Connections
TERMINAL BLOCKS
The following terminal blocks are used on the base board
(AA2).
-X29
-X28
0-5V 1
+5V 2
AUX1 3
AUX2 4
AUX3 5
AUX4 6
AUX5 7
AUX6 8
AUX7 9
AUX8 10
BT6 11
BT25 12
1
1
2
3
2
3
4
5
6
7
8
9
10
11
12
GND
+12V
B
A
OT+
OT−
0-5V
PWM0
PWM1
CPU
EXT COM
INT COM
ERROR
POWER
+5V
GND
BE1
BE2
BE3
K1
0
-X2
7
NO
O
NC
A
UX-R
ELA
Y
BT50 13
BT1 14
-X30
AA2
X1
X5
X6-2
X6-1
X7-2
X9
POWER CONNECTION
Supply voltage
Enclosed cable for incoming supply electricity is connected
to terminal block X1 and X6-1 on the PCB (AA2).
Connection 3x400V
AA2-X1
AA2-X6-1
PE
N
L1 L2 L3
1
2
3
4
Connection 1x230V
AA2-X1
PE
N
L (L) (L)
1
2
3
4
AA2-X6-1
If separate supply to the compressor and immersion heater
is required, see section "
External blocking of functions
" ".
Tariff control
If the voltage to the immersion heater and/or compressor
is lost for a period, this must be blocked at the same time
via the selectable inputs, see section "
puts – Possible selections for AUX inputs
".
External control voltage for the control
system
NOTE
Mark up any junction boxes with warnings for ex-
ternal voltage.
Control voltage (230 V ~ 50Hz) connects to AA2:X5:N, X5:L
and X6-2 (PE).
When connecting external control voltage, remove the
bridges from terminal block X5.
L
N
1.
2.
3.
4.
X5
19
Chapter 5 | Electrical connections
NIBE S1155PC
Содержание S1155PC