background image

DW1401989  Rev.K2 

Dec 18, 2019 

Instruction  Manual

           

   

                   

 

EVA-DIP-SCI  Dual  Input  Module

                                               

 

Before Installation 

Please read these instructions carefully and keep for future reference.   

The information in this document is subject to change without notice. For 

updates please refer to our website. 

 

 

 

 

 

 

 

Note

  : 

Follow the requirements for the installation of the product in 

accordance with the Specifications. Otherwise it may cause malfunction.

 

Note 

: 

Do  not  install  the  product  in  any  location  where  oil,  dust,  iron 

powder, chemicals, or hydrogen sulphide may occur or affect the product. It 

may cause malfunction.

   

 

This package contains the following items: 

Main  unit 

……………………………………………………………………

Outer  cover  EVA 

……………………………………………………………

Instruction  Manual

  …………………………………………………………

Tapping  screw 

………………………………………………………………

Pan  head  screw   

……………………………………………………………

EOL  register  (RE-10k) 

…………………………………………………

  2

 

 

General Description 

EVA-DIP-SCI Dual Input Module with Short Circuit Isolator is intended 

for  use  in  addressable  two  wire  systems.  The  module  monitors  and 

transmits  the  status  (normal, open,  short, or  active) of  devices equipped 

with NC/NO dry contacts to a control panel.    The initiating device circuit 

(IDC) can be wired on Class A

 

or Class B.   

Note: Any conventional detector cannot be connected with the module. 

 

 

 

 

 

General Operation 

Normal  standby  condition:  The  module  receives  polling  from  the  control 

panel at the regular interval.

 

Polling LED (green) flashes. 

Active  condition:  When  an  external  input  is  activated,  Input  LED  (red) 

illuminates, and the module communicates to the control panel the active 

status. 

Trouble  condition:  If an overcurrent occurs  because  SLC  (Signaling  Line 

Circuit)  is  shorted,  SCI  LED  (yellow)  illuminates,  and  the  module 

communicates  to  the  control  panel  the  short  status.  The  module  also 

communicates to the control panel the open/short status of IDC, depending 

on the Subtype Setting described below.

 

 

SCI (Short Circuit Isolator) Function 

The module has a built-in short circuit isolator. SCI circuit prevents entire 

loop failure in the event of a short between L+ and L- on the loop. If a short 

is  detected  between L+  and L-,  the yellow LED  indicator  is  illuminated. 

The line between Lin- and Lout- is disconnected automatically to isolate 

the short circuit, and short circuit status is communicated to the control 

panel. Upon removal of the short condition, the module will automatically 

connect  between Lin-  and Lout- to  restore  the entire  loop to  the normal 

standby status.   

 

 

 

 

 

 

Figure 1 

 

 

 

 

 

 

 

 

 

Figure 2 

NITTAN COMPANY, LIMITED

 

1-54-5 SASAZUKA, SHIBUYA-KU, TOKYO 151-8535, JAPAN 

 

http://www.nittan.com

 

Polling LED (GREEN)

Input LED (RED)

SCI LED (YELLOW)

Address Setting Port

mm(in) 

Make sure to turn the power off before commencing any wiring work. 

Otherwise it may cause electric shock or damage to equipment.

CAUTION

!

Do not use the products outside the rated power supply voltage range 
specified in the Specifications. It may cause a fire or damage to 
equipment.

CAUTION

!

Do not disassemble, repair, or modify the products. It may cause a fire 
or electric shock.

CAUTION

!

Содержание EVA-DIP-SCI

Страница 1: ...d Input LED red illuminates and the module communicates to the control panel the active status Trouble condition If an overcurrent occurs because SLC Signaling Line Circuit is shorted SCI LED yellow illuminates and the module communicates to the control panel the short status The module also communicates to the control panel the open short status of IDC depending on the Subtype Setting described b...

Страница 2: ...ype depending on the wiring configuration as below The subtype is to be set through the Configurator for the control panel Sub Type Input Method Open circuit Detection Short circuit Detection Class Interrupt 1 Normally Open Yes No Class B Disabled 2 Enabled 3 Class A Disabled 4 Enabled 5 Normally Close No Yes Class B Disabled 6 Enabled 7 Normally Open Yes Yes Class B Disabled 8 Enabled 9 Class A D...

Страница 3: ...rcuit detection is available It is a status that dry contact switches connected between A B and A B in EVA DIP SCI are OFF Two external inputs can be connected to the input line Resistor of 2 2k ohms RE 2 2k is an option and not included in this product B B A A Lin Lin Lout Lout Typical wiring for N O contacts only 2 2kΩ 2 2kΩ Loop TO NEXT DEVICE Loop FROM PANEL OR PREVIOUS DEVICE Figure 7 Normall...

Страница 4: ...nel detects the short circuit 6 Short between terminal Lin Lout and Lin Lout and the SCI LED yellow illuminates The short circuit isolator isolates the devices connected after the short circuited area which makes these devices have no response Upon removal of the short condition the area is automatically connected to go back to the normal standby status and the SCI LED yellow turns off FOR WARRANT...

Страница 5: ...s had been paid And the warranty period is three 3 years from the shipment from Nittan s factory 1 3 Notwithstanding anything to the contrary in this warranty terms Nittan shall not be liable to the customer by reason of any representation or implied warranty condition or other term or any duty at common law or under the express terms of this warranty terms for any consequential loss or damage whe...

Отзывы: