Application 

 

The FAST-STAT Model 3000 is designed to add additional control 
wiring between the thermostat and indoor unit or between the 
indoor unit and outdoor unit. 

 

Before Installing This Product 

 

1.

 

Read Instructions. If you have any questions please contact 
our tech support line 

 

2.

 

This product is designed for use only on 24-volt AC circuits 
supplied by a Class 2 transformer. 

 

3.

 

This product is only to be installed by qualified technicians. 

 

4.

 

To  avoid  risk  of  electrical  shock  or  equipment  damage, 
disconnect power before beginning installation. 

 

Sender Installation 

 

When  used  to  add  wiring  between  the  thermostat  and  indoor 
unit,  the  sender  is  installed  in  the  wall  space  behind  the 
thermostat. Enlarge the opening around the thermostat cable so 
that  the  sender  can  be  inserted  into  the  wall  cavity.  Once  the 
connections  to  the  cable  and  thermostat  are  completed,  insert 
the sender into the wall cavity. The sender hangs by its leads and 
does not require any mounting.  

 

When  used  to  extend  wiring  between  the  indoor  and  outdoor 
units,  the  sender  is  connected  to  the  indoor  unit  terminal  strip 
or  leads.  It  then  hangs  from  the  terminal  strip  or  is  grouped 
together with the other leads. 

 

Receiver Installation 

 

The  receiver  module  is  normally  mounted  inside  the  cabinet  of 
the indoor or outdoor unit near the other controls. If there is no 
space inside the cabinet, the module may be located in any dry 
location without exposure to high temperatures or water. 

 

Wiring  

 

1.

 

See included 

Wiring Diagrams 

for your application. 

 

2.

 

The  power  supply  must  be  between  20  to  30  volts  for 
proper  operation.  The  total  connected  load  must  not 
exceed  2  amps.  The  connected  load  cannot  operate  at  a 
voltage of more than 30 volts (not intended for line voltage 
control). 

 

Sequence of Operation  

 

The  receiver  has  3  normally-open  relays,  one  each  for  the 
yellow,  green  &  white  wires.  One  side  of  each  relay  contact  is 
connected  to  a  red  wire  which  is  then  connected  to  the 
transformer  “R”  terminal.  When  any  relay  is  energized,  it  will 
connect its load to the transformer “R” terminal. 

 

A  24  volt  input  on  the  sender  white 
wire will cause a 24 volt output on the 
receiver white wire. A 24 volt input on 
the sender green wire will cause a 24 
volt  output  on  the  receiver  green 
wire.  A  24  volt  input  on  the  sender 
yellow wire will cause a 24 volt output 
on  both  the  receiver  green  &  yellow 
wires.  

Troubleshooting 

– not operating 

 

1.

 

Check  that  there  is  24  volts  between  the  receiver  red  and 
black wires. 

 

2.

 

Check  that  the  sender  purple  and  receiver  purple  wires  are 
connected  together  (and  not  crossed).  If  they  are  crossed, 
then a call for heating will provide cooling and a call for fan 
or cooling will provide heat. 

 

3.

 

At  the  receiver,  join  the  receiver  purple  and  red  (red  wire 
going  to  the  sender)  wires  together.  All  3  relays  in  the 
receiver  should  energize  and  switch  on  their  connected 
loads. If the connected loads do not start, then measure the 
voltage from the receiver green, yellow & white wires to the 
transformer common. There should be a reading of 24 volts 
AC  at  each  wire.  If  there  is  voltage  at  the  yellow,  green  & 
white wires but the loads do not start, then check the wiring 
of the connected loads. If the receiver relays cannot be made 
to energize by this test, then the receiver may be defective. 

 

4.

 

If test #3 works OK but it doesn’t operate when connected to 
the sender then join together the 2 wires from the cable that 
are connected to the sender red & purple wires. This should 
cause a 24 volt output on the receiver green, yellow & white 
wires (same as test #3). If the receiver relays do not energize 
during this test, then there is a problem with the cable that 
connects the receiver and the sender together.   

 

5.

 

If test #4 works OK but it doesn’t operate when connected to 
the sender, then jumper transformer power “R” (sender red 
wire)  to  the  sender  green,  yellow  &  white  wires  (one  at  a 
time). This should cause the loads connected to the receiver 
green, yellow & white wires to start. If this test fails, then the 
sender  may  be  defective.  If  this  test  works  then  the  FAST-
STAT  and  the  field  wiring  is  OK.  The  problem  may  be  a 
compatibility issue with the thermostat. 

 

Troubleshooting 

– 2 stage compressor 

 

In  some  installations  the  indoor  unit  fan  may  operate  in  high 
speed  when  the  outdoor  unit  is  running  in  low  speed.  This  is 
caused by the sender having a 12 volt DC voltage on the indoor 
unit Y2 terminal. Some furnaces or air handlers mistake this 12 
volts DC for 24 volts AC and  switch the fan into high speed.  To 
correct this if it occurs add an isolation relay as follows: 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Tech Support Line: 1-800-775-4750 ext. 3

 

Monday 

– Friday: 8:30am to 4:30pm (

Pacific Standard Time) 

FAST-STAT

     

Model 3000 Installation Instructions 

 

Purple

Yellow

White

Sender

C

R

Y1

Y2

Relay

coil

 