5.3 - Electrical protections
In the factory, a switching device can be integrated as an
option to the
Powerdrive MD2SL
.
The optional power switch integrated to the drive
doesn’t isolate the input busbars of the drive.
During the installation and maintenance operation
ensure that the supply line is open.
References and size of the options below, mounted in
a
Powerdrive MD2SL
, are detailed in the Leroy-Somer
Configurator : http://configurateurls.leroy-somer.com
5.3.1 - aR semi-conductor fuses
The aR semiconductor fuses limit the consequences of
an incident related to a short-circuit in the drive. They don’t
provide protection to the drive power line and must always be
associated with a protective device against overload located
upstream the line.
aR semiconductor fuses kits (optional Fu aR) are available for
Powerdrive MD2SL
.
5.3.2 - Line switch
A 3-pole switch is available for the Powerdrive MD2SL.
This option is used to isolate the motor from the AC
supply during maintenance operations.
• Fully visible break with padlockable handle on the front
of the drive cabinet (can be turned manually, padlock not
supplied)
•
Conforming to standard IEC/EN 60947-3
The QS3P switch must
always
be included in aR semi-
conductor fuse kits, in accordance with the table in section
3.1.5.
The QS3P switch is necessarily associated with
semiconductor aR fuses in compliance with table § 3.1.
Characteristics at 40°C in category AC21
I
th
= thermal current
Powerdrive MD2SL
rating
Switch
Reference
I
th
@
400V
(A)
I
th
@
690V
(A)
Number of
operations
180T & 220T
QS3P_400A
400
400
5 000
270TH & 340TH
270T & 340T
QS3P_630A
630
630
5 000
400TH to 600TH
400T
QS3P_800A
800
800
3 000
750TH
470T to 570T
QS3P_1000A
1000
800
3 000
750T
QS3P_1250A
1250
1000
4 000
900TH
900T
QS3P_1600A
1600
1000
4 000
1100T
QS3P_1800A
1800
1000
4 000
1400T & 1700T
Contact your local technical support.
1200TH to 1800TH
.
5.3.3 - Emergency stop
• MD2-AU1: SIL1/PLb protection device
The MD2-AU1 protection device consists of an emergency
stop wired on the STO inputs and mounted on the front.
• SIL3/PLe protection device
The
Powerdrive MD2SL
can be made compatible with
SIL3/PLe by incorporating a safety relay for double channel
locking.
Contact LEROY-SOMER.
5.4 - Heater kit
To prevent condensation in the
Powerdrive MD2SL
a self-
limited temperature heater is available as an option.
The intaller must provide ~230V single phase protection (fuse
rating indicated below) and ensure its control (the module
must be turned off when the drive is in operation).
5.5 - RFI filters
The use of RFI filters contributes to a reduction in the
emission levels of radio-frequency signals. They allow the
compliance of the
Powerdrive MD2SL
components with the
variable speed standard EN61800-3.
Depending on the drive and the application, install the RFI filter
recommended (available as option) between the mains and the
drive input.
CAUTION:
The specific design of these filters makes it possible
to connect to IT power supplies. The installer should,
however, ensure that insulation supervision systems
dedicated to these installations are suitable for
monitoring electrical equipment that may contain
electronic variable speed drives.