INSTALLATION INSTRUCTIONS

ETS 12 / 121

Electrical addition

Heatpumps are not usually dimensioned to handle the
entire heat output requirement. Some form of addi-
tional output is necessary on cold days.
ETS 12 / 121 consists of an immersion heater with a
contactor set comprising of a thermostat and tempera-
ture limiter. The contactor set is designed for installa-
tion in the electrical connection area on FIGHTER
1110/1115/1120. 
This accessory makes it possible to use the Extra hot
water function when a water heater is connected via
the accessory VST 11.
FIGHTER 1110/1115: The function is activated from
menu 14, see the Installation and Maintenance
Instruction.
FIGHTER 1120: The function is activated from menu
9.2.13.2, see the Installation and Maintenance
Instruction.
ETS 12 for 3-phase. Part no 089 399 
ETS 121 for 1-phase. Part no 089 419

General

ETS 12 / 121

Components

LEK 

67

20

10

25

3

24

23

141

142

145

143

144

140

L

E

K

3

Operating thermostat, standby mode

10

Contactor, immersion heater step 1

20

Contactor plate with components

23

Protective housing, immersion heater

24

Immersion heater 

25

Temperature limiter

67

Contactor, immersion heater step 2

140

Cover

141

Seal

142

Knob

143

Cable ties, 4

144

Screws, 4

145

Assembly screws, 4

List of components

NOTE! 

The electrical installation must be

carried out by a qualified electrician.

The electrical installation and wiring
must conform to current regulations.

NOTE! 

Reset the temperature limiter (25).

It may have tripped during transport.

In the event of a fault on the heat pump's control or
collector circuit you can move the switch (8) to stand-
by mode. Only the heating medium pump and electri-
cal step 2 are activated in this mode. Heat for hot tap
water can not be produced as VST 11 is not active.
The flow temperature is controlled by the thermostat
(3). This needs to be set at an appropriate tempera-
ture depending on the type of heating system and out-
door temperature.
NOTE! When the operating option “fixed condensing”
is selected on FIGHTER 1110/1115, the heating medi-
um pump is not operational.

Standby mode

Содержание ETS 121

Страница 1: ...4 140 L E K 3 Operating thermostat standby mode 10 Contactor immersion heater step 1 20 Contactor plate with components 23 Protective housing immersion heater 24 Immersion heater 25 Temperature limite...

Страница 2: ...t the contactor set s supply wires 4 x 2 5 mm to terminal 22 in the electrical con nection area G Route the immersion heater wires 7 x 2 5 mm through the cable entry to the immersion heater H Route th...

Страница 3: ...ring diagram FIGHTER 1110 1115 Anslutes i X22 032 033 034 035 LEK 2 2 1 R 0 X9 K10 X22 B3 D25 K69 K67 Connected to the relay board Connected to X22 Immersion heater Immersion heater step 2 Immersion h...

Страница 4: ...Connect the contactor set s supply wires 4 x 2 5 mm to terminal X9 F Route the immersion heater wires 7 x 2 5 mm through the cable entry to the immersion heater G Route the temperature limiter and the...

Страница 5: ...phase Anslutes i X6 och K69 032 033 034 021 022 023 026 027 024 025 032 033 034 035 X9 K10 X6 B3 D25 K69 K67 Connected to X9 Connected to X9 Connected to X6 and K69 Immersion heater Immersion heater...

Страница 6: ...h K69 032 033 034 035 037 021 022 023 026 027 024 025 Wiring diagram FIGHTER 1120 ETS 121 1 phase K69 X9 K10 K67 X6 B3 D25 Connected to X9 Connected to X6 and K69 Immersion heater Immersion heater ste...

Страница 7: ...own brown 7 White connection blue blue blue blue white blue 9 Red connection FIGHTER 1110 1115 FIGHTER 1120 jumper Current step 2 6 kW 8 7 A 4 kW 15 A 4 kW 18 A Voltage 3 x 400 V N 3 x 230 V 230 V 1 p...

Страница 8: ...274 697 40 E mail info haato com www haato fi NIBE Systemtechnik GmbH Am Reiherpfahl 3 29223 Celle Tel 05141 7546 0 Fax 05141 7546 99 E mail info nibe de www nibe de NIBE Energietechniek B V Steenpad...

Отзывы: