NK TECHNOLOGIES AS1 - DODC - FL Скачать руководство пользователя страница 1

INSTRUCTIONS

1.  Run the wire to be monitored through 

aperture.

2.  Mount the sensor.

3.  Connect output wiring.

A.  Use up to 14 AWG copper wires.  
B.  Ensure load matches the output shown on 

the sensor label.

4. Adjust Setpoint

A.  Use the potentiometer to adjust the set-

point.

AS1 DODC SERIES

AC Current Operated Switch

With Dual Output

AS1  -  DODC  -  FL

CASE STYLE:

FL - Fixed Core, Top Terminals

OUTPUT 

(Solid State Switch)

:

DODC - Dual Normally Open, 1.0A @ 30VDC 

SENSOR TYPE:

AS1 - AC current operated switch with single range
0.75A -- 20A
AS2 - AC current operated switch with single range
20A -- 50A

Model Number Key

Specifi cations

Power Required 

None - self powered

Output Switch 

Isolated Solid State Switch

Switch Rating 

DODC - N.O. 1A @ 30VDC 

Off State Leakage 

<10 Microamps

Response Time 

100 mS

Hysteresis 

< 8% of Setpoint

Set Point Ranges 

A Contact: Adjustable 0.75A - 20A

 

B Contact: Adjustable 0.75A - 20A

Start-up Delay 

2.0 Seconds (fi xed)

Setpoint Adjust 

4 Turn potentiometer

Isolation Voltage 

Designed to meet UL508 require-
ments to 1,270 VAC

 

Tested to 5,000 VAC 

Frequency Range 

6-100Hz  

Sensing Apeture 

-FL  0.75” (19mm)

Environmental 

-4 to122Deg F (-20 to 50 Deg C) 

 

0-95% RH, Non Condensing

Ranges & Maximum Amps

Quick “How To” Guide

AS1-DODC-FL Inst. Rev 2  12/14  P/N 39-360-0001

3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
[email protected],  www.nktechnologies.com

Know Your Power

Other NK Technologies Products Include:

AC & DC Current Transducers
AC & DC Current Operated Switches
1

φ

 & 3

φ

Power Transducers

Current & Potential Transformers (CTs&PTs)

TYPE

RANGE

MAXIMUM INPUT AMPS

FIXED CORE

0.75- 20 A

CONTINUOUS

6 SEC.

1 SEC.

50A

200A

400A

FIXED CORE

20-50 A

50A

200A

400A