utility by selecting
Start»All Programs»National Instruments»NI-RIO»RIO Device
Setup
.
Powerup Option
Behavior
Do Not Autoload VI
Does not load the FPGA bit stream from flash memory.
Autoload VI on device powerup Loads the FPGA bit stream from flash memory to the FPGA when
the chassis powers on.
Table 2. Chassis Powerup Options
If you want the NI-9154 to autoload and run a VI at powerup, you must also
configure the VI to autoload before you compile it. For more information about
autoloading VIs, refer to the LabVIEW FPGA Module Help.
Checking MXI-Express LINK LEDs for Status
After powering on the chassis and host system, check the MXI-Express LINK LEDs to
ensure that all connected systems are linked and communicating properly. The MXI-
Express LINK LEDs of the NI-9154 indicate the following:
LINK LED Appearance
Meaning
Off
Chassis power is off.
Solid yellow
Link is not established.
Solid green
Link is established.
Blinking yellow
PCI Express clock is incompatible with NI-9154
Table 2. NI-9154 MXI-Express LINK LED Indications
Note
For information about PCI Express clock compatibility with the
NI-9154, go to
and enter the Info Code 915xclock.
Powering Down the MXI-Express System
Always power down the host system before powering down any connected NI-9154
chassis. When the host system is powered down, the order in which the NI-9154
chassis are powered down is not important.