background image

3

and indoor blower will both cycle on and 
off to maintain the indoor temperature at 
the desired heating level.

 

NOTE:  If the thermostat temperature level 
is re-adjusted, or the thermostat system 
switch is repositioned, the outdoor unit 
may not start immediately. The outdoor unit 
contains a protective timer circuit which 
holds the unit off for approximately five 
minutes following a previous operation, 
or the interruption of the main electrical 
power.

 

Emergency Heat:

 

The thermostat includes a system switch 
position termed EM. HT. This is a back-up 
heating mode to be used only if there is 
a suspected problem with the outdoor 
unit. With the system switch set to EM. 
HT. the outdoor unit will be locked off, 
and supplemental heat (typically electric 
resistance heating) will be used as a source 
of heat. Sustained use of electric resistance 
heat in place of the heat pump will result 
in an increase in electric utility costs.

 

Defrost:

  During cold weather heating operation, 

the outdoor unit will develop a coating 
of snow and ice on the heat transfer coil. 
This is normal, and the unit will periodically 
defrost itself. During the defrost cycle, the 
outdoor fan will stop, and the compressor 
will continue to run and heat the outdoor 
coil, causing the snow and ice to melt. 
After the snow and ice have melted, some 
steam may rise from the outdoor unit as 
the warm coil causes some melted frost to 
evaporate.

Figure  1. Typical Thermostat

OPERATING INSTRUCTIONS

TO OPERATE YOUR HEAT PUMP 

FOR COOLING —

1.  Set the thermostat system switch to COOL 

and the thermostat fan switch to AUTO.  
(See Figure 1)

2.  Set the thermostat temperature to the 

desired temperature level using the tem-
perature selector. Please refer to the sepa-
rate detailed thermostat user’s manual for 
complete instructions regarding thermostat 
programming. The outdoor unit and indoor 
blower will both cycle on and off to maintain 
the indoor temperature at the desired cool-
ing level.

 

NOTE: If the thermostat temperature level 
is re-adjusted, or the thermostat system 
switch is repositioned, the outdoor unit 
may not start immediately. The outdoor unit 
contains a protective timer circuit which 
holds the unit off for approximately five 
minutes following a previous operation, 
or the interruption of the main electrical 

power.

TO OPERATE YOUR HEAT PUMP 

FOR HEATING —

1.  Set the thermostat system switch to HEAT 

and the thermostat fan switch to AUTO.  
(See Figure 1)

2.  Set the thermostat temperature to the 

desired temperature level using the 
temperature selector. Please refer to 
the separate detailed thermostat user’s 
manual for complete instructions regarding 
thermostat programming. The outdoor unit 

TEMPERATURE
SENSOR

FAN
SWITCH

SYSTEM
MODE

Содержание DT4BE

Страница 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Страница 2: ...2...

Страница 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Страница 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Страница 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Страница 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Страница 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Страница 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Страница 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Страница 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Страница 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Страница 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Страница 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Страница 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Страница 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Страница 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Страница 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Страница 23: ...23...

Страница 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Отзывы: