1.8 USS
– Frequency inverter settings
BU 0050 GB-3111
Subject to technical amendments
51
1.8.1.2
Extra functions
Parameter
Setting value / Description / Note
Comments
P502
... [-01]
…
... [-05]
Master function value
(Master function value)
SK 5xxE
1 ... 24
{ 0 }
Selection of master values (up to SK 535E: max. 3 master values, SK 540 and above: max. 5
master values:
[-01] =
Master value 1
[-02] =
Master value 2
[-03] =
Master value 3
SK 540E and
above:
[-04] =
Master value 4
[-05] =
Master value 5
Selection of possible setting values for master values:
0 =
Off
1 =
Actual frequency
2 =
Actual speed
3 =
Current
4 =
Torque current
5 =
State of digital inputs
and outputs
6 =
Reserved
7 =
Reserved
8 =
Setpoint frequency
9 =
Error message
10 =
Reserved
11 =
Reserved
12 =
Digit
al Out Bit 0…7
13 =
Reserved
14 =
Reserved
15 =
Reserved
16 =
Reserved
17 =
Value analog input 1
18 =
Value analog input 2
19 =
Setpoint frequency
master value
20 =
Setpoint frequency after
master value ramp
21 =
Actual frequency without
master value slip
22 =
Speed encoder
23 =
Actual freq. with slip
(from SW V2.0)
24 =
Master value, act. freq.
with slip
(from SW V2.0)
P503
Master function output
(Master function output)
SK 300E, SK 700E, SK 750E
1 ... 6
{ 0 }
To use the
master function output
, the inverter controller source must be selected in P509. Only
the master frequency (setpoint 1 and control word) is transferred with
Mode 1
, while the actual
values selected in P543, P544 and P545 are transferred in
Mode 2
.
In
Mode 3
a 32Bit actual position and a 16Bit setpoint speed (after ramp) is output. Mode 3 is
required for synchronous control with the POSICON option.
0 = Off
1 = USS mode 1
2 = CAN Mode 1
up to 250kBaud
3 = USS mode 2
4 = CAN Mode 2
up to 250kBaud
5 = USS mode 3
6 = CAN Mode 3
P503
Master function output
(Master function output)
SK 5xxE
1 ... 5
{ 0 }
To use the Master function output, the inverter controller source must be selected in
P509. The master value to be transmitted is determined via the BUS interface in
parameter P502.
0 = Off
1 = USS
2 =
CAN
(up to 250kBaud)
3 =
CANopen
4 =
System bus active
5 =
Sys.bus act.
P507
PPO Type
(PPO Type)
1 ... 4
{ 1 }
Type of PPO used (see Section 1.5.2 6)