Содержание ExATSN1/2

Страница 1: ......

Страница 2: ...pped with interlocking mechanism which must not be operated improperly or with a handle other than the one specified 7 The product shall be grounded reliably or provided with appropriate equipotential protection measures 8 The user needs to provide fuses matched with the currents and voltages of the switch 9 Operating under conditions beyond those specified in relevant standards could affect the f...

Страница 3: ... controller 6 Grounding screw 7 Sight glass of main power switch position 8 Sight glass of spare power switch position 9 Mounting hole 6 Interphase insulating barrier nine barriers for four pole product and six for three pole product 7 Installation manual 8 SU60 functionality manual Mounting screw Spring washer Flat washer Mounting nut II Preparations OFF SWIT MAIN MAIN POWER SPAR SPAR Noark Elect...

Страница 4: ...VZLWFK IURP WKH 2 WR 0DLQ SRVLWLRQ Figures 4 and 5 2 ĺ6SDUH SUHVV WKH VZLWFK EXWWRQ Figure 3 and rotate the handle from the position shown in Figure 4 to the position in Figure 5 7KH KHDULQJ RI FOLFN LQGLFDWHV FRPSOHWLRQ RI WKH VZLWFKLQJ 1RZ WKH VZLWFK SRVLWLRQ VLJKW JODVV VKRZV 21 RI WKH PDLQ RU VSDUH Conformance with the above means the self test is acceptable In case of any abnormalities do not...

Страница 5: ...WLQJ VFUHZĺIODW ZDVKHUĺIL HG VROHSODWHĺIODW ZDVKHUĺVSULQJ ZDVKHUĺQXW 3 2 2 Installation instructions for controller Installation instructions for controller 1 Before installation remove the four clips Figure 1 and insert the controller into the perforated panel 2 During installation install the four clips from the back of the panel to fix the controller to the panel Installation and fixing of four...

Страница 6: ...IV Appearance and mounting dimensions 4 1 Appearance and mounting dimensions of equipment Size Model Note please contact us if you need the physical dimensions of ExATSN5 ...

Страница 7: ...4 2 Appearance and opening size of controller 4 2 1 Physical size of controller Installation with clips 4 2 2 Opening size of controller ...

Страница 8: ... provided with short circuit protective device meeting isolation requirements The secondary circuit is located on the right side of the equipment and its wiring is schematically shown in pictures right Main position feedback signal Auxiliary group two groups Spare position feedback signal Auxiliary group two groups Voltage AC230V Current 10A Terminal screw M3 Torque 0 5 Nm Terminal screw M6 Torque...

Страница 9: ...re power Main power Spare power Output power Output power NoteĹ NoteĹ NoteĹ NoteĹ NoteĻ Noteĺ Input of fire blocking signal Output of generator signal Input of auxiliary power supply kA intermediate relay NoteĻ Noteĺ Noteĺ Input of fire blocking signal Output of generator signal Input of auxiliary power supply Communication port kA intermediate relay Communication port ...

Страница 10: ...utput terminals is AC270V DC30V At the maximum voltage the output current must not exceed 1 A 5 3 Connection between equipment and its controller Connection instructions 1 The connection between equipment and its controller is of plug in type Take out wires from the accessory bag and securely connect them to the screws on both sides of a terminal block according to the terminal number 2 Before pul...

Страница 11: ...he relative humidity shall not exceed 50 at ambient air temperature of 40 it can be higher than 50 at lower temperatures In the wettest month the monthly average relative humidity is 90 as a maximum and 20 as a minimum Special measures are required for occasional condensation due to temperature variations Pollution degree 3 Installation category III 6 2 Usage class 6 3 Standards ...

Страница 12: ...at the panel front Auxiliary device for monitoring and indication Fire linkage function Alarm feedback signal Position feedback signal Standard Optional Unavailable Noteķ The front must be provided with short circuit protective device meeting isolation requirements Housing current Rated current Rated frequency Rated insulation voltage Rated impulse withstand voltage Rated voltage Rated short time ...

Страница 13: ...nected with the transfer switch are loose at the interface or come off The manual auto mode is not set correctly 1 Both power supplies fail 2 The wires show poor interface contact or come off 1 The fire signal wire is improperly connected 2 The switch is set at manual position Troubleshooting 1 Push the controller s power button on transfer switch to switch to I position 2 Reconnect the wire termi...

Страница 14: ...de or application of new technologies or for correction of misprint and incorrect information Copyright Noark Printed with eco friendly paper Noark Electric Europe s r o 54 6 Add Sezemická 2757 2 193 00 Praha 9 Czech Republic Registered at Municipal Court in Prague Section C Insert 181277 Tel 420 226 203 120 Email kristyna senfeldova noark electric com www noark electric cz ...