8 Additional information
BU 0600 en-3221
235
8.4.2 Reduced overcurrent due to time
The possible overload capacity changes depending on the duration of an overload. Several values are
cited in this table. If one of these limiting values is reached, the frequency inverter must have sufficient
time (with low utilisation or without load) in order to regenerate itself.
If operated repeatedly in the overload region at short intervals, the limiting values stated in the tables
are reduced.
230V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency
[kHz]
Time [s]
> 600
60
30
20
10
3.5
3...8
110%
150%
170%
180%
180%
200%
10
103%
140%
155%
165%
165%
180%
12
96%
130%
145%
155%
155%
160%
14
90%
120%
135%
145%
145%
150%
16
82%
110%
125%
135%
135%
140%
400V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency
[kHz]
Time [s]
> 600
60
30
20
10
3.5
3...6
110%
150%
170%
180%
180%
200%
8
100%
135%
150%
160%
160%
165%
10
90%
120%
135%
145%
145%
150%
12
78%
105%
120%
125%
125%
130%
14
67%
92%
104%
110%
110%
115%
16
57%
77%
87%
92%
92%
100%
Table 14: Overcurrent relative to time
Содержание SK 510P
Страница 1: ...BU 0600 en NORDAC PRO SK 500P Manual with installation instructions...
Страница 4: ...NORDAC PRO SK 500P Manual with installation instructions 4 BU 0600 en 3221...
Страница 223: ...7 Technical data BU 0600 en 3221 223...
Страница 233: ...8 Additional information BU 0600 en 3221 233 8 3 4 EU Declaration of Conformity...
Страница 253: ...Key word index BU 0600 en 3221 253...
Страница 254: ...NORDAC PRO SK 500P Manual with installation instructions 254 BU 0600 en 3221...
Страница 255: ...Key word index BU 0600 en 3221 255...
Страница 256: ...6076002 3221...