background image

EV-2I1O (-EU) Installation instructions   

 

IIS-EV-2I1O (-EU) Issue 4 04/03/2019 

 

RoHS Compliance Statement  

This product complies with the European Union RoHS (Restriction of Hazardous Substances) 
directive 2011/65/EU which restricts the use of the following six hazardous materials in the 
manufacture of electronic and electrical equipment. 
• Lead (Pb) 
• Hexavalent Chromium 
• Mercury (Hg) 
• Cadmium (Cd) 
• Polybrominated biphenyls (PBB’s) 
• Polybrominated diphenyl ethers (PBDE’s) 

 

 

NOTE:

 Please read these instructions carefully and keep for future reference. The 

information in this document is subject to change without notice. For updates please refer 
to our website. 

NOTE:

 Follow the requirements for the installation of the product in accordance with the 

Specifications. Otherwise it may cause malfunction 

NOTE:

 Do not install the product in any location where oil, dust, iron powder, chemicals, or 

hydrogen sulphide may occur or affect the product. It may cause malfunction. 

This package contains the following items

Main unit: 

x 1 

EOL resistor:  

10k ohm x 2 

Alarm Resistor:  

680 ohm x 2 

Jumper:   

x 1 

Allen Key  

x 1 

Mounting Screws  M3.5 x 25mm x 2 (EV-2I1O Only) 
Manual:   

(this document) x 1 

General Description

 

The EV-2I1O (-EU) Dual Input / Single Output Module is an addressable input/output 
module with short circuit isolator. The module provides two supervised inputs (Class B) and 
one dry contact relay output rated at 5A@240Vac. The EV-2I1O uses UK 2-gang box with 
surface and flush mount options, and the EV-2I1O-EU uses European 503 electrical box 
flush-mounted.  

Two inputs are monitored to detect normal/input/open/short state, which can be used as 
general purpose inputs.   

The relay output is used for the control of equipment such as dampers and extractors for 
ventilation or smoke control system. The relay contact is monitored to detect the 
condition (on /off /relay stuck). 

 

 

 

 
 
 
 
 
 

 

EV-2I1O (-EU) – Dual Input 

Single Output Module with 

Isolator 

EN 54-17: 2005 / AC: 2007 – Short Circuit Isolators 

EN 54-18: 2005 / AC: 2007 – Input / Output Devices 

 

         

  

19 

 

0359 

 

For use with Nittan Evolution Protocol Only. 

Loop Voltage: 20 to 38 Vdc 

Quiescent Current: 720µA 

Alarm Current: 5.5mA 

Loop resistance

< 50 ohm/ km 

Input line resistance

::::

 < 50 ohm/ km 

EOL resistor: 10k ohm 

Input resistance: 470 ohm or 680 ohm 

Input threshold level: ON

< 680 ohm, 

                                      Short

<50 ohm,  

                                        Open

> 20k ohm 

Relay Contact rating: 5A at 240Vac 

                                                Or 5A at 30 Vdc 

Min sw open voltage (Vso min): 11 Vdc 

Max sw open voltage (Vso max): 14 Vdc 

Min sw close voltage (Vsc min): 3 Vdc 

Max sw close voltage (Vsc max): 10 Vdc 

Max line current (Ic max): 500 mA 

Max switching current (Is max): 1500 mA 

Max leakage current (Il max): 15 mA 

Max switch resistance (Zc max): 150 m

Ω

 

Wire size: Min. 0.75mm

2

 

                 Max. 2.5mm

2

 

Operating temperature: -10

°

C to 55

°

Storage temperature: -40

°

C to 80

°

Max. relative humidity: 95%RH, non-condensing 

Mass EV-2I1O: 175g 