30
31
6.7. Faults reference code
Fault event
Fault code
Icon
Bus start failure
01
X
Bus over
02
X
Bus under
03
X
Bus unbalance
04
X
Inverter soft start fail
11
X
High inverter voltage
12
X
Low inverter voltage
13
X
Inverter output short circuited
14
SHORT
Negative power fault
1A
X
Inverter over current
60
X
Inverter current detection error
6D
X
Transformer over temperature
77
Battery SCR short circuited
21
X
Inverter relay short circuited
24
X
Charger short circuited
2a
X
CAN communication fault
31
X
Parallel output current unbalance
36
X
Over temperature
41
X
CPU communication failure
42
X
Overload
43
OVER LOAD
Battery turn-on failure
6a
X
PFC current failure in battery mode
6b
X
Bus voltage changes too fast
6c
X
SPS 12V abnormal
6e
X
6.8. Warning indicator
Warning
Icon (flashing)
Warning
code
Alarm
Low Battery
LOW BATT.
08
Sounding every
second
Overload
OVER LOAD
09
Sounding every 2
seconds
Battery is not connected
BATT. FAULT
01
Sounding every
second
Over Charge
07
Sounding every
second
EPO enable
EP
0B
Sounding every
second
Fan failure
0A
Sounding every
second
Over temperature
0D
Beeping every second
Charger failure
0E
Sounding every
second
I/P fuse broken
10
Sounding every
second
Locked in bypass after
overload 3 times in 30min
33
Sounding every
second
Bypass unstable
3D
Beeping every second
Boot loader is missing
3E
Beeping every second
Cover of maintain switch
is open
3A
Beeping every second
Line situations are differ
-
ent in parallel system
21
Beeping every second
Bypass situations are dif
-
ferent in parallel system
22
Beeping every second
Over-temperature on
transformer
42
Beeping every second
Содержание Balder 10000