If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Caution
Also see the Operating Manual for GreenMas-
ter-HP.
Start guide
The start guide appears at first start-up after installation,
but is also available in menu 5.7.
Menu system
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 1.1.1 - heating
Make settings for room temperature here.
Menu 1.9.1.1 - heating curve
Make settings for your own heating curve here.
Menu 3.1 - service info
Here you will find temperatures and other operating in-
formation for GreenMaster-HP.
Menu 5.1.7 - br pmp al set.
Make settings for the brine alarm in GreenMaster-HP
here.
Menu 5.1.9 - brine pump speed
Set the speed of the brine pump in GreenMaster-HP
here.
Menu 5.1.11 - pump speed heating medium
Set the speed of the heating medium pump in GreenMas-
ter-HP here.
Menu 5.1.14 - flow set. climate system
Make settings for the flow in the climate system here.
Menu 5.2.4 - accessories
Activate the air treatment unit here.
Activate: GreenMaster-HP
Menu 5.3.22 - greenmaster C-F
Make operating settings for GreenMaster-HP in this
menu.
months btwn filter alarms
Set the number of months between filter changes in
GreenMaster-HP here.
Setting range: 1–24
Factory setting: 12
type of fire alarm
Make settings for the fire alarm in GreenMaster-HP here.
Setting range: 1/2
Default value: 1
Fire alarm type 1
■
The exhaust air damper (QM40) closes
■
The fire bypass damper (QM41) opens
■
Exhaust air fan (GQ2) runs at fixed fire flow, which is
set in menu 5.3.22.
Fire alarm type 2
■
Exhaust air fan (GQ2) stops
■
The exhaust air damper (QM40) closes
fire flow
Make settings here for the speed at which the fan will
run in the event of fire.
Setting range: 0–100%
Factory setting: 70%
set point
Make settings for the control’s set point value here.
Setting range: 0–400 Pa
Factory setting: 150 Pa
min fan speed
Setting range: 1–99%
Factory setting: 10%
TIP
If both settings are set to the same value, the
fan operates at fixed speed.
max fan speed
Setting range: 2–100%
Factory setting: 100%
filt. alarm press.
Make settings for alarm for a clogged filter here. When
the set value is exceeded, an alarm is triggered.
Setting range: 100–300 Pa
Factory setting: 150 Pa
QM41 motion interval
Set the interval in days for how often the fire damper
(QM41) is to be actuated here.
Setting range: 1–30
Default value: 14
start manual motion QM41
yes/no
37
Chapter 7 |
Control - menus
GreenMaster-HP
7 Control - menus