4 Commissioning
BU 0250 en-3021
73
Pos: 196 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Inbetriebnahme [SK 1xxE, SK 2xxE, SK xxxE-FDS] @ 2\mod_1347364111083_388.docx @ 45181 @ 3 @ 1
4.5.4 Commissioning
Pos: 197 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Anschluss_01 [SK xxxE-FDS] @ 41\mod_1583921178361_388.docx @ 2596837 @ 4 @ 1
4.5.4.1
Connection
1. The connection of the AS-Interface cable (yellow) is established via the “
-ASI
”, “
-AUX
”, “
-AXS
” or “
-
ASS
” plug connector on option slot
M8
.
2. The connection of a two-wire line to supply with auxiliary power (“black cable”) is established via
the “
-AUX
” or “
-AXS
” plug connector on option slot
M8
(only if available). The supply should
preferably be effected via PELV.
(
Section 2.3.3 "Electrical connection of the control unit")
Pos: 198 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/AS-Interface [alle Geräte]/Anzeigen_01 [SK 2xxE-FDS] @ 20\mod_1519210045009_388.docx @ 2406758 @ 4 @ 1
4.5.4.2
Displays
The status of the AS interface is signalled by multi-
colour LEDs on option slot
M8
. A separate LED is
assigned to each of the two slaves of the FI.
2nd Slave
1)
1st Slave
1) Only if plug connector option ”-ASI“ or “-AUX”
ASi LED
Meaning
OFF
•
No AS interface voltage to the module
•
Connection cables not connected or incorrectly connected
green ON
•
Normal operation (AS interface active)
red ON
•
No exchange of data
– Slave address = 0 (slave still in factory setting)
– Slave not in LPS (list of planned slaves)
– Slave with incorrect IO/ID
– Master in STOP mode
– Reset active
Red flashing
(2 Hz)
1)
•
The slave is held at "Reset" during addressing
alternately
flashing red /
green (2 Hz)
1)
•
Peripheral error, AS-i communication controller in update mode
1)
Switch-on frequency per second, example: 2 Hz = LED 2 x per second "On"