NK TECHNOLOGIES AG3 Series Скачать руководство пользователя страница 1

INSTRUCTIONS

1.  Run all current carrying conductors through 

detector window

A.  Use an auxiliary CT if conductors do not fi t.  Consult 

Factory for CT selection.

2.  Mount the detector to a surface if needed.

3.  Connect output & power wiring.

A.  Use 22 to 14 AWG copper wires.  
B.  Make sure load matches the output shown on the 

detectors’ label.  

• 

Detectors labeled “xxAC” will only detector 
AC.   

• 

Detectors labeled “xxDC” will only detector 
DC.

C.  Make sure power supply matches the power input 

shown on the label.

4. Test 

A.  Pressing the “TEST” button tests the detectors 

internal circuits.  CAUTION: The output and any 
connected loads will detector!

AG1-NCAC-120 -FS - 005

Model Number Key

Specifi cations

Quick “How To” Guide

Power Supply Notes

AG 1, 2 & 3 SERIES

Ground Fault Detectors 

Solid State Auto-Reset

AG-auto-reset Inst. Rev 5,  4/16 P/N 49-010-0002

Output Type 

NCAC 

Normally Closed 1A @ 240 VAC

NOAC  Normally Open 1A @ 240 VAC
NCDC 

Normally Closed 0.15A @ 30 VDC

NODC  Normally Open 0.15A @ 30 VDC

Power Supply

24U 24 

VAC/DC

120 120 

VAC

240 200-240 

VAC

Setpoint Range

1 5-100mA, 

Adjustable 

2 80-950mA, 

Adjustable 

3  Tri-Set, 5, 10 & 30 mA, Jumper Select

AG Series Ground Fault Detector

Setpoint Range 

AG1 Series: 5-100mA Field Adjustable

 

AG2 Series: 80-950mA Field Adjustable

 AG3 

Series: 

 Tri-Set, 5, 10 & 30 mA, Jumper 

Select

Voltage Range 

Up to 1,500 VAC (Monitored Circuit)

Frequency Range 

50-400Hz (Monitored Circuit)

Output Options

 

(See  Product Label)

Solid State AC Detector 

1A @ 240 VAC (2A for 10 Min.)

Solid State DC Detector 

0.15A  30 VDC (500mA        

 momentary)

Response Time 

150 mS @ 5% above setpoint.  

 

100 mS @ 50% above setpoint.

Power Supply 

120 VAC (50-400 Hz) (66-132 volts) 

 2.5 

VA 

consumption 

 

240 VAC (50-400 Hz) (200-240 volts)

 2.9 

VA 

consumption

 

24VAC or VDC  (19-28 volts)

 2.5VA 

consumption

 

Green LED=Power supply energized

Dimensions 

2.5”H x 2.8”W x 1.5”D, (64x71x38mm), 
aperture 0.75” (19mm) dia. (See Diagram)

Case 

UL 94V-O Flammability Rated

Environmental 

-4 to122° F (-20 to 50 °C), 

 

0-95% RH, Non Condensing

Listings 

UL 1053, Class 1 Recognized, CE Certifi ed 
(Not all option combinations are recognized.  
See product label)

System Grounding

3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
[email protected],  www.nktechnologies.com

Know Your Power

Other NK Technologies Products Include:

AC & DC Current Transducers
AC & DC Current Operated Detectors
1

φ

 & 3

φ

Power Transducers

Current & Potential Transformers (CTs&PTs)

All low-current Ground-Fault Detectors are sensitive devices 
that require reasonable care in system design to  avoid false 
trips caused by high electrical noise levels.  Keep in mind 
that the best way to reduce noise in a system is to suppress 
it at its source. 

1.  Keep the detector power isolated from noisy  circuits.
2.     Do not power  the detector with the same circuit which pow-

ers contactors or other high current, inductive loads.

Good design practice and code  require that all AC power 
systems be grounded.  AG  Series detectors are designed to 
work on grounded AC power systems.  They may not operate 
properly on ungrounded systems. 

Setpoint

005 to 950   Factory Adjusted 
 

Setpoint in mA (specify 
when ordering)

TR3 

Tri-Set, 5, 10 & 30 mA, 
Jumper Select

Options

FS Normally 

Energized

NF Normally 

De-energized