Instruction manual
NivuSonic Clamp on
®
8.6
Signal Input/Output Menu (I/O)
This menu includes several submenus which both serve to assess and to check
sensors as well as to control signal inputs and outputs. It allows to indicate vari-
ous values (current values of inputs and outputs, relay conditions, echo profiles,
individual velocities etc.), however does not enable to influence signals or condi-
tions (offset, adjustment, simulation or similar). The menu therefore primarily
serves in order to assess the parameter settings and for error diagnosis.
Fig. 8-59
I/O submenu
The menu basically allows to indicate any input and output theoretically possi-
ble even if it might not be connected or available.
8.6.1 I/O Menu „Analog outputs”
Fig. 8-60
Screen analog values
This menu indicates the calculated values which have to be sent to the analog
converter as mA signals.
The actual currents fed to the output clamps will not be indicated. The only
signal visible is the signal the analog output converter receives for output.
This menu cannot be used to detect or to indicate faulty wiring.
NivuSonic CO - Rev. 00 as of 08.12.2010
Page 77
Содержание NivuSonic Clamp On
Страница 22: ...Instruction manual NivuSonic Clamp on Fig 6 2 Clamp wiring NivuSonic CO wall mount enclosure Page 22...
Страница 30: ...Instruction manual NivuSonic Clamp on Fig 6 16 AC model power supply Fig 6 17 DC model power supply Page 30...
Страница 109: ...18 Declaration of Conformity...
Страница 110: ......