Z-Wave specIfIcatIon
12.6: INDICATOR COMMAND CLASS
Indicator CC - available indicators
Indicator ID – 0x50 (Identify)
Indicator CC - available properties
Property
ID
Description
Values and requirements
0x03
On/Off Periods
Starts toggling between ON and OFF
Used to set the duration of an On/Off period.
Available values:
• 0x00 .. 0xFF (0 .. 25.5 seconds)
If this is specified, the On/Off Cycles MUST
also be specified.
0x04
On/Off Cycles
Used to set the number of On/Off periods.
Available values:
• 0x00 .. 0xFE (0 .. 254 times)
• 0xFF (indicate until stopped)
If this is specified, the On/Off Period MUST
also be specified.
0x05
On time with-
in an On/Off
period
Used to set the length of the On time during
an On/Off period. It allows asymetic On/Off
periods.
Available values
• 0x00 (symmetric On/Off period – On time
equal to Off time)
• 0x01 .. 0xFF (0.1 .. 25.5 seconds)
Example: 300ms ON and 500ms OFF is
achieved by setting On/Off period (0x03) =
0x08 and On time within an On/Off Period
(0x05) = 0x03
This value is ignored if On/Off periods is not
defined.
This value is ignored if On/Off periods value
is less than this value.
Indicator CC - Identifying the gateway with LED signal
The gateway can be Identified using LED signal:
• FGHC3-001: the
LED indicator will blink green 3 times
(3 times: ON for 600ms, then OFF for 200ms)
• HC3L-001 / YH-001: the LED indicator will blink orange 3 times
(3 times: ON for 600ms, then OFF for 200ms)