compressor
•
internally controlled additional heat
•
tariff blocking (additional heat, compressor, heating,
cooling and hot water are disconnected)
Possible selections for AUX output
Indications
•
alarm
•
common alarm
•
cooling mode indication
•
holiday
•
away mode
Control
•
circulation pump for hot water circulation
•
external heating medium pump
•
ground water pump
•
external reversing valve for hot water
NOTE
The relevant distribution box must be marked with
a warning about external voltage.
Connecting external circulation pump
An external circulation pump is connected to the AUX out-
put, as illustrated below.
S1155PC External
1
2
3
N
O
C
N
C
AA2-X27
L N PE
L
N
PE
Settings
ELECTRICAL ADDITION - MAXIMUM OUTPUT
Number of steps, maximum electrical power and supply on
connection for the immersion heater varies depending on
model, see tables.
The electric additional heat may be restricted depending on
the selected country.
The immersion heater’s power is set in menu 7.1.5.1 - "Int
elec add heat".
Power steps of the immersion heater
The table(s) displays the total phase current for the immer-
sion heater.
In addition to this, there is the current for compressor oper-
ation.
3x400 V
Max phase
current L3(A)
Max phase
current L2(A)
Max phase
current L1(A)
Max electric-
al addition
(kW)
–
–
–
0.0
–
–
2.2
0.5
–
4.3
–
1.0
–
4.3
2.2
1.5
8.7
–
–
2.0
8.7
–
2.2
2.5
8.7
4.3
–
3.0
8.7
4.3
2.2
3.5
7.5
11.5
–
4.0
7.5
11.5
2.2
4.5
15.6
7.5
–
5.0
15.6
7.5
2.2
5.5
15.6
11.5
–
6.0
15.6
11.5
2.2
6.5
1
1 Factory setting
1x230 V
Max phase current L1(A)
Max electric-
al addition
(kW)
–
0.0
2.2
0.5
4.3
1.0
6.5
1.5
8.7
2.0
10.9
2.5
13.0
3.0
15.2
3.5
17.4
4.0
19.6
4.5
1
1 Factory setting
When the current sensors are connected, S1155PC monitors
the phase currents and allocates the power steps automat-
ically to the least loaded phase.
NOTE
If the current sensors are not connected, S1155PC
calculates how high the currents will be if the rel-
evant power steps are added. If the currents are
higher than the set fuse size, the power step is not
allowed to cut in.
25
Chapter 5 | Electrical connections
NIBE S1155PC