1.8 USS
– Frequency inverter settings
BU 0050 GB-3111
Subject to technical amendments
57
Parameter
Setting value / Description / Note
Comments
P740
... [-01]
…
... [-23]
Process data Bus In
(Process data Bus In)
SK 540E / SK 545E
0000 ... FFFF (hex)
This
parameter
informs
about the actual control
word and the setpoints that
are transferred via the bus
systems.
For display, a BUS system
must be selected in P509
[-01 ] =
Control word
Control word, source from
P509.
[-02] =
Setpoint 1
[-03] =
Setpoint 2
[-04] =
Setpoint 3
[-05] =
Setpoint 4
[-06] =
Setpoint 5
Setpoint data from main
setpoint (P510 [-01]).
[-07] =
Bus I/O In Bits (P480)
The displayed value depicts all
Bus In bit sources linked with
OR
.
[-08] =
Parameter data In 1
[-09] =
Parameter data In 2
[-10] =
Parameter data In 3
[-11] =
Parameter data In 4
[-12] =
Parameter data In 5
Data during parameter transfer:
Order label (AK),
Parameter
number (PNU),
Index (IND),
Parameter value (PWE 1/2)
[-13] =
Setpoint 1
[-14] =
Setpoint 2
[-15] =
Setpoint 3
[-16] =
Setpoint 4
[-17] =
Setpoint 5
Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])
[-18] =
Control word PLC
Control word, source PLC
[-19] =
Setpoint 1
[-20] =
Setpoint 2
[-21] =
Setpoint 3
[-22] =
Setpoint 4
[-23] =
Setpoint 5
Setpoint data from the PLC.
P741
... [-01]
…
... [-06]
Process data Bus Out
(Process data Bus Out)
SK 300E, SK 700E, SK 750E
0000 ... FFFF (hex)
Displays the actual status word and actual values.
[-01]
= Status word
[-02]
= Actual value 1 (P543)
[-03]
= Actual value 1 High byte
[-04]
= Actual value 2 (P544)
[-05]
= Actual value 3 (P545)
[-06]
= Bus I/O Out Bits (P481)