background image

4

TO OPERATE YOUR HEAT PUMP 
FOR AUTOMATIC COOLING AND 

HEATING —

 

1.  Set the thermostat system switch to AUTO 

and the thermostat fan switch to AUTO. (See 
Figure 1)

 

Note:  Thermostats will vary. Some models 
will not include the AUTO mode, and others 
will have the AUTO in place of the HEAT and 
COOL, and some will include all three.

2.  Set the thermostat temperature to the 

desired heating and cooling temperature 
level(s). The outdoor unit and the indoor 
blower will then cycle on and off in either 
the heating or cooling mode of operation 
as required to automatically maintain the 
indoor temperature within the desired 
limits.

TO SHUT OFF YOUR HEAT PUMP —

Set the thermostat system switch to OFF and 
the thermostat fan switch to AUTO. (See Figure 
1)
 The system will not operate, regardless of the 
thermostat temperature selector(s) setting.

TO OPERATE THE INDOOR BLOWER 

CONTINUOUSLY —

Set the thermostat fan switch to ON (See Figure 
1)
. The indoor blower will start immediately, and 
will run continually until the fan switch is reset 
to AUTO.

The continuous indoor blower operation can be 
obtained with the thermostat system switch set 
in any position, including OFF.

The continuous indoor blower operation is 
typically used to circulate the indoor air to 
equalize a temperature unbalance due to a sun 
load, cooking, or fireplace operation.

TO MAINTAIN YOUR HEAT PUMP —

 CAUTION:

Make sure the electrical power to the 
outdoor unit and the furnace/air handler 
is disconnected before doing the 
following recommended maintenance.

1. Regularly:

a.  Clean or replace the indoor air filter at the 

start of each heating and cooling season, 
and when an accumulation of dust and dirt 
is visible on the air filter. Inspect the filter 
monthly.

b.  Remove any leaves and grass clippings from 

the coil in the outdoor unit, being careful 
not to damage the aluminum fins. 

c.  Check for any obstruction such as twigs, 

sticks, etc.

 CAUTION:

Do not over-oil, or oil motors not 
factory-equipped with oil tubes. The 
compressor is hermetically “sealed” 
and does not require lubrication.

2.  Before Calling a Service Technician, Be 

Certain:

a.  The unit thermostat is properly set — see 

“To Operate Your Heat Pump for Cooling” 
and “To Operate Your Heat Pump for 
Heating.”

b.  The unit disconnect fuses are in good 

condition, and the electrical power to the 
unit is turned on.

Read Your Warranty

Please read the separate warranty document 
completely. It contains valuable information 
about your system.

GENERAL INFORMATION

Read the following instructions completely before 
performing the installation.

 CAUTION:

This unit uses refrigerant R-410A. DO 
NOT under any circumstances use 
any other refrigerant besides R-410A 
in this unit. Use of another refrigerant 
will damage this unit.

Outdoor Unit Section — Each outdoor unit 
is shipped with a refrigerant charge adequate 
to operate the outdoor section with an indoor 
matching coil or air handler. Units with braze 
connections include the proper amount of 

Содержание DT4BE

Страница 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Страница 2: ...2...

Страница 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Страница 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Страница 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Страница 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Страница 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Страница 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Страница 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Страница 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Страница 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Страница 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Страница 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Страница 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Страница 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Страница 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Страница 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Страница 23: ...23...

Страница 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Отзывы: