NK TECHNOLOGIES AG1 Series Скачать руководство пользователя страница 1

INSTRUCTIONS

1. Run all current carrying conductors

through sensor window

A. Use an auxiliary CT if conductors do not fit.  Con-

sult Factory for CT selection.

2. Mount the sensor to a surface if needed.

3. Connect output & power wiring.

A. Use up to 14 AWG copper wires.
B. Make sure load matches the output shown on the

sensors’ label.

Sensors labeled “xxAC” will only switch AC.

Sensors labeled “xxDC” will only switch DC.

C. Make sure power supply matches the power input

shown on the label.

4. Test

A. Pressing the “TEST” button tests the sensors inter-

nal circuits.  CAUTION: The output and any con-
nected loads will switch!

AG1-NCAC-120 -FS - 005

Model Number Key

Specifications

Quick “How To” Guide

Power Supply Notes

AG 1, 2 & 3 SERIES

Ground Fault Sensors

Auto-Reset

Output Type

NCAC

Normally Closed 1A @ 240 VAC

NOAC

Normally Open 1A @ 240 VAC

NCDC

Normally Closed 0.15A @ 30 VDC

NODC

Normally Open 0.15A @ 30 VDC

NCR

Normally Closed, 0.5A @ 120 VAC, 0.25A
@ 240 VAC, 2A @ 30 VDC

NOR

Normally Open, 0.5A @ 120 VAC, 0.25A @
240 VAC, 2A @ 30 VDC

Power Supply

24U 24 VAC/DC
1 2 0 120 VAC
2 4 0 132-264 VA C

Setpoint Range

1

5-100mA, Adjustable

2

80-950mA, Adjustable

3

Tri-Set, 5, 10 & 30 mA, Jumper Select

AG Series Ground Fault Sensor

Setpoint Range

AG1 Series: 5-100mA Field Adjustable
AG2 Series: 80-950mA Field Adjustable
AG3 Series: 

 Tri-Set, 5, 10 & 30 mA, Jumper

Select

Voltage Range

Up to 1,500 VAC (Monitored Circuit)

Frequency Range

50-400Hz (Monitored Circuit)

Output Options

(See  Product Label)

Solid State AC Switch

1A @ 240 VAC (2A for 10 Min)

Solid State DC Switch

0.15A    30  VDC (500mA
momentary)

Relay Output

0.5A @ 120 VAC, 0.25A @ 240

VAC, 2A @ 30 VDC

Response Time

150 mS @ 5% above setpoint.
100 mS @ 50% above setpoint.

Power Supply

Operates from 55-110% of nominal voltage

Nominal Voltages

120, 240 VAC (50-400 Hz)
Green LED=Power

Optional Power

24VAC or 24 VDC  Op/- 20%

Power Consumption

2.5 Watts

Dimensions

2.5"H x 2.8"W x 1.5"D, (64x71x38mm),
aperture 0.75" (19mm) dia. (See Diagram)

Case

UL 94V-O Flammability Rated

Environmental

5 to158 DegF (-15 to 70 DegC), 0-95% RH,
Non Condensing

Listings

UL 1053, Class 1 Recognized, CE Certified
(Not all option combinations are recognized.
See product label)

System Grounding

Know Your Power

Other NK Technologies Products Include:

AC & DC Current Transducers
AC & DC Current Operated Switches
1

φ

 & 3

φ

Power Transducers

Current & Potential Transformers (CTs&PTs)

All low-current Ground-Fault Sensors are sensitive devices
that require reasonable care in system design to  avoid false
trips caused by high electrical noise levels.  Keep in mind that
the best way to reduce noise in a system is to suppress it at its
source.

1. Keep the sensor power isolated from noisy  circuits.
2. Do not power  the sensor with the same circuit that

switches contactors or other high current, inductive loads.

Good design practice and code  require that all AC power
systems be grounded.  AG  Series sensors are designed to
work on grounded AC power systems.  They may not operate
properly on ungrounded systems.

Setpoint

005 to 950 Factory Adjusted

Setpoint in mA (specify
when ordering)

TR3

Tri-Set, 5, 10 & 30 mA,
Jumper Select

Options

FS

Normally Energized

NF

Normally De-energized

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]