background image

13

Table 2. Module Wiring Troubleshooting

3.  Defrost board speed-up.  With compressor 

running in heat mode, next jump the “Test” 
pin to “C” on terminal strip. This will initiate 
a defrost test in 5, 10 or 15 seconds (This 
is determined by the 30, 60 or 90 minute 
defrost pin settings. The factory setting will 
be 30 minutes).  Note that this will bypass the 
compressor off delay when the unit goes into 
defrost test and if left in defrost test, the delay 
will be bypassed when the test is terminated 
by the processor.  If the jumper is removed 
before the test is over the processor will 
perform the remainder of a normal defrost.  
See step 2 above.

4. Remove the jumpers.

Note: The delay/no-delay pin concerns compressor 
operation during defrosts. The default setting is 
delay. Reciprocating compressors should only 
use this setting in conjunction with an approved 
hard start kit. Scroll compressors that have noise 
issues while going into or coming out of defrost 
should use this 30 second delay to reduce the 

defrost noise. To switch from no-delay to delay 
remove the pin from the “no-delay” pin location 
and shift it to the “delay” pin location.

Speed up changes:

Manually initiating a defrost will cause the 

compressor to run continually when entering 
defrost.

Normal defrost operation:

To test normal defrost operation when the 
temperature is above 35°F, jumper “R” to 
“DFT” on the 624656 board and allow the unit 
to run for 30 minutes.  Defrost will continue 
until the “R” to “DFT” jumper is removed or 
for 10 minutes.  Remove the jumper.

The 5 minute time delay feature can be shortened 
1 time to 1 second by jumping the “Test” to “C” 
terminal.  Remove the jumper and repeat as 
desired.

Note: If jumper is left on the “Test” to “common” 
pins permanently, the defrost cycle will become 
inoperable. 

Miswired Module Indication

Recommended Troubleshooting  Action

Green LED is not on, module does not power up

•  Determine if both 

R & C module terminals are connected.

•  Verify voltage is present at module’s 

R & C terminals. 

Green LED intermittent, module powers up only when 
compressor runs

•  Determine if 

R & Y terminals are wired in reverse.

•  Verify modules R & C terminals have a constant source.

Trip LED is on, but system and compressor check OK

•  Verify 

Y terminal is connected to 24VAC at contactor coil.

•  Verify voltage at contactor coil falls below 0.5VAC when off.
•  Verify  24VAC  is  present  across 

Y & C when thermostat demand 

signal is preset. If not, R & C are reversed wired.

TRIP LED & ALERT LED flashing together

•  Verify 

R & C terminals are supplied with 19 - 28VAC.

ALERT Flash CODE 3 displayed incorrectly
(Compressor short cycling)

•  Verify 

Y terminal is connected to 24VAC at contactor coil.

•  Verify voltage at contactor coil falls below 0.5VAC when off.

ALERT Flash Code 5, 6, or 7 displayed incorrectly
(Open Circuit, Open Start Circuit or Open Run 
Circuit) 

•  Verify  the  compressor  run  and  start  wires  are  routed  through  the 

module’s current sensing holes.

•  Verify the 

Y terminal is connected to 24VAC at contactor coil.

•  Verify voltage at contactor coil falls below 0.5VAC when off.

ALERT Flash Code 6 (Open Start Circuit) displayed 
for Code 7 (Open Run Circuit) or vice-versa

•  Verify  the  compressor  run  and  start  wires  are  routed  through  the 

correct module sensing holes.

ALERT Flash Code 8 displayed incorrectly (Welded 
Contactor) 

•  Determine if module’s 

Y terminal is connected.

•  Verify 

Y terminal is connected to 24VAC at contactor coil. 

•  Verify  24VAC  is  present  across 

Y & C when thermostat demand 

signal is present. If not, R & C are reversed wired.

•  Verify voltage at contactor coil falls below 0.5VAC when off.
•  Review Thermostat Demand Wiring (page 10) for 

Y & C wiring.

Содержание DT4BE

Страница 1: ...t eliminate your problem call your servicing contractor Heat Pump Principle of Operation USER S INFORMATION 5 4 1 2 3 6 5 4 3 2 1 6 SUMMER COOLING 1 Indoor air enters the air handler section 2 Cold he...

Страница 2: ...2...

Страница 3: ...and ice to melt After the snow and ice have melted some steam may rise from the outdoor unit as the warm coil causes some melted frost to evaporate Figure 1 Typical Thermostat OPERATING INSTRUCTIONS T...

Страница 4: ...re the electrical power to the outdoorunitandthefurnace airhandler is disconnected before doing the following recommended maintenance 1 Regularly a Clean or replace the indoor air filter at the start...

Страница 5: ...operational checkout of the equipment BrazingOperations Installationofequipment may require brazing operations Safety codes must be complied with Safety equipment e g safety glasses work gloves fire e...

Страница 6: ...installationreplaces a system with a filter dryer already present in the liquid line the filter dryer must be replaced with the one supplied with the unit The filter dryer must be installed in strict...

Страница 7: ...power to the outdoor unit ensure that the unit has been properly and securely grounded and that power supply connections have been made at both the facility power interface and outdoor unit Outdoor Un...

Страница 8: ...stat Green Red Brown G R W2 Orange Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Standard Air Handler W2 C W NOTE Jumper betweenW2 and E is required when no OD T Stat is used F...

Страница 9: ...Red White G R Black O Y R C Air Handler Heat Pump OD Section Typical Heat Pump with Outdoor Thermostat and Air Handler W2 C W E A typical installation with a heat pump thermostat air handler and heat...

Страница 10: ...tection The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices LED Description See Figure 2 POWERLED Green indicatesvoltageispresent at the power connection of...

Страница 11: ...he unit is being installed Example 1 Dry climate of Southern Arizona A 90 minute setting is recommended Example 2 Moist climate of Seattle Washington A 30 minute setting is recommended To set the cycl...

Страница 12: ...if voltage at disconnect is low Excessive liquid refrigerant in compressor Compressor bearings are seized ALERT Flash Code 4 Yellow LED Locked Rotor Run capacitor has failed Low line voltage contact...

Страница 13: ...ermanently the defrost cycle will become inoperable Miswired Module Indication Recommended Troubleshooting Action Green LED is not on module does not power up Determine if both R C module terminals ar...

Страница 14: ...the checkout procedures supplied with the equipment Adjustment of Refrigerant Charge CAUTION Split system heat pump equipment contains liquid and gaseous refrigerantunderpressure Adjustment of refrige...

Страница 15: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 2 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 16: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 3 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 17: ...90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res s ure ps ig Add refrigerant when below curve Remove refrigerant when above curve 4 Ton Heat Pump TXV Cooling Charging Chart 200 225...

Страница 18: ...m Cooling Charts 5 Ton Heat Pump TXV Cooling Charging Chart 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 70 75 80 85 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid P res...

Страница 19: ...Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Suc Liquid Disch Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press Press Temp Press P...

Страница 20: ...58 272 114 73 299 122 87 327 129 103 368 141 122 406 157 140 443 174 45 251 105 59 278 112 74 304 120 88 331 127 104 375 138 123 413 153 141 450 167 030K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 21: ...55 256 113 70 279 119 85 301 126 100 334 136 116 360 148 132 386 160 41 241 104 56 262 111 71 284 117 86 305 124 101 341 133 117 367 144 133 393 154 042K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60...

Страница 22: ...52 116 55 266 123 67 280 131 80 294 138 93 318 143 106 337 148 119 357 152 43 259 114 56 272 121 68 285 129 81 298 136 94 325 141 107 344 143 120 364 146 060K OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 5...

Страница 23: ...23...

Страница 24: ...PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER 708695B Replaces 708695A Specifications illustrations subject to change without notice or incurring obligations O Fallon MO Printed in U...

Отзывы: