4 Commissioning
BU 0135 en-4118
63
4.2.1 Connection
In order to provide basic operational capability, after the device has been attached to the motor or the
wall mounting kit, the power and motor lines must be connected to the relevant terminals
(
Section 2.3.2 "Electrical connection of power unit").
It is also essential for the device to be provided with a 24 V DC control voltage.
Information
Control voltage
The 24 V control voltage that is required can be implemented by means of an integrated (SK CU4-24V-…) or
external (SK TU4-24V-…) optional mains module or a comparable 24 V DC power source (
Section 2.3.3
"Electrical connection of the control unit").
4.2.2 Configuration
The device can be configured for the majority of operating modes by setting potentiometers (P1-P4)
and DIP switches (S1). For extended functions or for diagnostic purposes it may be necessary to
adjust or view individual parameters.
The basic steps for successful start-up of the motor starter are listed in the following. To begin with, it
must be decided whether the start-up is to take place via DIP switches and the potentiometers, or
exclusively by means of parameter setting.
The software adaptations that are made via the
parameters
are only
taken into consideration
if
parameter
P130
is set to a value of
( 1 )
.
Any
parameters that are not listed here
always have an influence
on the functionality of the motor
starter, irrespective of the setting of parameter
P130
. However, they always remain in the factory
setting at
P130
= "
0
".
Step
Commissioning via
Switches / potentiometers
(Hardware adaptations)
Parameter settings
(Software adaptation)
Element
Default
Parameter
Default
1. Parameter source
P130 = 0
{ 0 }
P130 = 1
{ 0 }
2. Rated motor current
P1
-
1)
P203
{ 3 }
3. Locking time
P2
-
1)
P570
{ 0.5 }
4. Start voltage
P3
-
1)
P210
{ 50 }
5. Acceleration time
P4
-
1)
P102
{ 1 }
6. Run time
P103
{ 1 }
7. Automatic starting
S1-DIP1
{ OFF }
P428
{ 0 }
8. Phase sequence detection
S1-DIP2
{ OFF }
P581
{ 0 }
9. Switch-off mode
S1-DIP3/4
{ OFF/OFF } P108
{ 2 }
10. Save data permanently
P550
= 1
2)
{ 0 }
1) For technical manufacturing reasons, no clear factory settings (defaults) can be stipulated.
2) After completing the software adaptations, the data must be transferred from the RAM memory of the device to the Flash memory in
order to retain them permanently. Otherwise the data changes will be lost when the device is switched off.
Table 9: Configuration - comparison of hardware and software adaptation
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...