1.  Ensure correct sensor model was chosen for Input Volt-

age of application.

2.  Mount the sensor to a DIN rail using integrated mounting 

clip on backside of transducer or secure using the tabs 
in each corner.

3.   Connect monitored voltage  to term. (2) & (1) and out-

put wiring using 22-16 AWG copper wires insulated to 
75/90°. Lift the orange clip on the terminal, insert wire 
and allow it to clamp on the stripped end of the wire.

 

Refer to “Output Wiring” section for voltage and imped-
ance recommendations. 

IMPORTANT: Monitored voltage (V1/V2) polarity sensi-

tive for output polarity. 

4. Connect 24VAC or DC power supply fused to 5 amp to 

term. 3-4. Use twisted pair for CE compliance.

5. Connect output to the load using terminal 6 for the output 

signal, and terminal 5 to common.

6. Energize primary circuit and sensor power.

VTD   1  -  010  - 24U  -   BD - OS

OUTPUT:

005 -  +/-5VDC
010 -  +/-10VDC

VOLTAGE INPUT RANGE:

0  - 15VDC
1 - 25VDC
2 - 50VDC
3 - 150VDC
4 - 300VDC
5 - 600 VDC

SENSOR TYPE:

VTD -   DC Voltage Transducers

Model Number Key

Specifi cations

Quick “How To” Guide

OUTPUT TYPE:

BD - Bidirectional

POWER SUPPLY:

24U - 24 VAC/DC

3511 Charter Park Drive, San Jose, CA  95136
800-959-4014 or 408-871-7510 Phone
408-871-7515 FAX
[email protected],  www.nktechnologies.com

VTD-BD Instruction Sheet Rev 1 01/17 P/N 292180021

Know Your Power

Other NK Technologies Products Include:

AC & DC Current Transducers
AC & DC Current Operated Switches
1

φ

 & 3

φ 

Power Transducers

Current & Potential Transformers (CTs & PTs)

 External Power Supply 

24VAC/DC (22-26V)  

Power Consumption 

<2VA Use class 2 power supply 

Voltage Measurement 

0-15, 25, 50, 150, 300 or 600 VDC

Monitored Line Impedance  >160K ohms
Output 

  +/-5 

VDC

   +/-10 

VDC

Response Time 

 

250 ms (10% to 90% value)

Accuracy  

 

< 1% Full Scale

Output Impedance   

>10K Ohms for stated accuracy

Isolation Voltage 

 

2500 Volts

Frequency Range   

DC only 

Operating Temp. 

 

-20°C to 50°C 

 

   (surrounding 

sensor)

Enclosure  UL94 

V0 

Rated

Environmental 

 

-4 to 122 ° F

 

 

 

(-20 to 50° C),0–95% RH

   Pollution 

Degree 

2

   Altitude 

to 

2000 

meters

Listings   

 

Designed for UL/cUL, CE 

 

Warning! Risk of danger

Safe operation can only be guaranteed if the 
transducer is used for the purpose for which is 
was designed and within the limits of the techni-
cal specifi cations. When this symbol is used, it 
means you must consult all documentation to 
understand the nature of potential hazards and 
the action required to avoid them.

Warning! Risk of electrical shock

When operating the transducer certain parts may 
carry hazardous live voltage (e.g. primary con-
ductors, power supply). The transducer should 
not be put into operation if the installation is not 
complete.

For products intended for the EU market, the following is ap-
plicable to the CE compliance of the product:

The VTD-BD series are designed to comply with EN 61010-1 
CAT III 600V max measurement category. Use 24 V input power 
and fuse at 5 amps. Power source overvoltage category I as 
defi ned per EN 61010-1

VTD-BD SERIES

Bidirectional DC Voltage Transducers

 +/-5 or +/-10VDC Output

INSTRUCTIONS