INSTRUCTIONS
1. Run all current carrying conductors through
detector window
A. Use an auxiliary CT if conductors do not fi t. Consult
Factory for CT selection.
2. Mount the detector to a surface if needed.
3. Connect output & power wiring.
A. Use 22 to 14 AWG copper wires.
B. Make sure load matches the output shown on the
detectors’ label.
•
Detectors labeled “xxAC” will only detector
AC.
•
Detectors labeled “xxDC” will only detector
DC.
C. Make sure power supply matches the power input
shown on the label.
4. Test
A. Pressing the “TEST” button tests the detectors
internal circuits. CAUTION: The output and any
connected loads will detector!
AG1-NCAC-120 -FS - 005
Model Number Key
Specifi cations
Quick “How To” Guide
Power Supply Notes
AG 1, 2 & 3 SERIES
Ground Fault Detectors
Solid State Auto-Reset
AG-auto-reset Inst. Rev 5, 4/16 P/N 49-010-0002
Output Type
NCAC
Normally Closed 1A @ 240 VAC
NOAC Normally Open 1A @ 240 VAC
NCDC
Normally Closed 0.15A @ 30 VDC
NODC Normally Open 0.15A @ 30 VDC
Power Supply
24U 24
VAC/DC
120 120
VAC
240 200-240
VAC
Setpoint Range
1 5-100mA,
Adjustable
2 80-950mA,
Adjustable
3 Tri-Set, 5, 10 & 30 mA, Jumper Select
AG Series Ground Fault Detector
Setpoint Range
AG1 Series: 5-100mA Field Adjustable
AG2 Series: 80-950mA Field Adjustable
AG3
Series:
Tri-Set, 5, 10 & 30 mA, Jumper
Select
Voltage Range
Up to 1,500 VAC (Monitored Circuit)
Frequency Range
50-400Hz (Monitored Circuit)
Output Options
(See Product Label)
Solid State AC Detector
1A @ 240 VAC (2A for 10 Min.)
Solid State DC Detector
0.15A 30 VDC (500mA
momentary)
Response Time
150 mS @ 5% above setpoint.
100 mS @ 50% above setpoint.
Power Supply
120 VAC (50-400 Hz) (66-132 volts)
2.5
VA
consumption
240 VAC (50-400 Hz) (200-240 volts)
2.9
VA
consumption
24VAC or VDC (19-28 volts)
2.5VA
consumption
Green LED=Power supply energized
Dimensions
2.5”H x 2.8”W x 1.5”D, (64x71x38mm),
aperture 0.75” (19mm) dia. (See Diagram)
Case
UL 94V-O Flammability Rated
Environmental
-4 to122° F (-20 to 50 °C),
0-95% RH, Non Condensing
Listings
UL 1053, Class 1 Recognized, CE Certifi ed
(Not all option combinations are recognized.
See product label)
System Grounding
3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
[email protected], www.nktechnologies.com
Know Your Power
Other NK Technologies Products Include:
AC & DC Current Transducers
AC & DC Current Operated Detectors
1
φ
& 3
φ
Power Transducers
Current & Potential Transformers (CTs&PTs)
All low-current Ground-Fault Detectors are sensitive devices
that require reasonable care in system design to avoid false
trips caused by high electrical noise levels. Keep in mind
that the best way to reduce noise in a system is to suppress
it at its source.
1. Keep the detector power isolated from noisy circuits.
2. Do not power the detector with the same circuit which pow-
ers contactors or other high current, inductive loads.
Good design practice and code require that all AC power
systems be grounded. AG Series detectors are designed to
work on grounded AC power systems. They may not operate
properly on ungrounded systems.
Setpoint
005 to 950 Factory Adjusted
Setpoint in mA (specify
when ordering)
TR3
Tri-Set, 5, 10 & 30 mA,
Jumper Select
Options
FS Normally
Energized
NF Normally
De-energized