24.1 Overvoltage Protection for Power Supply
NIVUS recommends type EnerPro 220Tr surge arrestors (for a 100-240 V AC power system)
and EnerPro 24Tr (for 24 V DC power supply) for the mains supply.
Observe the connection direction
Observe the non-reversed connection (p-side to transmitter) as well as a correct, straight
wiring supply. Ground (earth) must lead to the unprotected side.
The overvoltage protection devices are ineffective if wired incorrectly.
1) Low impulse earthing resistance required
Fig. 24-1
Overvoltage protection for power supply AC
1) Low impulse earthing resistance required
Do not reverse protected (p) and unprotected sides of overvoltage protection
Fig. 24-2
Overvoltage protection for power supply DC