Parameter Setting
OCM F - rev. 05 / 06.04.2018
page 55
>Mounting
height<
Only visible, if sensor type no. 1 is selected.
This value is set to 0 mm as KDA combi sensors as default. The value
needs to be adjusted in case of elevated (block or similar) or lowered
installation. Then the altered mounting height is specified (positive or
negative value).
>Value<
Enter a fixed value for the level here. Only visible, if sensor type no. 2
is selected.
Default setting: 0.1 m (3.9 in)
>Measurement
range<
Select between measurement ranges 4…20 mA or 0…20 mA.
Only visible, if sensor type no. 3 is selected.
>Value at 0 mA<
Enter a level value for 0 mA here.
Only visible if 0…20 mA has been selected as measurement range for
sensor type no. 3.
Default setting: 0 m (0.0 in)
>Value at 4 mA<
Enter a level value for 4 mA here.
Only visible, if sensor type no. 3 or 4 is selected.
Default setting: 0 m (0.0 in)
>Value at
20 mA<
Enter a level value for 20 mA here.
Only visible, if sensor type no. 3 or 4 is selected.
Default setting: 4 m (13.1 ft)
>Offset<
This entry will move the zero point of the external sensor.
Only visible, if sensor type no. 3 or 4 is selected.
Default setting: 0 m (0.0 in)
>Damping<
This value is to damp a fluctuating signal of an external level meas-
urement.
Only visible, if sensor type no. 3 or 4 is selected.
This value is set to 0 s as default and can be set to up to 10 s.
23.2.1
Information on how to connect i-Series sensors
Observe correct connection of sensors
The i-Series sensors feature pre-programmed measurement ranges. Please refer to the
according instruction manual. The sensor can be operated even without HART modem.
Setting the parameter “Value at 20 mA” requires entering the measurement span of the
sensor. Depending on the installation height of the sensor a negative offset value may be
additionally necessary.
i-3
i-6
i-10
i-15
4 mA (empty) – 0 %
span distance to sensor face in m
3.0
6.0
10.0
15.0
20 mA (full) – 100 %
span distance to sensor face in m
0.125
0.300
0.300
0.500
Measurement span (value at 20 mA)
2.875
5.7
9.7
14.5
Table 6
i-Series sensors measurement range
Содержание OCM F
Страница 105: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 105 Approvals and Certificates...
Страница 106: ...Instruction Manual OCM F page 106 OCM F rev 05 06 04 2018...
Страница 107: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 107...
Страница 108: ...Instruction Manual OCM F page 108 OCM F rev 05 06 04 2018...
Страница 109: ...Approvals and Certificates OCM F rev 05 06 04 2018 page 109...
Страница 110: ...Instruction Manual OCM F page 110 OCM F rev 05 06 04 2018...