De-icing
During periods of heavy frost all ventilation units with a heat exchanger with high level heat recovery
may develop ice in the heat exchanger.
Ice formation in the heat exchanger can be prevented with a pre-heating element for frost protection.
Service / De-icing
← De-icing
↳
Supply air de-icing
Settings:
Standard setting:
Description:
None / User / Low
User:
None: Indicates ceased supply air during de-icing.
User: Indicates user-defined supply air during de-icing.
Low: Indicates low level supply air during de-icing.
↳
T6 start de-icing
Settings:
Standard setting:
Description:
-10
↔
0 ºC
-2 ºC
Indicates at which evaporator temperature (T6) the
heat pump is to de-ice.
↳
T6 stop de-icing
Settings:
Standard setting:
Description:
2
↔
12 °C
6 °C
Indicates at which evaporator temperature (T6) de-
icing of the heat pump is to cease.
↳
T6 min. de-icing
Settings:
Standard setting:
Description:
10
↔
120 sec.
30 sec.
Indicates the maximum time allowed for de-icing the
evaporator.
↳
T6 max. de-icing
Settings:
Standard setting:
Description:
2
↔
12 °C
6 °C
Indicates the maximum time allowed for de-icing the
evaporator.
If de-icing has not been completed within the set time,
an alarm will be displayed and the unit will stop.
VPL28 (English)
BY NILAN
27