FIRST Interface causes the instrument to respond to a signal that is nearest to the
sensor (typically lighter density material). LAST Interface causes the instrument to
respond to a signal that is furthest from the sensor when multiple interfaces are
present.
FIRST is the typical selection for wastewater and water treatment clarifiers,
thickeners, sedimentation basins and similar processes.
Select LAST algorithm for filter applications to prevent the adverse effect of
suspended solids and air-bubbles in the filter water column during backwash.
The options for Interface are: FIRST or LAST
9.1.10.
Dampening
(
130
)
Dampening establishes the number of updates that are averaged to determine the
Current Measurement. This parameter is used to remove the effects of random
fluctuations caused by settling or disturbed material and prevents sudden changes
in the measurement resulting from the action of rakes and skimmers.
The range for Dampening is: 5 to 255
9.1.11.
Settling Zone
(
ON
)
When Settling Zone is
ON
the instrument ignores signal originating to the left of
LG Min. This enables the sensor to disregard suspended solids, air/gas bubbles and
similar sources of disturbance in the supernatant.
The options for Settling Zone are: ON and OFF
9.1.12.
Tank Display
(
ON
)
Tank Display allows the user to select a tank diagram for the Tank View Display.
There are five common tank designs from which to choose. (See Section 4.3.3 and
Figure 4.7)
The options for Tank Display are: ON and OFF
9.1.13.
Trend Display
(
ON
)
Trend Display allows the user to activate the Historical Trend Display. (See
Section 4.3.4 and Figure 4.8)
The options for Trend Display are: ON and OFF
9.1.14.
Display Contrast
(
55
)
Display Contrast allows the user to adjust the LCD Contrast for optimal visibility.
The range for Display Contrast is: 0 to 255
Содержание Echo Smart Series
Страница 2: ......
Страница 33: ... Page 24 Figure 6 1 EchoSmart Sensor Mounting Arrangements ...
Страница 37: ... Page 28 Figure 6 4 Controller Installation Drawing ...
Страница 38: ... Page 29 Figure 6 5 EchoSmart Power Supply Unit Installation Drawing ...
Страница 73: ... Page 64 Figure 13 1 Installation Recommendations and Field Measurement for Filter Applications ...