9.2.
Advanced Settings Display Parameters
Additional parameters, including those used to set up Analog Output Signals are found
at this display. Access this display by pressing the Soft Key next to the
Advanced
Settings
prompt at the Modify Settings Display.
9.2.1.
Max Range
(
11.0
)
Max Range establishes an optional measurement blanking-zone near the bottom of
the tank. Its location is referenced from the top of the tank.
When the Tank Depth parameter is changed, Max Range is automatically set to
110% of the Tank Depth value.
The range for Max Range is: 1.0 to 35.2 ft
9.2.2.
Measure
(
Level
)
Measure determines whether the calculated measurement is the depth of the
material (
LEVEL
) or the distance from the top of the tank to the material (
RANGE
).
The options for Measure are: LEVEL and RANGE
9.2.3.
Wiper Timing
(
240
)
Wiper Timing establishes the time (minutes) between wiper cycles. The sensor
wiper will also operate automatically on detection of signal loss regardless of the
selected Wiper Timing setting. This reduces the need to establish a short wiper
timing sequence and prolongs the life of the wiper mechanism.
The range for Wiper Timing is: 0 [OFF] to 240 minutes
9.2.4.
Gain Band
(
20
)
Gain Band establishes the amount that Current Gain (with Auto Gain ON) can vary
once the initial gain level (GB Midpoint)
has been established. At the default value,
Current Gain can increase or decrease by 20 around the GB Midpoint.
The range for Gain Band is: 5 to 30
9.2.5.
Gain Increment
(
0.1
)
Gain Increment determines the rate of change in gain as Auto Gain operates to
change the Current Gain level over time.
The range for Gain Increment is: 0.1 to 5.0
9.2.6.
Save GB Midpoint (MP)
(OFF)
When turned ON, the Save Gain Band Midpoint option allows the user to manually
set the gain midpoint
The options for Save GB MP are: ON and OFF
Содержание Echo Smart Series
Страница 2: ......
Страница 33: ... Page 24 Figure 6 1 EchoSmart Sensor Mounting Arrangements ...
Страница 37: ... Page 28 Figure 6 4 Controller Installation Drawing ...
Страница 38: ... Page 29 Figure 6 5 EchoSmart Power Supply Unit Installation Drawing ...
Страница 73: ... Page 64 Figure 13 1 Installation Recommendations and Field Measurement for Filter Applications ...