background image

6

nor transmit noise to the interior of the structure. 
Refrigerant and electrical line should be routed 
through suitably waterproofed openings to 
prevent water leaking into the structure.

INSTALLING THE INDOOR UNIT

The indoor section should be installed before 
proceeding with routing of refrigerant piping. 
Consult the Installation Instructions of the indoor 
unit (i.e.: air handler, furnace, etc.) for details 
regarding installation.

CONNECTING REFRIGERANT
TUBING BETWEEN THE INDOOR
AND OUTDOOR UNIT

 CAUTION:

This system utilizes R-410A refrigerant 
with POE oil. When servicing, cover or 
seal openings to minimize the exposure 
of the refrigerant system to air to 
prevent accumulation of moisture and 
other contaminants.

General — Once outdoor and indoor unit 
placement has been determined, route refrigerant 
tubing between the equipment in accordance with 
sound installation practices. Refrigerant tubing 
should be routed in a manner that minimizes the 
length of tubing and the number of bends in the 
tubing. Refrigerant tubing should be supported 
in a manner that the tubing will not vibrate or 
abrade during system operation. Tubing should 
be kept clean of foreign debris during installation 
and installation of a liquid line filter drier is 
recommended if cleanliness or adequacy of 
system evacuation is unknown or compromised. 
Every effort should be made by the installer 
to ensure that the field installed, refrigerant 
containing components of the system have been 
installed in accordance with these instructions 
and sound installation practices so as to insure 
reliable system operation and longevity. 

The maximum recommended interconnecting 
refrigerant line length is 75 feet, and the 
vertical elevation difference between the indoor 
and outdoor sections should not exceed 20 
feet. Consult long line application guide for 
installations in excess of these limits.

Filter Dryer Installation — A filter dryer is 
provided with the unit and must be installed in the 
liquid line of the system. If the installation replaces 
a system with a filter dryer already present in the 

liquid line, the filter dryer must be replaced with 
the one supplied with the unit. The filter dryer 
must be installed in strict accordance with the 
manufacturer’s installation instructions.

Optional Equipment — Optional equipment 
(e.g.: liquid line solenoid valves, etc.) should 
be installed in strict accordance with the 
manufacturer’s installation instructions.

ELECTRICAL CONNECTIONS

 WARNING:

Turn off all electrical power at the main 
circuit box before wiring electrical 
power to the outdoor unit. Failure to 
comply may cause severe personnel 
injury or death.

Wiring Diagram/Schematic — A wiring diagram/
schematic is located on the inside cover of 
the electrical box of the outdoor unit. The 
installer should become familiar with the wiring 
diagram/schematic before making any electrical 
connections to the outdoor unit.

Outdoor Unit Connections — The outdoor 
unit requires both power and control circuit 
electrical connections. Refer to the unit wiring 
diagram/schematic for identification and location 
of outdoor unit field wiring interfaces.

Control Circuit Wiring — The outdoor unit is 
designed to operate from a 24 VAC Class II control 
circuit. Control circuit wiring must comply with 
the current provisions of the “National Electrical 
Code” (ANSI/NFPA 70) and with applicable local 
codes having jurisdiction.

Thermostat connections should be made in 
accordance with the instructions supplied with 
the thermostat, and with the instructions supplied 
with the indoor equipment. A typical residential 
installation with a heat pump thermostat and air 
handler are shown below. 

Electrical Power Wiring — Electrical power 
wiring must comply with the current provisions 
of the “National Electrical Code” (ANSI/
NFPA 70) and with applicable local codes 
having jurisdiction. Use of rain tight conduit is 
recommended. Electrical conductors shall have 
minimum circuit ampacity in compliance with the 
outdoor unit rating label. The facility shall employ 
electrical circuit protection at a current rating no 
greater than that indicated on the outdoor unit 
rating label. Refer to the unit wiring diagram for 
connection details.

Содержание DT4BE

Страница 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Страница 2: ...2...

Страница 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Страница 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Страница 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Страница 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Страница 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Страница 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Страница 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Страница 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Страница 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Страница 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Страница 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Страница 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Страница 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Страница 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Страница 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Страница 23: ...23...

Страница 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Отзывы: