Use and Maintenance Manual model “A11V - C ZENITH & A11 V PLUS ZENITH”

ENGLISH

3.3 CHIMNEY FLUE

When installing the chimney flue, the following provi

-

sions must be applied.

• comply with the product standard EN 1856-1;

• 

it must be installed using materials suitable to  

   guarantee resistance to normal mechanical and 

   chemical stress, and have a correct insulation, to 

   avoid the formation of condensate, therefore it    

   must be hermetically insulated;

• 

have a mainly vertical state and   

   not be choked along its length;

• 

be correctly spaced using 

   air cavities and insulated from flammable 

   materials,

• 

the changes in direction must be 

   at most 2 and with an angle not exceeding 45°;

• the chimney flue inside the home must 

   however be insulated and can be inserted in  

   a cavity provided it complies with the relevant 

   piping standards;

• 

the smoke channel should be connected to the 

chimney flue using a “T” joint with an inspectionable 

collection chamber for collection of fuel residue 

and, in particular, for  condensate collection.

It is not possible to connect the appliance to a 

chimney flue shared with other combustion appli

-

ances or in the presence of hood exhausts.

It is forbidden to use direct wall discharge or 

towards closed spaces or any other form of dis-

charge not planned by legislation in force in the 

country of installation (In Italy, only roof discharge is 

permitted)

3.4 CHIMNEY STACK

The standard UNI 10683 states the stack must meet 

the following characteristics:

• 

the smoke outlet section must be at least 

   double the inner section of the chimney;

• 

shaped to prevent 

   water or snow penetration;

• 

be built in such a way that wind 

   cannot affect the smoke outlet 

   (wind-proof cap);

• 

the opening measurement, which is measured 

between the lower coverage protective layer 

   and the lower point of the 

   smoke outlet section into the atmosphere, must be  

   outside the back draught area;

• 

Be built far from antennas or 

   satellite dishes and must never be used as a 

   support.

You are advised to check the safe distances which 

must be complied with in the presence of 

combustible materials and the type of insulating 

material to use (data available directly on the 

chimney flue plate)

3.5 HERMETIC PRODUCT INSTALLATION

In the event of installation of a hermetic product, 

you can execute one of the following types of con-

nection with the piping:

• smoke discharge (1) and recovery of oxidising air 

   directly from outside (2) 

2

1

1

2

2

1

• smoke discharge (1) and oxidising air channelling 

(2) taking advantage of its coaxial discharge 

   to expel the smoke and pick 

   the air; therefore, installation is not necessary 

   of a grate to recirculate the air    

   inside the premises where the 

   the product.

For coaxial installation or air sampling directly from 

the outside, it is recommended not to exceed 

2.5 / 3 linear meters in order to ensure correct 

oxygen supply to combustion.

Содержание A11 C ZENITH

Страница 1: ...EN Installation use and maintenance manual A11 V ZENITH A11 C ZENITH A11 V PLUS ZENITH...

Страница 2: ...appropriate place having carefully consulted it Improper installation maintenance not carried out correctly and improper use of the product relieve the manufacturer of any liability towards people or...

Страница 3: ...ld device keys 14 7 3 Description of handheld device display 14 7 4 Flat battery signalling 15 7 5 Concise icons diagram 15 8 Menu browsing 16 9 First start up instructions 16 9 1 Date and time settin...

Страница 4: ...ing activity and maintenance of safety devices do not remove or bypass this devices 1 3 IMPROPER USE The product must be intended for the use for which it was expressly designed for any other use the...

Страница 5: ...tenance non conforming installation with that specified by the manufacturer refer to the installation and use manual supplied with the appliance further damage caused by wrong intervention by the user...

Страница 6: ...nment making it less comfortable and reducing the overall efficiency of the system Hermetic prod ucts can also be installed in the presence of forced ventilation or in premises which can go into negat...

Страница 7: ...other rooms garage etc and must have a net useful section equal or higher than 80 cm2 pellet burning stoves and thermostoves EN 14785 and 100 cm2 for boilers EN 303 5 The air intake is not necessary...

Страница 8: ...ation In Italy only roof discharge is permitted 3 4 CHIMNEY STACK The standard UNI 10683 states the stack must meet the following characteristics the smoke outlet section must be at least double the i...

Страница 9: ...flammable parts such as wood etc In both cases insert adequate insulation 5 be tween the chimney flue and the attic You are advised to check and comply with the plate data of the chimney flue in parti...

Страница 10: ...act with hot parts and must remain accessible after installation To carry out electrical connection proceed as de scribed below connect the power supply cable on the back of the appliance connect the...

Страница 11: ...nt product operation is not guaranteed In this phase the authorised technician should completely and accurately clean the smoke pipes check the sealing status of all the gaskets remove broken pellet r...

