Assembly Rotation WARNING Inducer rotation must be completed before the furnace is connected to gas and...

Страница 14: ...are included in the extra parts bag that is supplied with the purchase of your furnace Depending on your particular installation some of these components are optional and may not be used Please refer...

Страница 15: ...of the condensate drain lines will depend on the configuration selected in Table 4 page 14 The drain lines can be routed out the left or right side of the furnace but must maintain a downward slope t...

Страница 16: ...nd or damage to the furnace Leak Check WARNING FIRE OR EXPLOSION HAZARD Never test for gas leaks with an open flame Check all connections using a commercially available soap solution A fire or explosi...

Страница 17: ...B 7 See Note B Right Side Entry Left Side Entry 1 7 4 See Note A See Note A 3 9 5 8 9 3 5 6 2 Figure 19 Typical Gas Connection ITEM and COMPONENT 1 Automatic Gas Valve w manual shut off 2 Burner Asse...

Страница 18: ...any of the original wires supplied with the furnace the replacement wire must be copper wiring and have a temperature rating of at least 105 F 40 C Low Voltage Wiring The thermostat must be installed...

Страница 19: ...Figure 21 or the wiring diagram label inside of the control door Twinning The control boards on fixed speed furnaces are capable of being twinned to other furnaces of the same series only if the follo...

Страница 20: ...OT install a jumper wire across a switch to defeat its function Verify the blower door is in place closing the door switch in the line voltage circuit Verify the gas line has been purged and all conne...

Страница 21: ...door must be installed during unattended operation 1 Remove the burner compartment door 2 Set the thermostat above room temperature and observe the ignition sequence The burner flame shouldcarryoveri...

Страница 22: ...he heating cooling and fan modes are described below Refer to the field and furnace wiring diagrams Figure 15 page 16 Figure 16 page 17 and Figure 23 page 29 Heating Cycle 1 The thermostat calls for h...

Страница 23: ...n monoxide poisoning that could result in personal injury or death Lubrication DESCRIPTION OF COMPONENTS Thedescriptionsbelowarevariousfunctionalcomponents that affect the operation and shutting down...

Страница 24: ...furnace operates when the Blower Limit Switch is reset contact a qualified service technician to identify and repair the problem If the furnace still doesn t operate check the Flame Roll out Switches...

Страница 25: ...EW 4 KNOCKOUTS BOTH SIDES 1 LEFT SIDE RIGHT SIDE HOLE FOR THERMOSTAT CONDENSATE HOLE FOR ELECTRIC CONDENSATE HOLE FOR ELECTRIC 3 7 HOLE FOR THERMOSTAT 3 HOLE FOR VENT PIPE FLUE INLET AIR Figure 25 Fur...

Страница 26: ...1 085 36 1 045 37 1 0 1 1 1 350 30 1 315 30 1 280 31 1 245 31 1 205 33 1 170 33 1 135 35 1 100 36 0 1 1 1 1 390 29 1 350 29 1 315 30 1 275 31 1 240 2 1 200 33 1 160 34 1 125 35 1 1 1 1 1 420 29 1 380...

Страница 27: ...0 65 1 305 67 1 260 69 1 210 72 1 165 75 1 120 78 1 0 0 0 1 465 59 1 420 62 1 375 63 1 330 65 1 290 67 1 245 70 1 200 72 1 155 75 0 1 0 0 1 555 56 1 510 58 1 470 59 1 425 61 1 380 63 1 340 65 1 295 67...

Страница 28: ...176 353 48 75 375 750 104 35 173 346 50 72 360 720 106 34 170 340 52 69 346 692 108 33 167 333 54 67 333 667 110 33 164 327 56 64 321 643 112 32 161 321 58 62 310 621 114 32 158 316 60 60 300 600 116...

Страница 29: ...9 0 9 0 MANIFOLD PRESSURE 8 000 to 10 000 FT 51 51 51 51 ORIFICE SIZE 8 5 8 5 8 5 8 5 MANIFOLD PRESSURE Table 12 High Altitude Deration Propane Gas PROPANE ALTITUDE ABOVE SEA LEVEL INPUT BTU 46 000 61...

Страница 30: ...MODELS SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT COOL FAN SPEED HEAT HIGH COOL FAN HEAT MH ML LOW GREEN BLACK WHITE YELLOW YELLOW BLACK RED BLACK BLACK BLACK GREEN BLACK BLACK WHITE BLACK WHITE RED GREY...

Страница 31: ...See View A See View A PVC Cap Plug Exhaust Vent See View B Drain Line Attached to 3 4 x 1 2 Hose Barb PVC TEE and Reducer Option 2 X See View C Inline Drain This drain not needed if X is less than 6...

Страница 32: ...ed with J Trap or field supplied loop Inline Drain Header Box Drain VIEW D VIEW E Inline Drain See View G See View G Plug See View E See View E See View D Drain Line Attached to 3 4 x 1 2 Hose Barb Ex...

Страница 33: ...t Air PVC Cap PVC Cap See View H See View I See View H Plug See View I Plug See View K See View K See View J Exhaust Vent PVC TEE and Reducer Drain Line Attached to 3 4 x 1 2 Hose Barb See View J Inle...

Страница 34: ...t as Close to Furnace as Possible Straight Neoprene Couplings with 2 Hose Clamps Upward Pitch 1 4 Per Foot Exhaust Vent 5 Combustion Air Vent Pipe 7 90 Elbows 90 Elbow Exhaust Vent Combustion Air Exha...

Страница 35: ...nsor 7 Gas Manifold 8 Gas Valve 9 Igniter 10 Inducer Assembly 11 Limit Switch 12 Main Air Limit Switch 13 Motor Control Board 14 Pressure Switch s B C D cabinets only 15 Roll Out Switch s 16 Transform...

Страница 36: ...ly for combustion and ventilation YES NO Installation Altitude ____________________ FT Deration Percentage ___________________ Furnace Input _______________________ Btuh Supply Air Temperature _______...

Отзывы: