Coil and Tube Installation
(contd)
9. Connect the coil wiring to the bus bar terminals (5). Attach the wiring
per the markings on the insulation jacket and the bus bar numbering.
One end of the coil attaches to the first bus bar while the opposite end
attaches to the second bus bar.
NOTE:
Bi-Filar and multiple terminated coils have more than one terminal
at each end of the coil. Attach all terminations at one end to the common
bus bar, and all terminations at other end to other common bus bar.
1
2
3
4
5
Figure 8
Coil and Tube Installation
1. Air heater and exhaust vent screws
(4 on each hub)
2. Cushion and hold-down screws
3. Glass coil tube
4. Coil
5. Bus bar terminals
System Wiring
Schematics and Wiring Diagrams
Refer to the Addendum to this manual for dryer schematics and wiring
diagrams.
Power Input
See Figure 9 for connections. Service requirement is 360
−
415 Vac 50 Hz or
440
−
480 Vac 60 Hz, 3 phase at 50 amperes. Class J fusing required.
WARNING:
If plant supply is not through current-limiting Class J 50 amp
fusing, customer is required to follow arc flash hazard criteria and label
appropriately.