Страница 12: ...utilizzato per la costruzione dell oggetto rappresentato n venire comunicato a terzi o riprodotto La Societ proprietaria tutela i propri diritti a rigore di legge All proprietary rights reserved by N...

Страница 13: ...el is loaded by inserting pellets from the upper part of the product opening the door Ensure the content of the bag of pellets does not fall around the edges of the tank paying particular attention to...

Страница 14: ...wing chapter carefully relating to use of the receiver and the handheld device as well as their related functions INFORMATIVE NOTE frequency bands and transmitted power used by the equipment as report...

Страница 15: ...the appliance see Concise icons diagram 7 4 FLAT BATTERIES SIGNAL If batteries are flat the display presents a symbol which indicates their limit status however maintaining the functions enabled of t...

Страница 16: ...Scroll the items to SETTINGS with the key Access the menu by pressing key Scroll the items to TIME DATE with the key On the TIME DATE menu item key The screen appears to adjust the time and calendar...

Страница 17: ...inhibits manual management of the op tional fan with the exception of the fan setting on OFF In this case the appliance autonomously only manages power to the fireplace Ventilation remains disabled 9...

Страница 18: ...eplace as soon as the temperature in the premises goes under the required setting optimisation of combustion and acoustic comfort During first start up of the product unpleasant odours may occur or sm...

Страница 19: ...AND BY screen use the key repeating the operation multiple times OK OK Edit the value with the keys The logic relating to this type of management is as follows USER the user reserves the right to set...

Страница 20: ...Thermostat with timer function you can program for each day of the week automatic switch on and off of the product with 4 independent time intervals PROGRAM 1 2 3 4 The steps are outlined below to fol...

Страница 21: ...e the switch on phase of the appliance after accurate cleaning was conducted of the hopper pellet con tainer to remove sawdust which over time is creat ed on the base See the chapter Routine mainte na...

Страница 22: ...ELLET and 3 EXTRACTION was set this kind of setting results from the fact combustion is lacking oxygen and the pellets are small in size compared to the average 2cm OK Select the type of screen you wa...

Страница 23: ...at is installed has not yet reached the temperature required the writing T OFF if in the room the ambient temperature is reached 11 6 LANGUAGE Based on the destination country or the user acquir ing t...

Страница 24: ...se simply approach the appliance to re establish communication 12 CHANNEL where planned The products of the range equipped with channel ling are in two types single duct channelling or double duct cha...

Страница 25: ...ne to channel with the help of an optional ambient probe provided on request of Nobis s r l not supplies as standard OK If the flag is enabled for channelling temperature management with the external...

Страница 26: ...ture setting from the handheld device but rather from the external ther mostat Having confirmed setting of the RH channelling confirm with the key and re peat the same sequence of operations for the L...

Страница 27: ...TART PHASE DESCRIPTION Ambient setting in MAN therefore the appliance only works with the power to the fireplace set never going to saving MAN WORK 14 FUNCTIONS CONCISE DIAGRAM Edit the data highlight...

Страница 28: ...or controlling correct combustion For safety purposes while waiting for the technician the appliance is set to saving mode The maximum smoke temperature threshold has been reached the appliance for a...

Страница 29: ...Service ALARM CODE REASON 05 EXTRACTOR ROTATIONS NOT RESPECTED The rotations of the smoke extractor show a loss of efficiency due to obstruction of the fan or a drop in voltage SOLUTION If the proble...

Страница 30: ...blem persists contact the Support Service ALARM CODE REASON 16 PELLET TANK DOOR OPEN During the pellet loading phase of the product the tank door was not closed properly SOLUTION Check the pellet tank...

Страница 31: ...urfaces on the painted metal parts use a cloth soaked in water and soap Use of abrasive detergents or diluents causes damage to the surface of the product 18 1 CLEANING THE FIREPLACE Open the fire doo...

Страница 32: ...t and which could damage the appliance used for cleaning The cleaning operations depend on the quality of the pellets used and the frequency of use of the product It can happen that such operations mu...

Страница 33: ...ct appliance operation PARTS FREQUENCY TIME Ash pan approx time 7 DD Glass 2 3 DD Extraction pipe 1 SE Door seal ash pan 1 SE Tube bundle scraper where present 7 DD Chimney flue 1 SE Combustion chambe...

Страница 34: ...AL RESET THERMAL SWITCH CONTACT DOOR ASH PAN 1 PELLET TANK 2 220V SOCKET WITH ON OFF SWITCH AND FUSE SAFETY VACUUM SWITCH VENTILATION FRONT K J PC CONNECTION technical support only USB CONNECTION tech...

Страница 35: ......

Страница 36: ...N 11 25037 Pontoglio BS www nobisfire it Cod 110 002 0011N_S1 Nobis Srl cannot be held in any way liable for any errors in this manual and considers itself free to change the features of its products...

Отзывы: